Mitsubishi Electric Q68AD-G User Manual page 161

Channel isolated analog-digital converter module/ channel isolated analog-digital converter module (with signal conditioning function)
Table of Contents

Advertisement

6
PROGRAMMING
(2) Intelligent function module switch setting
Based on the setting conditions given in Section 6.2 (2), make the intelligent function
module switch settings.
(a) Each switch setting
(b) Write the settings in (a) to the Q68AD-G.
1) Switch1,Switch2: Input range setting
<Switch 2>
<Switch 1>
0
0
0
0
0
0
H
CH8 CH7
CH6 CH5
CH4 CH3 CH2 CH1
2) Switch3: Empty (No setting required)
3) Switch4: Mode setting
<Switch 4>
0
F
0
0
H
Fixed at 0
4) Switch5: Use prohibited (0
<Switch 5>
0
0
0
0
H
*1:If any other than 0
is set to Switch 5, an error occurs.
H
On GX Developer's "Parameter setting" window, select the "I/O assignment" tab,
click "Switch setting", and make settings of Switch 1 to 5 on the window shown
below.
6.2 For Use in Normal System Configuration (Q68AD-G)
0
0
H
CH1 to CH3: 0H(4 to 20mA input)
CH4 to CH8: 0H(default)
Setting of normal resolution mode/high resolution mode
All channels: FH(High resolution mode)
Setting of normal mode / Offset/gain setting mode
All channels: 0H(normal mode)
*1
:fixed
)
H
Fixed at 0
6.2.1 Before creating a program
1
2
3
4
5
6
7
8
6