2.2 Key Features
•
Measurement of TRMS voltages up to 1000Vrms AC/DC for two, three,
four or five-wire systems
•
Measurement of TRMS currents up to 6500Arms (sensor dependent)
•
Measurement of DC current up to 1400A
•
Automatic probe detection and calibration
•
Frequency measurement (40 to 69Hz systems)
•
Direct measurement of neutral current for WYE configurations
•
Record and display trend data as fast as once per second for one month
for up to 25 variables. It is recommended to limit recordings to under
100MB.
•
Energy assessments
•
Transient detection on all V and I inputs
•
Inrush current
•
Calculation of Crest Factors for current and voltage
•
Calculation of the K Factor for transformers
•
Calculation of short-term flicker for voltage
•
Calculation of the phase unbalance for voltage and current
(3 phase only)
•
Measurement of harmonic angles and rates (referenced to the funda-
mental or RMS value) for voltage, current or power, up to 50th harmonic
•
Display of harmonic sequencing and direction
•
Calculation of overall harmonic distortion factors
•
Real time display of Phasor diagrams including values and phase
angles
•
Monitoring of the average value of any parameter, calculated over a
period running from 1 sec to 2 hrs
•
Measurement of active, reactive and apparent power per phase and
their respective sum total
•
Calculation of power factor, displacement power factor and tangent
factor
•
Total power from a point in time, chosen by the operator
•
Recording, time stamping and characterization of disturbance (swells,
sags and interruptions, exceedance of power and harmonic thresholds)
•
Detection of transients and recording of associated waveforms.
•
Color-coded input tags to identify voltage and current inputs to local
standards.
•
2GB internal memory
•
DataView
and analysis and report generation.
Power Quality Analyzer Model 8335
software included for downloading measurements, storage,
®
(with MR193 probe)
DC
11