Electrical Connection
Current Probe
Trend (Recording) Mode
Alarm Mode
Erase Memory
About
4.3.1 Electrical Hookup (electrical network)
• Highlight Electrical Hook-up using the ▲ and ▼ buttons, then press the
button.
• Choose the hookup type using the arrow buttons.
• Press the
button to apply the new hookup selection.
Power Quality Analyzer Model 8335
Determines the type of connection to the network (see § 4.3.1)
•
Single-Phase
•
Split-Phase
•
3-Phase 4-Wire
•
3-Phase 5-Wire
Defines the type of current probe to connect (see § 4.3.2)
•
MN93: 200A
•
MN193: 100A or 5A (with variable ratio)
•
SR193: 1000A
•
AmpFlex
Sensors: 3000A (measures up to 6500Arms)
®
•
MiniFlex
Sensors: 1000A
™
•
MR193: 1000A
AC
•
5A three-phase adapter (3-channel only)
Selects the parameters to record (see § 4.3.3)
Defines the parameters of an alarm (see § 4.3.4)
Deletes configurations, alarm settings, snapshots and recordings
(see § 4.3.5)
Displays the serial number, software and hardware version
Figure 4-3
/1400A
DC
31