2. Replace power supply n. (n = power supply number)
• 80070208-0a01ffff : Sensor [SensorElementName] has transitioned to critical from a less severe
state. (PS 1 Therm Fault)
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702080a01ffff or 0x800702080a01ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Power
SNMP Trap ID
4
CIM Information
Prefix: PLAT ID: 0522
User Response
1. Make sure that there are no obstructions, such as bundled cables, to the airflow from the
power-supply fan.
2. Use the IBM Power Configurator utility to ensure current system power consumption
is under limitation. For more information and to download the utility, go to
http://www-03.ibm.com/systems/bladecenter/resources/powerconfig.html.
3. Replace power supply n. (n = power supply number)
• 80070208-0a02ffff : Sensor [SensorElementName] has transitioned to critical from a less severe
state. (PS 2 Therm Fault)
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702080a02ffff or 0x800702080a02ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No