GE G60 Instruction Manual page 48

Ur series generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

2.2 SPECIFICATIONS
PHASE/NEUTRAL/GROUND IOC
Pickup level:
Dropout level:
Level accuracy:
0.1 to 2.0 × CT rating: ±0.5% of reading or ±0.4% of rated
> 2.0 × CT rating
2
Overreach:
Pickup delay:
Reset delay:
Operate time:
Timer accuracy:
PHASE DIRECTIONAL OVERCURRENT
Relay connection:
Quadrature voltage:
Polarizing voltage threshold: 0.000 to 3.000 pu in steps of 0.001
Current sensitivity threshold: 0.05 pu
Characteristic angle:
Angle accuracy:
Operation time (FlexLogic operands):
NEUTRAL DIRECTIONAL OVERCURRENT
Directionality:
Polarizing:
Polarizing voltage:
Polarizing current:
Operating current:
Level sensing:
Restraint, K:
Characteristic angle:
Limit angle:
Angle accuracy:
Offset impedance:
Pickup level:
Dropout level:
Operation time:
2-16
0.000 to 30.000 pu in steps of 0.001
97 to 98% of pickup
(whichever is greater)
±1.5% of reading
<2%
0.00 to 600.00 s in steps of 0.01
0.00 to 600.00 s in steps of 0.01
<16 ms at 3 × pickup at 60 Hz
(Phase/Ground IOC)
<20 ms at 3 × pickup at 60 Hz
(Neutral IOC)
±3% of operate time or ±1/4 cycle
(whichever is greater)
°
90
(quadrature)
ABC phase seq.: phase A (V
), phase
BC
B (V
), phase C (V
); ACB phase
CA
AB
seq.: phase A (V
), phase B (V
CB
AC
phase C (V
)
BA
°
0 to 359
in steps of 1
±2°
Tripping (reverse load, forward fault):<
12 ms, typically
Blocking (forward load, reverse fault):<
8 ms, typically
Co-existing forward and reverse
Voltage, Current, Dual, Dual-V, Dual-I
V_0 or VX
IG
I_0
3 × (|I_0| – K × |I_1|), IG
0.000 to 0.500 in steps of 0.001
–90 to 90° in steps of 1
40 to 90° in steps of 1, independent for
forward and reverse
±2°
0.00 to 250.00 Ω in steps of 0.01
0.002 to 30.000 pu in steps of 0.01
97 to 98%
<16 ms at 3 × pickup at 60 Hz
G60 Generator Protection System
NEGATIVE SEQUENCE DIRECTIONAL OC
Directionality:
Polarizing:
Polarizing voltage:
Operating current:
Level sensing:
Restraint, K:
Characteristic angle:
Limit angle:
Angle accuracy:
Offset impedance:
Pickup level:
Dropout level:
Operation time:
GENERATOR UNBALANCE
Gen. nominal current:
Stages:
),
Pickup level:
Dropout level:
Level accuracy:
0.1 to 2 x CT rating:
> 2.0 x CT rating:
Time dial (K-value):
Pickup delay:
Reset delay:
Timer accuracy:
Operate time:
SPLIT PHASE PROTECTION
Operating quantity:
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Timer accuracy:
Operate time:
SENSITIVE DIRECTIONAL POWER
Measured power:
Number of stages:
Characteristic angle:
Calibration angle:
Minimum power:
Pickup level accuracy:
Hysteresis:
Pickup delay:
Timer accuracy:
Operate time:
2 PRODUCT DESCRIPTION
Co-existing forward and reverse
Voltage
V_2
I_2
Zero-sequence:|I_0| – K × |I_1|
Negative-sequence:|I_2| – K × |I_1|
0.000 to 0.500 in steps of 0.001
0 to 90° in steps of 1
40 to 90° in steps of 1, independent for
forward and reverse
±2°
0.00 to 250.00 Ω in steps of 0.01
0.015 to 30.000 pu in steps of 0.01
97 to 98%
<16 ms at 3 × pickup at 60 Hz
0.000 to 1.250 pu in steps of 0.001
2
2 (I
t with linear reset and definite time)
0.00 to 100.00% in steps of 0.01
97 to 98% of pickup
±0.5% of reading or 1% of rated
(whichever is greater)
±1.5% of reading
0.00 to 100.00 in steps of 0.01
0.0 to 1000.0 s in steps of 0.1
0.0 to 1000.0 s in steps of 0.1
±3% of operate time or ±20 ms, which-
ever is greater
<50 ms at 60 Hz
split phase CT current biased by genera-
tor load current
0.020 to 1.500 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading or ±1% of rated
0.000 to 65.535 s in steps of 0.001
±3% of operate time or ±5 cycles, which-
ever is greater
<5 cycles at 1.10 × pickup at 60 Hz
3-phase, true RMS
2
0 to 359° in steps of 1
0.00 to 0.95° in steps of 0.05
–1.200 to 1.200 pu in steps of 0.001
±1% or ±0.001 pu, whichever is greater
2% or 0.001 pu, whichever is greater
0 to 600.00 s in steps of 0.01
±3% of operate time or ±1/4 cycle
(whichever is greater)
<50 ms