Electrical Specifications; Environmental Requirements - Oracle sun X4-8 Installation Manual

Hide thumbs Also See for sun X4-8:
Table of Contents

Advertisement

Server Specifications

Electrical Specifications

The following table lists the electrical specifications for the Sun Server X4-8.
Note -
and navigate to the Sun Server X4-8 page:
http://www.oracle.com/technetwork/server-storage/sun-x86/overview/index.html
Parameter
Nominal input frequencies
Operating input voltage range
Rated input current
Maximum power consumption
Maximum heat output

Environmental Requirements

The following table lists the environmental requirements for the Sun Server X4-8.
Parameter
Operating temperature (single, non-rack system)
Operating temperature
Non-operating temperature
Operating humidity
Non-operating humidity
Operating altitude
Non-operating altitude
Acoustic noise
32
Sun Server X4-8 Installation Guide • December 2015
For up-to-date information on power consumption, go to the Sun x86 Servers web site
Value
50/60 Hz
200-240 VAC
23A @ 200 to 230 VAC
12A max per cord
3400 W
11600 BTU/Hr
Value
At sea level: 5° C to 35° C (41° F to 95° F)
At altitude: 5° C to 31° C (41° F to 88° F)
5° C to 35° C (4° F to 95° F)
-40 °C to 70 °C (-40 °F to 158° F)
10% to 90% relative humidity, non-condensing
Up to 93% relative humidity, non-condensing
Up to 3,000 m (9,840 ft), maximum ambient temperature
is derated by 1 degree C per 300m above 900 m, except
in China where regulations may limit installations to a
maximum altitude of 2,000 m
0 m to 12,000 m (0 ft to 40,000 ft)
Acoustic noise: 7.7 B operating, 6.8 B idling - (LwAd: 1
B=10 dB)

Advertisement