Ch[ ] Maximum Value/Minimum Value Storage Area (Un\G30 To Un\G45); Input Signal Error Detection Extended/Input Signal Error Detection Setting (Un\G47) - Mitsubishi Electric Q68AD-G User Manual

Channel isolated analog-digital converter module/ channel isolated analog-digital converter module (with signal conditioning function)
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.10
CH[
Un\G45)
(1) For each channel, the maximum and minimum values of the converted digital values
are stored in this area every sampling time in 16-bit signed binary.
(2) The stored values for all channels will be cleared to 0 when the operating condition
setting request (Y9) is set to ON and the setting is changed or when the maximum
value/minimum value reset request (YD) is set to ON.
(3) For the channel where averaging processing is specified also, the maximum and
minimum values of the digital values from sampling processing are stored in this area.
(4) When the scaling function is enabled, maximum/minimum values after scaling
conversion are stored.
3.4.11 Input signal error detection extended/input signal error detec-
tion setting (Un\G47)
(1) This area is used to set whether the input signal error detection, process alarm, or
rate alarm will be enabled or disabled for each channel.
If the warning of input signal error detection is enabled, the input signal error detection
can be performed by setting the same value of upper and lower limit or different value
of upper and lower limit.
(2) To validate the input signal error detection extended/input signal error detection
setting, the operating condition setting request (Y9) must be turned ON/OFF. (Refer to
Section 3.3.2.)
(3) All channels for the input signal error detection and all channels for the input signal
error detection extended setting are set to the same value of upper limit and lower
limit as the default setting.
Un\G47

3.4.10 CH[ ] maximum value/minimum value storage area (Un\G30 to Un\G45)

]
maximum value/minimum value storage area (Un\G30 to
b15 b14 b13 b12 b11
CH8 CH7 CH6 CH5
CH4 CH3 CH2 CH1
Input signal error detection extended setting
0: Same upper limit value/lower limit value,
1: Different upper limit value/lower limit value
For Q66AD-DG, information of b6, b7, b14, b15 is fixed at 0.
b10
b9
b8
b7
b6
b5
CH8 CH7 CH6 CH5
Input signal error detection setting
0: Enable, 1: Disable
3.4 Buffer Memory
b4
b3
b2
b1
b0
CH4 CH3 CH2 CH1
3
- 62
1
2
3
4
5
6
7
8