Electrical Specifications

Description
Minimum service clearance
(front)
Minimum service clearance
(rear)
Minimum airflow clearance
(front)
Minimum airflow clearance
(rear)
Related Information
"Server Overview" on page 12
"Handling Precautions" on page 25
"Installing the Server" on page 29
"Electrical Specifications" on page 18
"Environmental Requirements" on page 19
"Airflow Precautions" on page 21
Electrical Specifications
Use these specifications only as a general planning guide. To determine power values based on
expected workloads, use the SPARC T7-4 power calculator at:
http://www.oracle.com/goto/powercalculators/
Description
Operating input range
Maximum operating input current at 200 VAC (per cord)
Maximum operating input current at 200 VAC (all inputs)
Maximum operating input power at 200 VAC
Maximum heat dissipation
Maximum standby power
18
SPARC T7-4 Server Installation Guide • March 2017
Metric
914.4 mm
914.4 mm
50.8 mm
76.2 mm
U.S.
36 in.
36 in.
2 in.
3 in.
Value
200 to 240 VAC,
50-60 Hz
16 A
22.9 A
4498 W
15,348 BTU/hr
(16,193 KJ/hr)
105 W

Advertisement