Electrical Specifications
Use these specifications only as a general planning guide. To determine power values based on
expected workloads, use the SPARC T8-4 power calculator at:
http://www.oracle.com/goto/powercalculators/
Description
Operating input range
Maximum operating input current at 200 VAC (per cord)
Maximum operating input power at 200 VAC
Actual amperage draw may exceed rating by no more than 10%.
The maximum operating input current values are based on the formula P / (V *0.90),
Note -
where P = maximum operating input power and V = input voltage. For example: 620W / (100V
* 0.90) = 6.89A You can use this formula to calculate the maximum operating current at your
input voltage.
Caution -
18
SPARC T8-4 Server Installation Guide • September 2017
Use only the power cords provided with the server.
Metric
U.S.
610 mm
24 in.
978.4 mm
38.87 in.
610 mm
24 in.
Value
200 to 240 VAC,
50/60 Hz
12.6 A
5040 W