Lenovo System x3300 M4 Installation And Service Manual page 386

Machine type: 7382
Hide thumbs Also See for System x3300 M4:
Table of Contents

Advertisement

2. Replace power supply n. (n = power supply number)
• 80070208-0a01ffff : Sensor [SensorElementName] has transitioned to critical from a less severe
state. (PS 1 Therm Fault)
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702080a01ffff or 0x800702080a01ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Power
SNMP Trap ID
4
CIM Information
Prefix: PLAT ID: 0522
User Response
1. Make sure that there are no obstructions, such as bundled cables, to the airflow from the
power-supply fan.
2. Use the IBM Power Configurator utility to ensure current system power consumption
is under limitation. For more information and to download the utility, go to
http://www-03.ibm.com/systems/bladecenter/resources/powerconfig.html.
3. Replace power supply n. (n = power supply number)
• 80070208-0a02ffff : Sensor [SensorElementName] has transitioned to critical from a less severe
state. (PS 2 Therm Fault)
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702080a02ffff or 0x800702080a02ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
372
System x3300 M4 Installation and Service Guide

Advertisement

Table of Contents
loading

Table of Contents