5 SETTINGS
should be set to "15". Note that these settings are the deadband default values. DNP object 34 points can be used to
change deadband values, from the default, for each individual DNP analog input point. Whenever power is removed and
re-applied to the G60, the default deadbands will be in effect.
The
DNP TIME SYNC IIN PERIOD
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The
DNP MESSAGE FRAGMENT SIZE
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to be
necessary which can provide for more robust data transfer over noisy communication channels.
When the DNP data points (analog inputs and/or binary inputs) are configured for Ethernet-enabled relays, check
the "DNP Points Lists" G60 web page to view the points lists. This page can be viewed with a web browser by enter-
ing the G60 IP address to access the G60 "Main Menu", then by selecting the "Device Information Menu" > "DNP
NOTE
Points Lists" menu item.
The
DNP OBJECT 1 DEFAULT VARIATION
default variation number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation
response when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Refer to the DNP implementation section in
appendix E for additional details.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the G60 relay, DNP binary outputs are mapped to virtual inputs. However,
some legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to sup-
port the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the
DNP master can operate a single point for both trip and close, or raise and lower, operations. The G60 can be configured to
support paired control points, with each paired control point operating two virtual inputs. The
setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired oper-
TROL POINTS
ate on a one-to-one basis.
The
DNP TCP CONNECTION TIMEOUT
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be
aborted by the G60. This frees up the connection to be re-used by a client.
Relay power must be re-cycled after changing the
effect.
NOTE
j) DNP / IEC 60870-5-104 POINT LISTS
PATH: SETTINGS
PRODUCT SETUP
 DNP / IEC104
 POINT LISTS
MESSAGE
The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can
configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning
FlexLogic operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
 BINARY INPUT / MSP
 POINTS
MESSAGE
MESSAGE
GE Multilin
setting determines how often the Need Time Internal Indication (IIN) bit is set by the G60.
setting determines the size, in bytes, at which message fragmentation occurs. Large
to
DNP OBJECT 32 DEFAULT VARIATION
setting specifies a time delay for the detection of dead network TCP connections. If
DNP TCP CONNECTION TIMEOUT


COMMUNICATIONS
 BINARY INPUT / MSP
 POINTS
 ANALOG INPUT / MME
 POINTS


COMMUNICATIONS
Point:
0
Off
Point:
1
Off
Point:
255
Off
G60 Generator Protection System
settings allow the user to select the DNP
DNP / IEC104 POINT LISTS
Range: see sub-menu below
Range: see sub-menu below
DNP / IEC104 POINT LISTS
BINARY INPUT / MSP POINTS
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
5.2 PRODUCT SETUP
DNP NUMBER OF PAIRED CON-
setting for the changes to take
5-39
5