For Use In Normal System Configuration (Q66Ad-Dg) - Mitsubishi Electric Q68AD-G User Manual

Channel isolated analog-digital converter module/ channel isolated analog-digital converter module (with signal conditioning function)
Table of Contents

Advertisement

6
PROGRAMMING
6.4

For Use in Normal System Configuration (Q66AD-DG)

(1) System configuration
(2) Conditions for the intelligent function module switch setting
(3) Program conditions
6.4 For Use in Normal System Configuration (Q66AD-DG)
6
- 21
CH1 external device
CH2 external device
CH3 external device
Input range setting
CH1
4 to 20mA
CH2
(For 2-wire transmitter
CH3
input)
CH4
to
not used
CH6
(a) The following averaging processing specification is used for each channel.
• CH1: Sampling processing
• CH2: Time averaging (50 times)
• CH3: Primary delay filtering (100ms)
(b) CH1 uses the input signal error detection function (Refer to Section 3.2.3.)
• Input signal error detection: 10%
(c) CH2 uses the warning output setting (process alarm) (Refer to Section 3.2.4 (1).)
• Process alarm lower lower limit value: 1000
• Process alarm lower upper limit value: 1500
• Process alarm upper lower limit value: 6000
• Process alarm upper upper limit value: 7000
(d) CH3 uses the warning output setting (rate alarm) (Refer to Section 3.2.4 (2).)
• Rate alarm warning detection period : 50ms
• Rate alarm upper limit value: 0.3%
• Rate alarm upper limit value: 0.1%
(e) In the event of a write error, an error code shall be displayed in BCD format.
The error code shall be reset after removal of the cause.
QY10
(Y20 toY 2F)
QX10
(X10 to X1F)
Q66AD-DG
Normal resolution mode/ High resolution mode
High resolution mode
-
(X/Y0 to X/YF)

Hide quick links:

Advertisement

Table of Contents
loading