Function
Factor K
Unbalance
(three phase network)

3.2.4 Current Probe Accuracy

Sensor Type
MR193
1000A
SR193
1000A
AmpFlex
®
3000A
MiniFlex
1000A
MN93
200A
MN193
100A
MN193
5A
5A
Adapter
N.S. = Not Specified
Power Quality Analyzer Model 8335
Measurement Range
Minimum
Maximum
1
0%
TRMS Current
[1A; 10A]
[10A; 100A]
[100A; 800A]
[800A; 1200A]
[1200A; 1400A]
[1A; 3A]
[3A; 10A]
[10A; 100A]
[100A; 1200A]
[10A; 100A]
[100A; 6500A]
[10A; 100A]
[100A; 1000A]
[0.5A; 2A]
[2A; 10A]
[10A; 100A]
[100A; 240A]
[100mA; 300mA]
[300mA; 1A]
[1A; 120A]
[5mA; 50mA]
[50mA; 500mA]
[500mA; 6A]
[5mA; 50mA]
[50mA; 6A]
Resolution
99.99
0.01
100%
0.1%
(to be added to the PowerPad
Accuracy on IRMS
±(1.5% + 1A)
±(3%)
±(5%)
±(0.8%)
±(0.3%)
±(0.2%)
±(3%)
±(2%)
±(3%)
±(2%)
±(3% + 1A)
±(2.5% + 1A)
±(1% + 1A)
±(0.7% + 2mA)
±(0.7%)
±(1% + 0.1mA)
±(1%)
±(0.7%)
±(1%)
±(0.5%)
Accuracy
±(5%)
±(1%)
's accuracy)
®
Accuracy on φ
N.S.
±(2°)
±(1.5°)
N.S.
±(1°)
±(0.5°)
±(0.3°)
±(1°)
±(0.5°)
±(1°)
±(0.5°)
N.S.
±(6°)
±(3°)
±(2°)
N.S.
±(1.5°)
±(0.7°)
±(1.7°)
±(1°)
±(1°)
±(0°)