7.3.6 When user range setting is used and initial setting was made with sequence program (other system is
When user range setting is used and initial setting was made
with sequence program (other system is unavailable)
(a) Set the A/D conversion enable/disable setting (Un\G0) for all channel conversion
disable and turn operating condition setting request (Y9) from OFF to ON to stop
conversion.
After confirming that conversion has stopped with the A/D conversion completion
flag (Un\G10), turn off Operation Condition Setting Request (Y9).
(The window shows the setting example of the Q68AD-G.)