Power Supply - AEMC 8335 User Manual

Powerpad 3-phase power quality analyzer
Hide thumbs Also See for 8335:
Table of Contents

Advertisement

Nominal Range
Measurement Range
Probe Output Signal*
Sensor
Safety
*Output is proportional to the amplitude and frequency of the measured current.
NOTE: Currents <10A will be displayed as zero. Neutral current measures down to 0A.
Nominal Range
Measurement Range
Probe Output Signal*
Sensor
Safety
*Output is proportional to the amplitude and frequency of the measured current.
NOTE: Currents <10A will be displayed as zero. Neutral current measures down to 0A.

3.2.6 Power Supply

AC Power (external power supply)
Operating Range: 230V
Max Power: 40VA
Battery Power
(allows use in the event of an interruption)
Type: NiMH 4000mAh min
Rated Voltage: 9.6V
Charge Time: 5 hrs approx
Battery Life: 10 hrs (completely charged) approx
Operating Temperature: 32° to 122°F (0° to 50°C)
Recharging Temperature: 50° to 104°F (10° to 40°C)
Storage Temperature: -4 to +122°F (-20 to +50°C) for ≤ 30 days
When the charger is connected, the battery starts to charge and the ON/OFF
button will stay illuminated. Once the battery is charged, the instrument
uses the current supplied by the power supply, without drawing from the
battery.
Power Quality Analyzer Model 8335
AmpFlex
3000A
AC
10A to 6500A
140mV
/3000A
AC
Length = 24" (610mm); Ø = 7.64" (190mm)
Length = 36" (910mm); Ø = 11.46" (290mm)
EN 61010-2-032, Pollution Degree 2, 600V CAT IV, 1000V CAT III
MiniFlex
1000A
AC
10A to 1000A
47µV
/1000A
AC
Length = 10" (250mm); Ø = 2.75" (70mm)
EN 61010-2-032, Pollution Degree 2, 600V CAT IV, 1000V CAT III
± 10% @ 50Hz and 120V
AC
35 hrs (recording in progress) approx
Sensors
®
AC
at 60Hz
AC
Sensors
AC
at 60Hz
AC
± 10% @ 60Hz
AC
23

Advertisement

Table of Contents
loading