SETUP AND PROCEDURES BEFORE OPERATION
(2) Operating procedure
Start the settings with GX Developer I/O assignment setting window.
(a)
I/O assignment setting window
Set the following for the slot in which the A/D
converter module is mounted.
The type setting is required; set other items as
needed.
Type
:
Select "intelli."
Model name
:
Enter the module model name.
Points
:
Select 16 points.
Start
:
Enter the start I/O number for
the A/D converter module.
Detailed
:
Specify the control PLC for the
setting
A/D converter module.
It is unnecessary to set the
"Error time output mode" or "H/
W error time PLC operation
mode" since these settings are
invalid for the A/D converter
module.
(b)
Switch setting for intelligent function module win-
dow
Click on [Switch setting] on the I/O assignment
setting window to display the window shown at
left, then set switches 1 to 5.
The switches can easily be set if values are
entered in hexadecimal. Change the entry format
to hexadecimal and then enter the values.
4.5 Intelligent Function Module Switch Setting
1
2
3
4
5
6
7
8
4
- 13