GE UR T60 Instruction Manual

Ur series transformer protection system
Table of Contents

Advertisement

Quick Links

Title Page
GE
Digital Energy
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet:
http://www.GEDigitalEnergy.com
*1601-0090-W2*
T60 Transformer Protection System
UR Series Instruction Manual
Manual P/N: 1601-0090-W2 (GEK-113219A)
IND.CONT. EQ.
T60 Revision: 5.9x
828743A2.CDR
E83849
LISTED
52TL
GE Multilin's Quality Management
System is registered to
ISO9001:2008
QMI # 005094
UL # A3775

Advertisement

Table of Contents
loading

Summary of Contents for GE UR T60

  • Page 1 GE Digital Energy LISTED 650 Markland Street IND.CONT. EQ. 52TL Markham, Ontario GE Multilin's Quality Management Canada L6C 0M1 System is registered to ISO9001:2008 Tel: +1 905 927 7070 Fax: +1 905 927 5098 QMI # 005094 UL # A3775 Internet: http://www.GEDigitalEnergy.com...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3: Table Of Contents

    APPROVALS ....................2-22 2.2.14 MAINTENANCE ....................2-22 3. HARDWARE 3.1 DESCRIPTION 3.1.1 PANEL CUTOUT ....................3-1 3.1.2 MODULE WITHDRAWAL AND INSERTION ............. 3-6 3.1.3 REAR TERMINAL LAYOUT................3-8 3.2 WIRING 3.2.1 TYPICAL WIRING.................... 3-10 GE Multilin T60 Transformer Protection System...
  • Page 4 INTRODUCTION TO AC SOURCES..............5-5 5.2 PRODUCT SETUP 5.2.1 SECURITY......................5-8 5.2.2 DISPLAY PROPERTIES ..................5-13 5.2.3 CLEAR RELAY RECORDS ................5-14 5.2.4 COMMUNICATIONS ..................5-16 5.2.5 MODBUS USER MAP ..................5-41 5.2.6 REAL TIME CLOCK ..................5-41 5.2.7 USER-PROGRAMMABLE FAULT REPORT............5-42 T60 Transformer Protection System GE Multilin...
  • Page 5 5.8 INPUTS AND OUTPUTS 5.8.1 CONTACT INPUTS..................5-265 5.8.2 VIRTUAL INPUTS..................5-267 5.8.3 CONTACT OUTPUTS..................5-268 5.8.4 VIRTUAL OUTPUTS ..................5-270 5.8.5 REMOTE DEVICES ..................5-271 5.8.6 REMOTE INPUTS..................5-272 5.8.7 REMOTE DOUBLE-POINT STATUS INPUTS ..........5-273 GE Multilin T60 Transformer Protection System...
  • Page 6 USER-PROGRAMMABLE FAULT REPORTS ..........6-25 6.4.2 EVENT RECORDS ...................6-25 6.4.3 OSCILLOGRAPHY ...................6-25 6.4.4 DATA LOGGER ....................6-26 6.4.5 PHASOR MEASUREMENT UNIT RECORDS ..........6-27 6.4.6 BREAKER MAINTENANCE ................6-27 6.5 PRODUCT INFORMATION 6.5.1 MODEL INFORMATION ...................6-28 6.5.2 FIRMWARE REVISIONS..................6-28 T60 Transformer Protection System GE Multilin...
  • Page 7 INRUSH INHIBIT TESTS ................. 9-16 9.6.3 OVEREXCITATION INHIBIT TESTS ............... 9-17 10. MAINTENANCE 10.1 UNINSTALL AND CLEAR FILES AND DATA 10.1.1 UNINSTALL AND CLEAR FILES AND DATA..........10-1 10.2 REPAIRS 10.2.1 REPAIRS ......................10-2 GE Multilin T60 Transformer Protection System...
  • Page 8 NON-IEC 61850 DATA ..................C-7 C.3.9 COMMUNICATION SOFTWARE UTILITIES............. C-7 C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE C.4.1 OVERVIEW ....................... C-8 C.4.2 GSSE CONFIGURATION.................. C-8 C.4.3 FIXED GOOSE ....................C-8 C.4.4 CONFIGURABLE GOOSE ................C-8 viii T60 Transformer Protection System GE Multilin...
  • Page 9 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY ..................F-1 F.1.2 CHANGES TO THE T60 MANUAL ..............F-2 F.2 ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS ............... F-12 F.3 WARRANTY F.3.1 GE MULTILIN WARRANTY ................F-14 INDEX GE Multilin T60 Transformer Protection System...
  • Page 10 TABLE OF CONTENTS T60 Transformer Protection System GE Multilin...
  • Page 11 (Cd), ólom (Pb) vagy higany (Hg) tartalomra utaló betűjelzés. A hulladék akkumulátor leadható a termék forgalmazójánál új akkumulátor vásárlásakor, vagy a kijelölt elektronikai hulladékudvarokban. További információ a www.recyclethis.info oldalon. GE Multilin T60 Transformer Protection System...
  • Page 12 Batteriet är märkt med denna symbol, vilket kan innebära att det innehåller kadmium (Cd), bly (Pb) eller kvicksilver (Hg). För korrekt återvinning skall batteriet returneras till leverantören eller till en därför avsedd deponering. För mer information, se: www.recyclethis.info. T60 Transformer Protection System GE Multilin...
  • Page 13 North America 905-294-6222 Latin America +55 11 3614 1700 Europe, Middle East, Africa +(34) 94 485 88 00 Asia +86-21-2401-3208 India +91 80 41314617 From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574 GE Multilin T60 Transformer Protection System xiii...
  • Page 14 0.1 BATTERY DISPOSAL 0 BATTERY DISPOSAL T60 Transformer Protection System GE Multilin...
  • Page 15: Getting Started

    • Mounting screws For product information, instruction manual updates, and the latest software updates, please visit the GE Digital Energy website. If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE Multilin immediately. NOTE...
  • Page 16: Ur Overview

    This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals. T60 Transformer Protection System...
  • Page 17: Hardware Architecture

    (dual) ring configuration. This feature is optimized for speed and intended for pilot- aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis. GE Multilin T60 Transformer Protection System...
  • Page 18: Software Architecture

    5. An explanation of the use of inputs from CTs and VTs is in the Introduction to AC sources section in chapter 5. A description of how digital signals are used and routed within the relay is contained in the Introduction to FlexLogic™ section in chapter 5. T60 Transformer Protection System GE Multilin...
  • Page 19: Enervista Ur Setup Software

    After ensuring the minimum requirements for using EnerVista UR Setup are met (see previous section), use the following procedure to install the EnerVista UR Setup from the enclosed GE EnerVista CD. Insert the GE EnerVista CD into your CD-ROM drive.
  • Page 20: Configuring The T60 For Software Access

    The user can connect remotely to the T60 through the rear RS485 port or the rear Ethernet port with a PC running the EnerVista UR Setup software. The T60 can also be accessed locally with a computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature. T60 Transformer Protection System GE Multilin...
  • Page 21 RS232 port. A computer with an RS232 port and a serial cable is required. To use the RS485 port at the back of the relay, a GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.
  • Page 22 UR device must be on the same subnet. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.
  • Page 23: Using The Quick Connect Feature

    Before starting, verify that the serial cable is properly connected from the laptop computer to the front panel RS232 port with a straight-through 9-pin to 9-pin RS232 cable. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.
  • Page 24 White/green White/orange Blue Blue White/blue White/blue Green Orange White/brown White/brown Brown Brown 842799A1.CDR Figure 1–6: ETHERNET CROSS-OVER CABLE PIN LAYOUT Now, assign the computer an IP address compatible with the relay’s IP address. 1-10 T60 Transformer Protection System GE Multilin...
  • Page 25 Right-click the Local Area Connection icon and select Properties. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button. Click on the “Use the following IP address” box. GE Multilin T60 Transformer Protection System 1-11...
  • Page 26 Verify the physical connection between the T60 and the laptop computer, and double-check the programmed IP address in    setting, then repeat step 2 in the above procedure. PRODUCT SETUP COMMUNICATIONS NETWORK IP ADDRESS If the following sequence of messages appears when entering the command: C:\WINNT>ping 1.1.1.1 1-12 T60 Transformer Protection System GE Multilin...
  • Page 27 If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon- nected from the T60 relay. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or online from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.
  • Page 28 The EnerVista UR Setup software will then proceed to configure all settings and order code options in the Device Setup menu, for the purpose of communicating to multiple relays. This feature allows the user to identify and interrogate, in seconds, all UR-series devices in a particular location. 1-14 T60 Transformer Protection System GE Multilin...
  • Page 29: Connecting To The T60 Relay

    View the T60 event record. • View the last recorded oscillography record. • View the status of all T60 inputs and outputs. • View all of the T60 metering values. • View the T60 protection summary. GE Multilin T60 Transformer Protection System 1-15...
  • Page 30: Ur Hardware

    Figure 1–7: RELAY COMMUNICATIONS OPTIONS To communicate through the T60 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the T60 rear communications port.
  • Page 31: Using The Relay

    LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain until the relay is explicitly put in the “Programmed” state. Select the menu message    SETTINGS PRODUCT SETUP INSTALLATION RELAY SETTINGS RELAY SETTINGS: Not Programmed GE Multilin T60 Transformer Protection System 1-17...
  • Page 32: Relay Passwords

    Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level passwords. NOTE 1.5.6 FLEXLOGIC™ CUSTOMIZATION FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex- Logic™ section in Chapter 5 for additional details. 1-18 T60 Transformer Protection System GE Multilin...
  • Page 33: Commissioning

    View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements. If it is concluded that the relay or one of its modules is of concern, contact GE Multilin for prompt service. GE Multilin...
  • Page 34 1.5 USING THE RELAY 1 GETTING STARTED 1-20 T60 Transformer Protection System GE Multilin...
  • Page 35: Product Description

    Phase directional overcurrent 50/87 Instantaneous differential overcurrent Power swing blocking 50BF Breaker failure Out-of-step tripping Ground instantaneous overcurrent Overfrequency Neutral instantaneous overcurrent Underfrequency Phase instantaneous overcurrent Restricted ground fault Ground time overcurrent Transformer differential GE Multilin T60 Transformer Protection System...
  • Page 36 2.1 INTRODUCTION 2 PRODUCT DESCRIPTION Figure 2–1: SINGLE LINE DIAGRAM T60 Transformer Protection System GE Multilin...
  • Page 37: Ordering

    The order codes for the horizontal mount units with traditional CTs and VTs are shown below. The following features are not available when the T60 is ordered with three CT/VT modules: breaker arcing current, load encroachment, and breaker failure. NOTE GE Multilin T60 Transformer Protection System...
  • Page 38 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels T60 Transformer Protection System GE Multilin...
  • Page 39 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels GE Multilin T60 Transformer Protection System...
  • Page 40 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels T60 Transformer Protection System GE Multilin...
  • Page 41 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels GE Multilin T60 Transformer Protection System...
  • Page 42: Replacement Modules

    4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed) 4 DCmA inputs, 4 RTD inputs 8 DCmA inputs T60 Transformer Protection System GE Multilin...
  • Page 43 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed) 4 DCmA inputs, 4 RTD inputs 8 DCmA inputs GE Multilin T60 Transformer Protection System...
  • Page 44: Specifications

    CT location: all delta-wye and wye-delta transformers Voltage supervision pickup (series compensation applications): 0 to 5.000 pu in steps of 0.001 Operation time: 1 to 1.5 cycles (typical) Reset time: 1 power cycle (typical) 2-10 T60 Transformer Protection System GE Multilin...
  • Page 45 IEEE Moderately/Very/Extremely zone Inverse; IEC (and BS) A/B/C and Short Reach (secondary Ω): 0.02 to 500.00 Ω in steps of 0.01 Inverse; GE IAC Inverse, Short/Very/ Reach accuracy: ±5% including the effect of CVT tran- Extremely Inverse; I t; FlexCurves™...
  • Page 46 Level accuracy: ±0.5% of reading from 10 to 208 V of life, in hours Curve shapes: GE IAV Inverse, Definite Time Pickup level: 0 to 500000 hours in steps of 1 Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01...
  • Page 47 Number of elements: (L = Live, D = Dead) Number of inputs: PILOT-AIDED SCHEMES Operate time: <2 ms at 60 Hz Permissive Overreaching Transfer Trip (POTT) Time accuracy: ±3% or 10 ms, whichever is greater GE Multilin T60 Transformer Protection System 2-13...
  • Page 48: User-Programmable Elements

    Operating signal: any FlexLogic™ operand Pickup delay: 0.000 to 999999.999 s in steps of 0.001 Dropout delay: 0.000 to 999999.999 s in steps of 0.001 Timing accuracy: ±3% or ±4 ms, whichever is greater 2-14 T60 Transformer Protection System GE Multilin...
  • Page 49: Monitoring

    –0.8 < PF ≤ –1.0 and 0.8 < PF ≤ 1.0 Range: ±0 to 1 × 10 Mvarh REACTIVE POWER (VARS) Parameters: three-phase only Accuracy: ±1.0% of reading at –0.2 ≤ PF ≤ 0.2 Update rate: 50 ms GE Multilin T60 Transformer Protection System 2-15...
  • Page 50: Inputs

    0.0 to 16.0 ms in steps of 0.5 Accuracy: ±2°C Continuous current draw:4 mA (when energized) Lead resistance: 25 Ω maximum for Pt and Ni type; 3 Ω max. for Cu type Isolation: 36 Vpk 2-16 T60 Transformer Protection System GE Multilin...
  • Page 51: Power Supply

    250 V 0.2 A FORM-A VOLTAGE MONITOR Operate time: < 4 ms Applicable voltage: approx. 15 to 250 V DC Contact material: silver alloy Trickle current: approx. 1 to 2.5 mA GE Multilin T60 Transformer Protection System 2-17...
  • Page 52 L/R = 20 ms L/R = 40 ms L/R = 40 ms Internal fuse: 5 A / 350 V AC, Ceramic, Axial SLO 0.8 A L/R = 40 ms BLO; Manufacturer: Conquer; Part number: SCD-A 005 2-18 T60 Transformer Protection System GE Multilin...
  • Page 53: Communications

    Shielded twisted pair: 150 m (492 ft.) MAXIMUM STANDARD FAST ETHERNET SEGMENT LENGTHS 10Base-T (CAT 3, 4, 5 UTP): 100 m (328 ft.) 100Base-TX (CAT 5 UTP):100 m (328 ft.) Shielded twisted pair: 150 m (492 ft.) GE Multilin T60 Transformer Protection System 2-19...
  • Page 54: Inter-Relay Communications

    – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Noise: 0 dB Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6days). 2-20 T60 Transformer Protection System GE Multilin...
  • Page 55: Type Tests

    20 V/m, 80 MHz to 1 GHz Safety UL508 e83849 NKCR Safety UL C22.2-14 e83849 NKCR7 Safety UL1053 e83849 NKCR 2.2.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. GE Multilin T60 Transformer Protection System 2-21...
  • Page 56: Approvals

    Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to NOTE avoid deterioration of electrolytic capacitors. 2-22 T60 Transformer Protection System GE Multilin...
  • Page 57: Panel Cutout

    RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. 11.016” [279,81 mm] 9.687” [246,05 mm] 17.56” [446,02 mm] 7.460” [189,48 mm] 6.995” 6.960” [177,67 mm] [176,78 mm] 19.040” [483,62 mm] 842807A1.CDR Figure 3–1: T60 HORIZONTAL DIMENSIONS (ENHANCED PANEL) GE Multilin T60 Transformer Protection System...
  • Page 58 The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent equipment. T60 Transformer Protection System GE Multilin...
  • Page 59 The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. Figure 3–4: T60 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin T60 Transformer Protection System...
  • Page 60 Figure 3–5: T60 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For side mounting T60 devices with the enhanced front panel, see the following documents available on the UR DVD and the GE Digital Energy website: • GEK-113180: UR-Series UR-V Side-Mounting Front Panel Assembly Instructions •...
  • Page 61 3 HARDWARE 3.1 DESCRIPTION Figure 3–6: T60 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL) GE Multilin T60 Transformer Protection System...
  • Page 62: Module Withdrawal And Insertion

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the T60. T60 Transformer Protection System GE Multilin...
  • Page 63 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. CPU connections must be individually disconnected from the module before the module can be removed from the chassis. NOTE NOTE GE Multilin T60 Transformer Protection System...
  • Page 64: Rear Terminal Layout

    Inst. Manual: Contact Outputs: Standard Pilot Duty / 250V AC 7.5A MAZB98000029 Serial Number: 360V A Resistive / 125V DC Break Firmware: GE Multilin 4A @ L/R = 40mS / 300W 1998/01/05 Mfg. Date: Technical Support: Made in Tel: (905) 294-6222 ®...
  • Page 65 3 HARDWARE 3.1 DESCRIPTION Figure 3–11: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin T60 Transformer Protection System...
  • Page 66: Wiring

    3.2 WIRING 3 HARDWARE 3.2WIRING 3.2.1 TYPICAL WIRING Figure 3–12: TYPICAL WIRING DIAGRAM 3-10 T60 Transformer Protection System GE Multilin...
  • Page 67: Dielectric Strength

    An LED on the front of the control power module shows the status of the power supply: LED INDICATION POWER SUPPLY CONTINUOUS ON ON / OFF CYCLING Failure Failure GE Multilin T60 Transformer Protection System 3-11...
  • Page 68: Ct/Vt Modules

    CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram. The exact placement of a zero-sequence core balance CT to detect ground fault current is shown as follows. Twisted-pair cabling on the zero-sequence CT is recommended. 3-12 T60 Transformer Protection System GE Multilin...
  • Page 69 Substitute the tilde “~” symbol with the slot position of the module in the following figure. NOTE Current inputs Voltage inputs 8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs) Current inputs 8H, 8J, 8N, and 8R modules (8 CTs) 842766A3.CDR Figure 3–15: CT/VT MODULE WIRING GE Multilin T60 Transformer Protection System 3-13...
  • Page 70: Process Bus Modules

    3.2.5 PROCESS BUS MODULES The T60 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.
  • Page 71 Logic™ operand driving the contact output should be given a reset delay of 10 ms to prevent dam- age of the output contact (in situations when the element initiating the contact output is bouncing, at values in the region of the pickup value). GE Multilin T60 Transformer Protection System 3-15...
  • Page 72 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs 3-16 T60 Transformer Protection System GE Multilin...
  • Page 73 Not Used ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used GE Multilin T60 Transformer Protection System 3-17...
  • Page 74 3.2 WIRING 3 HARDWARE Figure 3–17: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) 3-18 T60 Transformer Protection System GE Multilin...
  • Page 75 3 HARDWARE 3.2 WIRING Figure 3–18: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output con- nections. GE Multilin T60 Transformer Protection System 3-19...
  • Page 76 Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. 3-20 T60 Transformer Protection System GE Multilin...
  • Page 77 CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–21: AUTO-BURNISH DIP SWITCHES The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, the auto-burnish functionality can be checked using an oscilloscope. NOTE GE Multilin T60 Transformer Protection System 3-21...
  • Page 78: Transducer Inputs/Outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE Figure 3–22: TRANSDUCER INPUT/OUTPUT MODULE WIRING The following figure show how to connect RTDs. 3-22 T60 Transformer Protection System GE Multilin...
  • Page 79 3 HARDWARE 3.2 WIRING Figure 3–23: RTD CONNECTIONS GE Multilin T60 Transformer Protection System 3-23...
  • Page 80: Rs232 Faceplate Port

    10Base-F or 10Base-T (obsolete) RS485 Redundant 10Base-F or 10Base-T (obsolete) RS485 100Base-FX or 10/100Base-T RS485 Redundant 100Base-FX or 10/100Base-T RS485 100Base-FX (obsolete) RS485 Redundant 100Base-FX (obsolete) RS485 10/100Base-T RS485 Six-port managed Ethernet switch RS485 3-24 T60 Transformer Protection System GE Multilin...
  • Page 81 Installation of the 10/100Base-T Ethernet cable at the same time as the CH1 and/or CH2 100Base-F fiber cables does not affect the communication over the CH1 or CH2 fiber ports. Figure 3–25: CPU MODULE COMMUNICATIONS WIRING (MODULE APPLICABLE DEPENDS ON ORDER CODE) GE Multilin T60 Transformer Protection System 3-25...
  • Page 82 To ensure maximum reliability, all equipment should have similar transient protection devices installed. Both ends of the RS485 circuit should also be terminated with an impedance as shown below. Figure 3–26: RS485 SERIAL CONNECTION 3-26 T60 Transformer Protection System GE Multilin...
  • Page 83: Irig-B

    (AM). Third party equipment is available for generating the IRIG-B signal; this equipment can use a GPS satellite system to obtain the time reference so that devices at different geographic locations can be syn- chronized. Figure 3–27: OPTIONS FOR IRIG-B CONNECTION GE Multilin T60 Transformer Protection System 3-27...
  • Page 84 UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal even when a relay in the series is powered down. Figure 3–28: IRIG-B REPEATER Using an amplitude modulated receiver causes errors up to 1 ms in event time-stamping. NOTE 3-28 T60 Transformer Protection System GE Multilin...
  • Page 85: Direct Input/Output Communications

    1 to channel 2 on UR2, the setting should be “Enabled” on UR2. This DIRECT I/O CHANNEL CROSSOVER forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1. GE Multilin T60 Transformer Protection System 3-29...
  • Page 86 1300 nm, multi-mode, LED, 2 channels 1300 nm, single-mode, ELED, 2 channels 1300 nm, single-mode, LASER, 2 channels Channel 1: RS422, channel: 820 nm, multi-mode, LED Channel 1: RS422, channel 2: 1300 nm, multi-mode, LED 3-30 T60 Transformer Protection System GE Multilin...
  • Page 87: Fiber: Led And Eled Transmitters

    The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module. Module: 72/ 7D 73/ 7K Connection Location: Slot X Slot X 831720A3.CDR 1 Channel 2 Channels Figure 3–33: LASER FIBER MODULES GE Multilin T60 Transformer Protection System 3-31...
  • Page 88: Interface

    Before performing this action, control power must be removed from the relay. The original location of the module should be recorded to help ensure that the same or replacement module is inserted into the correct slot. 3-32 T60 Transformer Protection System GE Multilin...
  • Page 89 Internal Timing Mode: The system clock is generated internally. Therefore, the G.703 timing selection should be in the internal timing mode for back-to-back (UR-to-UR) connections. For back-to-back connections, set for octet timing (S1 = OFF) and timing mode to internal timing (S5 = ON and S6 = OFF). GE Multilin T60 Transformer Protection System 3-33...
  • Page 90 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–38: G.703 DUAL LOOPBACK MODE 3-34 T60 Transformer Protection System GE Multilin...
  • Page 91: Rs422 Interface

    1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. GE Multilin T60 Transformer Protection System...
  • Page 92 Figure 3–42: CLOCK AND DATA TRANSITIONS d) RECEIVE TIMING The RS422 interface utilizes NRZI-MARK modulation code and; therefore, does not rely on an Rx clock to recapture data. NRZI-MARK is an edge-type, invertible, self-clocking code. 3-36 T60 Transformer Protection System GE Multilin...
  • Page 93: Rs422 And Fiber Interface

    When using a laser interface, attenuators may be necessary to ensure that you do not exceed the maximum optical input power to the receiver. Shield Tx – G.703 Rx – channel 1 Tx + Rx + Surge Fiber channel 2 842778A1.CDR Figure 3–44: G.703 AND FIBER INTERFACE CONNECTION GE Multilin T60 Transformer Protection System 3-37...
  • Page 94: Ieee C37.94 Interface

    IEEE C37.94 standard, as shown below. In 2008, GE Digital Energy released revised modules 76 and 77 for C37.94 communication to enable multi-ended fault location functionality with firmware 5.60 release and higher. All modules 76 and 77 shipped since the change support this feature and are fully backward compatible with firmware releases below 5.60.
  • Page 95 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. GE Multilin T60 Transformer Protection System...
  • Page 96 3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS 3 HARDWARE Figure 3–45: IEEE C37.94 TIMING SELECTION SWITCH SETTING 3-40 T60 Transformer Protection System GE Multilin...
  • Page 97: C37.94Sm Interface

    It can also can be connected directly to any other UR-series relay with a C37.94SM module as shown below. In 2008, GE Digital Energy released revised modules 2A and 2B for C37.94SM communication to enable multi-ended fault location functionality with firmware 5.60 release and higher. All modules 2A and 2B shipped since the change support this feature and are fully backward compatible with firmware releases below 5.60.
  • Page 98 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. 3-42 T60 Transformer Protection System GE Multilin...
  • Page 99 3 HARDWARE 3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS Figure 3–46: C37.94SM TIMING SELECTION SWITCH SETTING GE Multilin T60 Transformer Protection System 3-43...
  • Page 100: Managed Ethernet Switch Modules

    Not used Two 10/100Base-T ports Four 100Base-FX multimode ports with ST connectors RS232 console port Independent power supply. Options: 2S: high-voltage 2T: low-voltage FRONT VIEW REAR VIEW 842867A2.CDR Figure 3–47: MANAGED ETHERNET SWITCHES HARDWARE 3-44 T60 Transformer Protection System GE Multilin...
  • Page 101: Managed Switch Led Indicators

    Configuring the T60 switch module through EnerVista UR Setup. These procedures are described in the following sections. When the T60 is properly configured, the LED will be off and the error message will be cleared. GE Multilin T60 Transformer Protection System 3-45...
  • Page 102 From the Windows Start Menu, select the Settings > Network Connections menu item. 2.2. Right-click on the Local Area Connection icon and select the Properties item. This will open the LAN proper- ties window. 2.3. Click the Properties button as shown below. 3-46 T60 Transformer Protection System GE Multilin...
  • Page 103 After few seconds you should see your local area connection attempting to connect to the switch. Once connected, check your IP address by going to bottom of your screen and right-clicking the Local Area Connection icon as shown below. GE Multilin T60 Transformer Protection System 3-47...
  • Page 104 Click the Read Order Code button. You should be able to communicate with the T60 device regardless of the value of the Ethernet switch IP address and even though the front panel display states that the Ethernet module is offline. 3-48 T60 Transformer Protection System GE Multilin...
  • Page 105: Configuring The Managed Ethernet Switch Module

    Switch has been shipped with a default IP address of 192.168.1.2 and a subnet mask of 255.255.255.0. Consult your net- work administrator to determine if the default IP address, subnet mask or default gateway needs to be modified. Do not connect to network while configuring the switch module. GE Multilin T60 Transformer Protection System 3-49...
  • Page 106 Select the desired device from site tree in the online window. Select the Settings > Product Setup > Communications > Ethernet Switch > Ethernet Switch Settings File > Retrieve Settings File item from the device settings tree. 3-50 T60 Transformer Protection System GE Multilin...
  • Page 107 Navigate to the folder containing the Ethernet switch settings file, select the file, then click Open. The settings file will be transferred to the Ethernet switch and the settings uploaded to the device. GE Multilin T60 Transformer Protection System 3-51...
  • Page 108: Uploading T60 Switch Module Firmware

    NOTE b) SELECTING THE PROPER SWITCH FIRMWARE VERSION The latest switch module firmware is available as a download from the GE Multilin web site. Use the following procedure to determine the version of firmware currently installed on your switch Log into the switch using the EnerVista web interface.
  • Page 109 Select the firmware file to be loaded on to the Switch, and select the Open option. The following window will pop up, indicating that the firmware file transfer is in progress. If the firmware load was successful, the following window will appear: Note GE Multilin T60 Transformer Protection System 3-53...
  • Page 110: Ethernet Switch Self-Test Errors

    To clear the main CPU upon power-up the fault, cycle power to the T60. and create the error if there is a conflict between the input/ output state and the order code. 3-54 T60 Transformer Protection System GE Multilin...
  • Page 111: Human Interfaces

    Factory default values are supplied and can be restored after any changes. The following communications settings are not transferred to the T60 with settings files. Modbus Slave Address Modbus TCP Port Number RS485 COM1 Baud Rate RS485 COM1 Parity COM1 Minimum Response Time GE Multilin T60 Transformer Protection System...
  • Page 112 The firmware of a T60 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”. T60 Transformer Protection System GE Multilin...
  • Page 113: Enervista Ur Setup Main Window

    Settings list control bar window. Device data view windows, with common tool bar. Settings file data view windows, with common tool bar. Workspace area with data view tabs. Status bar. 10. Quick action hot links. GE Multilin T60 Transformer Protection System...
  • Page 114 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4 HUMAN INTERFACES 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW T60 Transformer Protection System GE Multilin...
  • Page 115: Extended Enervista Ur Setup Features

    Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable. GE Multilin T60 Transformer Protection System...
  • Page 116 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. T60 Transformer Protection System GE Multilin...
  • Page 117 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND GE Multilin T60 Transformer Protection System...
  • Page 118 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. T60 Transformer Protection System GE Multilin...
  • Page 119: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. GE Multilin T60 Transformer Protection System...
  • Page 120 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. 4-10 T60 Transformer Protection System GE Multilin...
  • Page 121: Settings File Traceability

    UR-series device to determine if security SENT BACK TO ENERVISTA AND has been compromised. ADDED TO SETTINGS FILE. 842864A1.CDR Figure 4–11: SETTINGS FILE TRACEABILITY MECHANISM With respect to the above diagram, the traceability feature is used as follows. GE Multilin T60 Transformer Protection System 4-11...
  • Page 122 Figure 4–12: DEVICE DEFINITION SHOWING TRACEABILITY DATA This information is also available in printed settings file reports as shown in the example below. Traceability data in settings report 842862A1.CDR Figure 4–13: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA 4-12 T60 Transformer Protection System GE Multilin...
  • Page 123 If the user converts an existing settings file to another revision, then any existing traceability information is removed from the settings file. • If the user duplicates an existing settings file, then any traceability information is transferred to the duplicate settings file. GE Multilin T60 Transformer Protection System 4-13...
  • Page 124: Faceplate Interface

    The faceplate is hinged to allow easy access to the removable modules. There is also a removable dust cover that fits over the faceplate which must be removed in order to access the keypad panel. The following figure shows the horizontal arrangement of the faceplate panels. Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS 4-14 T60 Transformer Protection System GE Multilin...
  • Page 125: Led Indicators

    The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. GE Multilin T60 Transformer Protection System 4-15...
  • Page 126 LED indicator or target message, once the condition has been cleared (these latched conditions can also be reset via the   menu). The RS232 port is intended for connection SETTINGS INPUT/OUTPUTS RESETTING to a portable PC. keys are used by the breaker control feature. USER 4-16 T60 Transformer Protection System GE Multilin...
  • Page 127 User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program the operation of the LEDs on these panels. GE Multilin T60 Transformer Protection System 4-17...
  • Page 128: Custom Labeling Of Leds

    EnerVista UR Setup software is installed and operational. • The T60 settings have been saved to a settings file. • The T60 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://www.gedigitalenergy.com/products/support/ur/URLEDenhanced.doc and printed. •...
  • Page 129 Remove the T60 label insert tool from the package and bend the tabs as described in the following procedures. These tabs will be used for removal of the default and custom LED labels. It is important that the tool be used EXACTLY as shown below, with the printed side containing the GE part number facing the user.
  • Page 130 Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay. Slide the label tool under the LED label until the tabs snap out as shown below. This will attach the label tool to the LED label. 4-20 T60 Transformer Protection System GE Multilin...
  • Page 131 Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown below. Make sure the bent tab is pointing away from the relay. GE Multilin T60 Transformer Protection System 4-21...
  • Page 132 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will attach the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. 4-22 T60 Transformer Protection System GE Multilin...
  • Page 133: Display

    If the mode is selected as three-pole, a single input tracks the breaker open or closed posi- tion. If the mode is selected as one-pole, all three breaker pole states must be input to the relay. These inputs must be in agreement to indicate the position of the breaker. GE Multilin T60 Transformer Protection System 4-23...
  • Page 134: Menus

    Each press of the MENU key advances through the following main heading pages: • Actual values. • Settings. • Commands. • Targets. • User displays (when enabled). 4-24 T60 Transformer Protection System GE Multilin...
  • Page 135: Changing Settings

    TIME: 1.0 s 4.3.8 CHANGING SETTINGS a) ENTERING NUMERICAL DATA Each numerical setting has its own minimum, maximum, and increment value associated with it. These parameters define what values are acceptable for a setting. GE Multilin T60 Transformer Protection System 4-25...
  • Page 136 For example: to enter the text, “Breaker #1”. Press the decimal to enter text edit mode. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position. 4-26 T60 Transformer Protection System GE Multilin...
  • Page 137 To enter the initial setting (or command) password, proceed as follows: Press the MENU key until the header flashes momentarily and the message appears on the SETTINGS PRODUCT SETUP display. GE Multilin T60 Transformer Protection System 4-27...
  • Page 138 FlexLogic™ operand is set to “Off” after five minutes for a Command password or 30 minutes for a Settings pass- DENIED word. These default settings can be changed in EnerVista under Settings > Product Setup > Security. 4-28 T60 Transformer Protection System GE Multilin...
  • Page 139: Overview

    See page 5–63.   TELEPROTECTION See page 5–70.   INSTALLATION See page 5–71.   SETTINGS  AC INPUTS See page 5–73.  SYSTEM SETUP   POWER SYSTEM See page 5–75.  GE Multilin T60 Transformer Protection System...
  • Page 140 See page 5–230.   SELECTOR SWITCH See page 5–231.   UNDERFREQUENCY See page 5–237.   OVERFREQUENCY See page 5–238.   SYNCHROCHECK See page 5–239.   DIGITAL ELEMENTS See page 5–243.  T60 Transformer Protection System GE Multilin...
  • Page 141  GOOSE UINTEGERS  SETTINGS  DCMA INPUTS See page 5–283.  TRANSDUCER I/O   RTD INPUTS See page 5–284.   RRTD INPUTS See page 5-285.   DCMA OUTPUTS See page 5–289.  GE Multilin T60 Transformer Protection System...
  • Page 142: Introduction To Elements

    VTs, the secondary base quantity and secondary voltage setting is: 13800 --------------- - × 115 V (EQ 5.1) 14400 For wye-connected VTs, the primary and secondary bases quanitities are as before, but the secondary voltage (here a phase-to-phase ground value) is: T60 Transformer Protection System GE Multilin...
  • Page 143: Introduction To Ac Sources

    Some current flows through the upper bus bar to some other location or power equipment, and some current flows into transformer winding 1. The current into winding 1 is the phasor sum (or GE Multilin T60 Transformer Protection System...
  • Page 144 INCREASING SLOT POSITION LETTER --> CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 < bank 1 > < bank 3 > < bank 5 > < bank 2 > < bank 4 > < bank 6 > T60 Transformer Protection System GE Multilin...
  • Page 145 Upon startup, the CPU configures the settings required to characterize the current and voltage inputs, and will display them in the appropriate section in the sequence of the banks (as described above) as follows for a maximum configuration: F1, F5, M1, M5, U1, and U5. GE Multilin T60 Transformer Protection System...
  • Page 146: Product Setup

    (via the setting and command level access timeout settings). The remote setting and command ses- sions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout. T60 Transformer Protection System GE Multilin...
  • Page 147 ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both com- mands and settings. NOTE If a remote connection is established, local passcodes are not visible. NOTE GE Multilin T60 Transformer Protection System...
  • Page 148  SUPERVISION  TIMEOUTS Range: 2 to 5 in steps of 1 INVALID ATTEMPTS MESSAGE BEFORE LOCKOUT: 3 Range: 5 to 60 minutes in steps of 1 PASSWORD LOCKOUT MESSAGE DURATION: 5 min 5-10 T60 Transformer Protection System GE Multilin...
  • Page 149 If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain setting access, then the message is displayed on the front panel. UNAUTHORIZED ACCESS GE Multilin T60 Transformer Protection System 5-11...
  • Page 150 If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. 5-12 T60 Transformer Protection System GE Multilin...
  • Page 151: Display Properties

    The T60 applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below the cut-off level, it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical GE Multilin T60 Transformer Protection System...
  • Page 152: Clear Relay Records

    CLEAR EVENT RECORDS: MESSAGE Range: FlexLogic™ operand CLEAR OSCILLOGRAPHY? MESSAGE Range: FlexLogic™ operand CLEAR DATA LOGGER: MESSAGE Range: FlexLogic™ operand CLEAR ARC AMPS 1: MESSAGE Range: FlexLogic™ operand CLEAR ARC AMPS 2: MESSAGE 5-14 T60 Transformer Protection System GE Multilin...
  • Page 153 Set the properties for user-programmable pushbutton 1 by making the following changes in the  SETTINGS PRODUCT   menu: SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 “Self-reset” PUSHBUTTON 1 FUNCTION: “0.20 s” PUSHBTN 1 DROP-OUT TIME: GE Multilin T60 Transformer Protection System 5-15...
  • Page 154: Communications

    19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet or RS485 port. The rear COM2 port be used for either RS485 or RRTD communications. 5-16 T60 Transformer Protection System GE Multilin...
  • Page 155 The port is strictly dedicated to RRTD usage when is selected as “RRTD”. COM2 USAGE Power must be cycled to the T60 for changes to the setting to take effect. COM2 USAGE NOTE GE Multilin T60 Transformer Protection System 5-17...
  • Page 156 0 disables Modbus PORT NUMBER MODBUS TCP PORT NUMBER over TCP/IP, meaning closes the Modbus TCP port. When it is set to 0, use the front panel or serial port to communicate with the relay. 5-18 T60 Transformer Protection System GE Multilin...
  • Page 157 DNP POWER DEFAULT MESSAGE DEADBAND: 30000 Range: 0 to 100000000 in steps of 1 DNP ENERGY DEFAULT MESSAGE DEADBAND: 30000 Range: 0 to 100000000 in steps of 1 DNP PF DEFAULT MESSAGE DEADBAND: 30000 GE Multilin T60 Transformer Protection System 5-19...
  • Page 158 TCP/IP on channels 1 or 2. When this value is set to “Network - UDP”, the DNP protocol can be used over UDP/IP on chan- nel 1 only. Refer to Appendix E for additional information on the DNP protocol. 5-20 T60 Transformer Protection System GE Multilin...
  • Page 159 DNP MESSAGE FRAGMENT SIZE fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to be necessary which can provide for more robust data transfer over noisy communication channels. GE Multilin T60 Transformer Protection System 5-21...
  • Page 160 FlexLogic™ operand. Refer to the Introduction to FlexLogic™ section in this chapter for the full range of assignable operands. The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below. 5-22 T60 Transformer Protection System GE Multilin...
  • Page 161  GGIO2 CONTROL MESSAGE  CONFIGURATION  GGIO4 ANALOG MESSAGE  CONFIGURATION  GGIO5 UINTEGER MESSAGE  CONFIGURATION  REPORT CONTROL MESSAGE  CONFIGURATION  XCBR MESSAGE  CONFIGURATION  XSWI MESSAGE  CONFIGURATION GE Multilin T60 Transformer Protection System 5-23...
  • Page 162 Range: 65-character ASCII string GSSE ID: MESSAGE GSSEOut Range: standard MAC address DESTINATION MAC: MESSAGE 000000000000 These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted. 5-24 T60 Transformer Protection System GE Multilin...
  • Page 163 ID for each GOOSE sending device. This value can be left at its default if the feature is not required. Both the GOOSE VLAN settings are required by IEC 61850. PRIORITY GOOSE ETYPE APPID GE Multilin T60 Transformer Protection System 5-25...
  • Page 164 The aggressive scheme is only supported in fast type 1A GOOSE messages (GOOSEOut 1 and GOOSEOut 2). For slow GOOSE messages (GOOSEOut 3 to GOOSEOut 8) the aggressive scheme is the same as the medium scheme. 5-26 T60 Transformer Protection System GE Multilin...
  • Page 165 Configure the transmission dataset. Configure the GOOSE service settings. Configure the data. The general steps required for reception configuration are: Configure the reception dataset. Configure the GOOSE service settings. Configure the data. GE Multilin T60 Transformer Protection System 5-27...
  • Page 166 Configure the GOOSE service settings by making the following changes in the  INPUTS/OUTPUTS REMOTE DEVICES  settings menu: REMOTE DEVICE 1 – to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”. REMOTE DEVICE 1 ID 5-28 T60 Transformer Protection System GE Multilin...
  • Page 167 The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic™ operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con- taining the defined dataset. GE Multilin T60 Transformer Protection System 5-29...
  • Page 168 Range: up to 80 alphanumeric characters LOCATION: Location MESSAGE Range: 1 to 65535 in steps of 1 IEC/MMS TCP PORT MESSAGE NUMBER: Range: Disabled, Enabled INCLUDE NON-IEC MESSAGE DATA: Enabled Range: Disabled, Enabled SERVER SCANNING: MESSAGE Disabled 5-30 T60 Transformer Protection System GE Multilin...
  • Page 169 PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL MMXU DEADBANDS  MMXU DEADBANDS  MMXU1 DEADBANDS    MMXU2 DEADBANDS MESSAGE   MMXU3 DEADBANDS MESSAGE   MMXU4 DEADBANDS MESSAGE  GE Multilin T60 Transformer Protection System 5-31...
  • Page 170 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the T60 virtual inputs. 5-32 T60 Transformer Protection System GE Multilin...
  • Page 171 ANALOG IN 1 MIN ANALOG IN 1 MAX numbers. Because of the large range of these settings, not all values can be stored. Some values may be rounded NOTE to the closest possible floating point number. GE Multilin T60 Transformer Protection System 5-33...
  • Page 172 LLN0 if a user needs some (but not all) data from already existing GGIO1, GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset. 5-34 T60 Transformer Protection System GE Multilin...
  • Page 173 XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1. GE Multilin T60 Transformer Protection System...
  • Page 174 IP address of the T60 into the “Address” box on the web browser. Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of those protocols. NOTE 5-36 T60 Transformer Protection System GE Multilin...
  • Page 175 60870-5-104 data change buffers, no more than two masters should actively communicate with the T60 at one time. Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of those protocols. NOTE GE Multilin T60 Transformer Protection System 5-37...
  • Page 176 This feature is specified as a software option at the time of ordering. Refer to the Order- ing section of chapter 2 for additional details. The Ethernet Global Data (EGD) protocol feature is not available if CPU Type E is ordered. 5-38 T60 Transformer Protection System GE Multilin...
  • Page 177 Range: 0 to 65535 in steps of 1 EXCH 1 DATA ITEM MESSAGE (Modbus register address range in decimal) ↓ Range: 0 to 65535 in steps of 1 EXCH 1 DATA ITEM 50: MESSAGE (Modbus register address range in decimal) GE Multilin T60 Transformer Protection System 5-39...
  • Page 178 The client software (EnerVista UR Setup, for example) is the preferred interface to configure these settings. through settings allow Ethernet switch module events to be logged in the event PORT 1 EVENTS PORT 6 EVENTS recorder. 5-40 T60 Transformer Protection System GE Multilin...
  • Page 179: Modbus User Map

    Range: Sunday to Saturday (all days of the week) DST STOP DAY: MESSAGE Sunday Range: First, Second, Third, Fourth, Last DST STOP DAY MESSAGE INSTANCE: First Range: 0:00 to 23:00 DST STOP HOUR: MESSAGE 2:00 GE Multilin T60 Transformer Protection System 5-41...
  • Page 180: User-Programmable Fault Report

    Each fault report is stored as a file to a maximum capacity of ten files. An eleventh trigger overwrites the oldest file. The EnerVista UR Setup software is required to view all captured data. A event is automatically created when FAULT RPT TRIG the report is triggered. 5-42 T60 Transformer Protection System GE Multilin...
  • Page 181: Oscillography

    See the  ACTUAL VALUES  menu to view the number of cycles captured per record. The following table provides sam- RECORDS OSCILLOGRAPHY ple configurations with corresponding cycles/record. GE Multilin T60 Transformer Protection System 5-43...
  • Page 182 FlexLogic™ operand state recorded in an oscillography trace. The length of DIGITAL 1(63) CHANNEL each oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. Upon startup, the relay will automatically prepare the parameter list. 5-44 T60 Transformer Protection System GE Multilin...
  • Page 183 2nd to 25th harmonics in the relay as follows: NOTE Analog channel 0 ↔ 2nd harmonic Analog channel 1 ↔ 3rd harmonic Analog channel 23 ↔ 25th harmonic GE Multilin T60 Transformer Protection System 5-45...
  • Page 184: Data Logger

    490920 s 436380 s 254460 s 3600000 ms 2727.5 235645200 s 340.9 29455200 s 26182800 s Changing any setting affecting data logger operation will clear any data that is currently in the log. NOTE 5-46 T60 Transformer Protection System GE Multilin...
  • Page 185: Demand

    D 1 e (EQ 5.6) – where: d = demand value after applying input quantity for time t (in minutes) D = input quantity (constant), and k = 2.3 / thermal 90% response time. GE Multilin T60 Transformer Protection System 5-47...
  • Page 186: User-Programmable Leds

    See below  LEDS   TRIP & ALARM MESSAGE See page 5–51.  LEDS  USER-PROGRAMMABLE MESSAGE See page 5–51.  LED1  USER-PROGRAMMABLE MESSAGE  LED2 ↓  USER-PROGRAMMABLE MESSAGE  LED48 5-48 T60 Transformer Protection System GE Multilin...
  • Page 187 The test responds to the position and rising edges of the control input defined by the set- LED TEST CONTROL ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed. GE Multilin T60 Transformer Protection System 5-49...
  • Page 188 2. Once stage 2 has started, the pushbutton can be released. When stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton. 5-50 T60 Transformer Protection System GE Multilin...
  • Page 189 LED 19 operand LED 8 operand LED 20 operand LED 9 operand LED 21 operand LED 10 operand LED 22 operand LED 11 operand LED 23 operand LED 12 operand LED 24 operand GE Multilin T60 Transformer Protection System 5-51...
  • Page 190: User-Programmable Self Tests

    Refer to the Relay self-tests section in chapter 7 for additional information on major and minor self-test alarms. To enable the Ethernet switch failure function, ensure that the is “Enabled” in this ETHERNET SWITCH FAIL FUNCTION menu. NOTE 5-52 T60 Transformer Protection System GE Multilin...
  • Page 191: Control Pushbuttons

    An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously – a given key must be released before the next one can be pressed. GE Multilin T60 Transformer Protection System 5-53...
  • Page 192: User-Programmable Pushbuttons

    PUSHBTN 1 DROP-OUT MESSAGE TIME: 0.00 s Range: FlexLogic™ operand PUSHBTN 1 LED CTL: MESSAGE Range: Disabled, Normal, High Priority PUSHBTN 1 MESSAGE: MESSAGE Disabled Range: Disabled, Enabled PUSHBUTTON 1 MESSAGE EVENTS: Disabled 5-54 T60 Transformer Protection System GE Multilin...
  • Page 193 The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the set- PUSHBTN 1 RESET ting or by directly pressing the associated active front panel pushbutton. GE Multilin T60 Transformer Protection System 5-55...
  • Page 194 This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer. 5-56 T60 Transformer Protection System GE Multilin...
  • Page 195 “Normal” if the setting is “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. GE Multilin T60 Transformer Protection System 5-57...
  • Page 196 Off = 0 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–10: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) 5-58 T60 Transformer Protection System GE Multilin...
  • Page 197 User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via NOTE EnerVista UR Setup with the Maintenance > Enable Pushbutton command. GE Multilin T60 Transformer Protection System 5-59...
  • Page 198: Flex State Parameters

    • USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL setting. Any FlexLogic™ operand (in particular, the user-programmable pushbutton operands), can be used to navi- gate the programmed displays. 5-60 T60 Transformer Protection System GE Multilin...
  • Page 199 (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this conversion). GE Multilin T60 Transformer Protection System 5-61...
  • Page 200 If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items NOTE are different. 5-62 T60 Transformer Protection System GE Multilin...
  • Page 201: Direct Inputs And Outputs

    “Yes”), all direct output messages should be received back. If not, the direct input/output ring CH2 RING CONFIGURATION break self-test is triggered. The self-test error is signaled by the FlexLogic™ operand. DIRECT RING BREAK GE Multilin T60 Transformer Protection System 5-63...
  • Page 202 The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the Inputs and outputs section in this chapter for information on configuring FlexLogic™ operands (flags, bits) to be exchanged. 5-64 T60 Transformer Protection System GE Multilin...
  • Page 203 UR IED 1 BLOCK UR IED 4 UR IED 2 UR IED 3 842712A1.CDR Figure 5–13: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME For increased reliability, a dual-ring configuration (shown below) is recommended for this application. GE Multilin T60 Transformer Protection System 5-65...
  • Page 204 The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns. 5-66 T60 Transformer Protection System GE Multilin...
  • Page 205 Inputs and outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This could be accomplished using a dual-ring configuration as shown below. GE Multilin T60 Transformer Protection System...
  • Page 206 FlexLogic™ operand is set. When the total message counter reaches the user-defined maximum specified by the set- CRC ALARM CH1 MESSAGE COUNT ting, both the counters reset and the monitoring process is restarted. 5-68 T60 Transformer Protection System GE Multilin...
  • Page 207 The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration. The total number of unreturned input and output messages is available as the   ACTUAL VALUES STATUS DIRECT  actual value. INPUTS UNRETURNED MSG COUNT CH1 GE Multilin T60 Transformer Protection System 5-69...
  • Page 208: Teleprotection

    On two- terminals two-channel systems, the same is transmitted over LOCAL RELAY ID NUMBER both channels; as such, only the has to be programmed on the receiving end. TERMINAL 1 ID NUMBER 5-70 T60 Transformer Protection System GE Multilin...
  • Page 209: Installation

    This name will appear on generated reports. This name RELAY NAME is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com- munications channel using the IEC 61850 protocol. GE Multilin T60 Transformer Protection System 5-71...
  • Page 210: Remote Resources Configuration

    Configure shared inputs and outputs as required for the application's functionality. Shared inputs and outputs are dis- tinct binary channels that provide high-speed protection quality signaling between relays through a Brick. For additional information on how to configure a relay with a process bus module, please refer to GE publication number GEK-113500: HardFiber System Instruction Manual.
  • Page 211: System Setup

    1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then a pickup level of 1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). GE Multilin T60 Transformer Protection System 5-73...
  • Page 212 = 66.4. On a 14.4 kV system with a delta connection and a VT primary to secondary turns ratio of 14400:120, the voltage value entered would be 120; that is, 14400 / 120. 5-74 T60 Transformer Protection System GE Multilin...
  • Page 213: Power System

    NOTE Systems with an ACB phase sequence require special consideration. Refer to the Phase relationships of three- phase transformers sub-section of chapter 5. NOTE GE Multilin T60 Transformer Protection System 5-75...
  • Page 214: Signal Sources

    CT wiring problem. A disturbance detector is provided for each source. The 50DD function responds to the changes in magnitude of the sequence currents. The disturbance detector scheme logic is as follows: 5-76 T60 Transformer Protection System GE Multilin...
  • Page 215 This configuration could be used on a two-winding transformer, with one winding connected into a breaker-and-a-half sys- tem. The following figure shows the arrangement of sources used to provide the functions required in this application, and the CT/VT inputs that are used to provide the data. GE Multilin T60 Transformer Protection System 5-77...
  • Page 216: Transformer

     TRANSFORMER  GENERAL See page 5–79.    WINDING 1 MESSAGE See page 5–81.   WINDING 2 MESSAGE See page 5–81.   WINDING 3 MESSAGE See page 5–81.  5-78 T60 Transformer Protection System GE Multilin...
  • Page 217 7.1x that can cause signal clamping and misoperation on the differential element. To avoid this, manually select the winding as outlined in the T35/T60 Reference Winding Selection and CT Ratio Mismatch Application Note (document GET-8548). For releases subsequent to 7.1x, contact GE Digital Energy to inquire if this applies. •...
  • Page 218 C = 0.02 × (weight of core and aluminum coils from the nameplate) • WINDING THERMAL TIME CONSTANT: Required for insulation aging calculation. If this value is not available from the transformer data, select “2 min.”. 5-80 T60 Transformer Protection System GE Multilin...
  • Page 219 TRANSFORMER GENERAL NUMBER OF WINDINGS total Compensation     SETTINGS SYSTEM SETUP TRANSFORMER GENERAL PHASE COMPENSATION Source [w]     SETTINGS SYSTEM SETUP TRANSFORMER WINDING w WINDING w SOURCE GE Multilin T60 Transformer Protection System 5-81...
  • Page 220 The reason the source phase sequence must be stated when describing the winding phase relationships is that these rela- tionships change when the phase sequence changes. The example shown below shows why this happens, using a trans- former described in IEC nomenclature as a type “Yd1” or in GE Multilin nomenclature as a “Y/d30.” 828716A1.CDR Figure 5–21: EXAMPLE TRANSFORMER...
  • Page 221 Note that the delta winding currents leads the wye winding currents by 30°, (which is a type Yd11 in IEC nomenclature and a type Y/d330 in GE Multilin nomenclature) which is in disagreement with the transformer nameplate. This is because the physical connections and hence the equations used to calculate current for the delta winding have not changed.
  • Page 222 1.0000 (EQ 5.15) 2 [ ] V × 2 [ ] 1500 A × 69 kV primary The maximum allowed magnitude compensation factor (and hence the maximum allowed CT ratio mismatch) is 32. 5-84 T60 Transformer Protection System GE Multilin...
  • Page 223 The following table shows the linear combination of phases of a transformer winding that achieves the phase shift and zero sequence removal for typical values of Φ comp where: I [w] = uncompensated winding ‘w’ phase A current [w] = phase and zero sequence compensated winding ‘w’ phase A current GE Multilin T60 Transformer Protection System 5-85...
  • Page 224 ------ - I – – ------ - I ------ - I ------ - I ------ - I – – ------ - I ------ - I ------ - I ------ - I – – 5-86 T60 Transformer Protection System GE Multilin...
  • Page 225 = magnitude, phase and zero sequence compensated winding w phase currents = magnitude compensation factor for winding w (see previous sections) [ ] I , and = phase and zero sequence compensated winding w phase currents (see earlier) GE Multilin T60 Transformer Protection System 5-87...
  • Page 226 SYSTEM SETUP SIGNAL  settings menu. SOURCES SOURCE 1(4) “WDG 1X” SOURCE 1 NAME: “F1” SOURCE 1 PHASE CT: “None” SOURCE 1 GROUND CT: “None” SOURCE 1 PHASE VT: “None” SOURCE 1 AUX VT: 5-88 T60 Transformer Protection System GE Multilin...
  • Page 227 SYSTEM SETUP SIGNAL  settings menu. SOURCES SOURCE n “WDG 2" SOURCE 2 NAME: “M1” SOURCE 2 PHASE CT: “M1” SOURCE 2 GROUND CT: “None” SOURCE 2 PHASE VT: “None” SOURCE 2 AUX VT: GE Multilin T60 Transformer Protection System 5-89...
  • Page 228 Range: –60 to 60°C in steps of 1 FEBRUARY AVERAGE: MESSAGE –30°C Range: –60 to 60°C in steps of 1 MARCH AVERAGE: MESSAGE –10°C ↓ Range: –60 to 60°C in steps of 1 DECEMBER AVERAGE: MESSAGE –10°C 5-90 T60 Transformer Protection System GE Multilin...
  • Page 229: Breakers

    Range: 0.000 to 65.535 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic™ operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled GE Multilin T60 Transformer Protection System 5-91...
  • Page 230 MANUAL CLOSE RECAL1 TIME: This setting specifies the interval required to maintain setting changes in effect after an operator has initiated a manual close command to operate a circuit breaker. • BREAKER 1 OUT OF SV: Selects an operand indicating that breaker 1 is out-of-service. 5-92 T60 Transformer Protection System GE Multilin...
  • Page 231 5.4 SYSTEM SETUP Figure 5–24: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the T60 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin T60 Transformer Protection System 5-93...
  • Page 232 5.4 SYSTEM SETUP 5 SETTINGS Figure 5–25: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2) 5-94 T60 Transformer Protection System GE Multilin...
  • Page 233: Disconnect Switches

    1. • SWITCH 1 MODE: This setting selects “3-Pole” mode, where disconnect switch poles have a single common auxiliary switch, or “1-Pole” mode where each disconnect switch pole has its own auxiliary switch. GE Multilin T60 Transformer Protection System 5-95...
  • Page 234 This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the T60 is in “Programmed” mode and not in the local control mode. NOTE 5-96 T60 Transformer Protection System GE Multilin...
  • Page 235 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–26: DISCONNECT SWITCH SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-97...
  • Page 236: Flexcurves

    1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin- ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu. 5-98 T60 Transformer Protection System GE Multilin...
  • Page 237 The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE GE Multilin T60 Transformer Protection System 5-99...
  • Page 238 EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the T60 are displayed in the following graphs. 5-100 T60 Transformer Protection System GE Multilin...
  • Page 239 CURRENT (multiple of pickup) 842723A1.CDR Figure 5–30: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–31: RECLOSER CURVES GE113, GE120, GE138 AND GE142 GE Multilin T60 Transformer Protection System 5-101...
  • Page 240 Figure 5–32: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–33: RECLOSER CURVES GE131, GE141, GE152, AND GE200 5-102 T60 Transformer Protection System GE Multilin...
  • Page 241 Figure 5–34: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–35: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 GE Multilin T60 Transformer Protection System 5-103...
  • Page 242 Figure 5–36: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–37: RECLOSER CURVES GE119, GE135, AND GE202 5-104 T60 Transformer Protection System GE Multilin...
  • Page 243: Phasor Measurement Unit

    MESSAGE See page 5-107.  CALIBRATION  PMU 1 MESSAGE See page 5-108.  COMMUNICATION  PMU 1 MESSAGE See page 5-110.  TRIGGERING  PMU 1 MESSAGE See page 5-117.  RECORDING GE Multilin T60 Transformer Protection System 5-105...
  • Page 244 This setting applies to all channels of the PMU. It is effectively for recording and transmission on all ports configured to use data of this PMU. Class M filtering functionality is derived from the draft IEEE C37.118 specification and may be subject to change when the standard is published. NOTE 5-106 T60 Transformer Protection System GE Multilin...
  • Page 245 Normally, the two correcting PMU 1 SEQ VOLT SHIFT ANGLE angles are set identically, except rare applications when the voltage and current measuring points are located at differ- ent windings of a power transformer. GE Multilin T60 Transformer Protection System 5-107...
  • Page 246 Range: available synchrophasor values PMU1 PORT PHS-1 MESSAGE PMU 1 V1 Range: 16-character ASCII string PMU1 PORT PHS-1 MESSAGE NM: GE-UR-PMU1-V1 ↓ Range: available synchrophasor values PMU1 PORT PHS-14 MESSAGE PMU 1 V1 Range: 16 alphanumeric characters PMU1 PORT PHS-14...
  • Page 247 PMU1 PORT D-CH-1 NORMAL STATE to PMU1 PORT D-CH-16 NORMAL STATE: These settings allow for specify- ing a normal state for each digital channel. These states are transmitted in configuration frames to the data concentra- tor. GE Multilin T60 Transformer Protection System 5-109...
  • Page 248  PMU 1 USER PMU1 USER TRIGGER:  TRIGGER The user trigger allows customized triggering logic to be constructed from FlexLogic™. The entire triggering logic is refreshed once every two power system cycles. 5-110 T60 Transformer Protection System GE Multilin...
  • Page 249 PMU 1 FREQ TRIGGER HIGH-FREQ: PMU 1 FREQ TRIGGER DPO TIME: PMU 1 SIGNAL FLEXLOGIC OPERAND SOURCE: 0< f < LOW-FREQ PMU 1 FREQ TRIGGER FREQUENCY, f f > HIGH-FREQ 847002A2.CDR Figure 5–39: FREQUENCY TRIGGER SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-111...
  • Page 250 PMU 1 VOLT TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor- mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig- gering condition is asserted). 5-112 T60 Transformer Protection System GE Multilin...
  • Page 251 PMU 1 CURR TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor- mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig- gering condition is asserted). GE Multilin T60 Transformer Protection System 5-113...
  • Page 252 For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second- ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin- gle-phase power. The comparator applies a 3% hysteresis. 5-114 T60 Transformer Protection System GE Multilin...
  • Page 253 S > APPARENT PICKUP APPARENT POWER, SB S > APPARENT PICKUP APPARENT POWER, SC S > APPARENT PICKUP 3P APPARENT POWER, S S > 3*(APPARENT PICKUP) 847003A1.CDR Figure 5–42: POWER TRIGGER SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-115...
  • Page 254 PMU 1 df/dt TRIGGER DPO TIME: PMU 1 SIGNAL FLEXLOGIC OPERAND SOURCE: df/dt > RAISE PMU 1 ROCOF TRIGGER ROCOF, df/dt –df/dt > FALL 847000A1.CDR Figure 5–43: RATE OF CHANGE OF FREQUENCY TRIGGER SCHEME LOGIC 5-116 T60 Transformer Protection System GE Multilin...
  • Page 255 Range: available synchrophasor values PMU 1 REC PHS-1: MESSAGE PMU 1 V1 Range: 16 character ASCII string PMU 1 REC PHS-1 MESSAGE NM: GE-UR-PMU-V1 ↓ Range: available synchrophasor values PMU 1 REC PHS-14: MESSAGE Range: 16 character ASCII string PMU 1 REC PHS-14...
  • Page 256 Record Record Record Record Free Other logical PMUs memory Record Record Record Record Record Other logical PMUs No further recording after all allocated memory is used 847706A1.CDR Figure 5–46: “PROTECTED” MODE 5-118 T60 Transformer Protection System GE Multilin...
  • Page 257 PMU 1 REC D-CH-1 NM to PMU 1 REC D-CH-16 NM: This setting allows custom naming of the digital channels. Six- teen-character ASCII strings are allowed as in the CHNAM field of the configuration frame. GE Multilin T60 Transformer Protection System...
  • Page 258 NETWORK UDP PORT 1: This setting selects the first UDP port that will be used for network reporting. • NETWORK UDP PORT 2: This setting selects the second UDP port that will be used for network reporting. 5-120 T60 Transformer Protection System GE Multilin...
  • Page 259: Flexlogic

    Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic™ minimizes the requirement for auxiliary components and wiring while making more complex schemes possible. GE Multilin T60 Transformer Protection System 5-121...
  • Page 260 The virtual input is presently in the ON state Virtual Output Virt Op 1 On The virtual output is presently in the set state (i.e. evaluation of the equation which produces this virtual output results in a "1") 5-122 T60 Transformer Protection System GE Multilin...
  • Page 261 Breaker restrike detected in phase B of the breaker control 1 element BRK RESTRIKE 1 OP C Breaker restrike detected in phase C of the breaker control 1 element BKR RESTRIKE 2 to 3 Same set of operands as shown for BKR RESTRIKE 1 GE Multilin T60 Transformer Protection System 5-123...
  • Page 262 GROUND TOC1 OP Ground time overcurrent 1 has operated overcurrent GROUND TOC1 DPO Ground time overcurrent 1 has dropped out GROUND TOC2 to 6 Same set of operands as shown for GROUND TOC1 5-124 T60 Transformer Protection System GE Multilin...
  • Page 263 Phase B of phase instantaneous overcurrent 1 has dropped out PHASE IOC1 DPO C Phase C of phase instantaneous overcurrent 1 has dropped out PHASE IOC2 to 12 Same set of operands as shown for PHASE IOC1 GE Multilin T60 Transformer Protection System 5-125...
  • Page 264 An unstable power swing has been detected (incoming locus) POWER SWING OUTGOING An unstable power swing has been detected (outgoing locus) POWER SWING UN/BLOCK Asserted when power swing is detected and de-asserted when a fault during power swing occurs 5-126 T60 Transformer Protection System GE Multilin...
  • Page 265 SWITCH 1 OPEN Disconnect switch 1 is open SWITCH 1 DISCREP Disconnect switch 1 has discrepancy SWITCH 1 TROUBLE Disconnect switch 1 trouble alarm SWITCH 2 Same set of operands as shown for SWITCH 1 GE Multilin T60 Transformer Protection System 5-127...
  • Page 266 Phase A of transformer percent differential has operated XFMR PCNT DIFF OP B Phase B of transformer percent differential has operated XFMR PCNT DIFF OP C Phase C of transformer percent differential has operated 5-128 T60 Transformer Protection System GE Multilin...
  • Page 267 An LED test has been initiated and has not finished LED test LED INDICATORS: LED USER 1 Asserted when user-programmable LED 1 is on User-programmable LED USER 2 to 48 The operand above is available for user-programmable LEDs 2 through 48 LEDs GE Multilin T60 Transformer Protection System 5-129...
  • Page 268 ID of any of these operands, the assigned name will appear in the relay list of operands. The default names are shown in the FlexLogic™ operands table above. The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic™ are listed in the Flex- Logic™ operators table. 5-130 T60 Transformer Protection System GE Multilin...
  • Page 269: Flexlogic™ Rules

    A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") may only be used once. If this rule is broken, a syntax error will be declared. GE Multilin T60 Transformer Protection System...
  • Page 270: Flexlogic™ Evaluation

    (i.e. Virtual Output 3). The final output must also be assigned to a virtual output as virtual output 4, which will be programmed in the contact output section to oper- ate relay H1 (that is, contact output H1). 5-132 T60 Transformer Protection System GE Multilin...
  • Page 271 Until accustomed to using FlexLogic™, it is suggested that a worksheet with a series of cells marked with the arbitrary parameter numbers be prepared, as shown below. GE Multilin T60 Transformer Protection System...
  • Page 272 99: The final output of the equation is virtual output 4 which is parameter “= Virt Op 4". 98: The operator preceding the output is timer 2, which is operand “TIMER 2". Note that the settings required for the timer are established in the timer programming section. 5-134 T60 Transformer Protection System GE Multilin...
  • Page 273 It is now possible to check that the selection of parameters will produce the required logic by converting the set of parame- ters into a logic diagram. The result of this process is shown below, which is compared to the logic for virtual output 4 dia- gram as a check. GE Multilin T60 Transformer Protection System 5-135...
  • Page 274 In the expression above, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a form of feedback, in this case, used to create a seal-in effect with the latch, and is correct. 5-136 T60 Transformer Protection System GE Multilin...
  • Page 275: Flexlogic™ Equation Editor

    TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". • TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0". GE Multilin T60 Transformer Protection System 5-137...
  • Page 276: Flexelements

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. 5-138 T60 Transformer Protection System GE Multilin...
  • Page 277 The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS GE Multilin T60 Transformer Protection System 5-139...
  • Page 278 DIRECTION = Under; FLEXELEMENT INPUT MODE = Signed; FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIRECTION = Under; FLEXELEMENT INPUT MODE = Absolute; FlexElement 1 OpSig 842706A2.CDR Figure 5–57: FLEXELEMENT™ INPUT MODE SETTING 5-140 T60 Transformer Protection System GE Multilin...
  • Page 279 “Delta”. FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. GE Multilin T60 Transformer Protection System 5-141...
  • Page 280: Non-Volatile Latches

    LATCH N LATCH N LATCH N LATCH N TYPE RESET Reset Dominant Previous Previous State State Dominant Previous Previous State State Figure 5–58: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC 5-142 T60 Transformer Protection System GE Multilin...
  • Page 281: Grouped Elements

    Each of the six setting group menus is identical. Setting group 1 (the default active group) automatically becomes active if no other group is active (see the Control elements section for additional details). GE Multilin T60 Transformer Protection System 5-143...
  • Page 282 (logic 1), the distance functions become memory-polarized regardless of the positive-sequence voltage magni- tude at this time. When the selected operand is de-asserted (logic 0), the distance functions follow other conditions of the memory voltage logic. 5-144 T60 Transformer Protection System GE Multilin...
  • Page 283 COMP LIMIT: 90° Range: 30 to 90° in steps of 1 PHS DIST Z1 MESSAGE DIR RCA: 85° Range: 30 to 90° in steps of 1 PHS DIST Z1 MESSAGE DIR COMP LIMIT: 90° GE Multilin T60 Transformer Protection System 5-145...
  • Page 284 PHS DIST Z1 DIR: All phase distance zones are reversible. The forward direction is defined by the PHS DIST Z1 RCA setting, whereas the reverse direction is shifted 180° from that angle. The non-directional zone spans between the for- 5-146 T60 Transformer Protection System GE Multilin...
  • Page 285 COMP LIMIT DIR COMP LIMIT DIR COMP LIMIT DIR RCA 837720A1.CDR Figure 5–60: DIRECTIONAL MHO DISTANCE CHARACTERISTIC COMP LIMIT REV REACH 837802A1.CDR Figure 5–61: NON-DIRECTIONAL MHO DISTANCE CHARACTERISTIC GE Multilin T60 Transformer Protection System 5-147...
  • Page 286 Figure 5–62: DIRECTIONAL QUADRILATERAL PHASE DISTANCE CHARACTERISTIC COMP LIMIT COMP LIMIT LFT BLD RCA RGT BLD RCA -LFT BLD RGT BLD REV REACH COMP LIMIT COMP LIMIT 837803A1.CDR Figure 5–63: NON-DIRECTIONAL QUADRILATERAL PHASE DISTANCE CHARACTERISTIC 5-148 T60 Transformer Protection System GE Multilin...
  • Page 287 DIR COMP LIMIT = 60 RGT BLD RCA = 90 RGT BLD RCA = 80 LFT BLD RCA = 90 LFT BLD RCA = 80 837723A1.CDR Figure 5–65: QUADRILATERAL DISTANCE CHARACTERISTIC SAMPLE SHAPES GE Multilin T60 Transformer Protection System 5-149...
  • Page 288 Therefore, in order to calculate the SIR value properly and to maintain the optimal operating speed of the distance ele- ments, you need to set zone 1 reach with a regular 80 to 85% of the line impedance reach setting, even when zone 1 is disabled. 5-150 T60 Transformer Protection System GE Multilin...
  • Page 289 PHS DIST Z1 DELAY: This setting allows the user to delay operation of the distance elements and implement stepped distance protection. The distance element timers for zones 2 and higher apply a short dropout delay to cope with faults GE Multilin T60 Transformer Protection System...
  • Page 290 2 operation when the fault evolves from one type to another or NOTE migrates from the initial zone to zone 2. Desired zones in the trip output function should be assigned to accomplish this functionality. 5-152 T60 Transformer Protection System GE Multilin...
  • Page 291 | IB – IC | > 3 × Pickup PH DIST Z1 SUPN IBC FLEXLOGIC OPERAND PH DIST Z1 SUPN ICA | IC – IA | > 3 × Pickup 837002AL.CDR Figure 5–70: PHASE DISTANCE SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-153...
  • Page 292 Range: 60 to 90° in steps of 1 GND DIST Z1 QUAD MESSAGE LFT BLD RCA: 85° Range: 0.050 to 30.000 pu in steps of 0.001 GND DIST Z1 MESSAGE SUPV: 0.200 pu 5-154 T60 Transformer Protection System GE Multilin...
  • Page 293 GND DIST Z1 REV REACH RCA • GND DIST Z1 SHAPE: This setting selects the shape of the ground distance characteristic between the mho and quadrilateral characteristics. The selection is available on a per-zone basis. GE Multilin T60 Transformer Protection System 5-155...
  • Page 294 (3I_0) measured in the direction of the zone being compensated must be connected to the ground input CT of the CT bank configured under the . This setting specifies the ratio between the magnitudes of the mutual DISTANCE SOURCE 5-156 T60 Transformer Protection System GE Multilin...
  • Page 295 GND DIST Z1 DIR RCA: Selects the characteristic angle (or ‘maximum torque angle’) of the directional supervising function. If the mho shape is applied, the directional function is an extra supervising function, as the dynamic mho GE Multilin T60 Transformer Protection System...
  • Page 296 GND DIST Z1 SUPN IN OPEN POLE OP ** ** D60, L60, and L90 only. Other UR-series models apply regular current seal-in for zone 1. 837018A7.CDR Figure 5–73: GROUND DISTANCE ZONE 1 OP SCHEME 5-158 T60 Transformer Protection System GE Multilin...
  • Page 297 3 or 4 to zone 2. The desired zones should be assigned in the trip output element to accomplish this functionality. Figure 5–75: GROUND DISTANCE ZONES 3 AND HIGHER OP SCHEME GE Multilin T60 Transformer Protection System 5-159...
  • Page 298 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–76: GROUND DISTANCE ZONE 1 SCHEME LOGIC 5-160 T60 Transformer Protection System GE Multilin...
  • Page 299 The supervision is biased toward operation in order to avoid compromising the sensitivity of ground distance elements at low signal levels. Otherwise, the reverse fault condition that generates concern will have high polarizing levels so that a cor- rect reverse fault decision can be reliably made. GE Multilin T60 Transformer Protection System 5-161...
  • Page 300 LIMIT ANGLE: 120° Range: 40 to 140° in steps of 1 POWER SWING MIDDLE MESSAGE LIMIT ANGLE: 90° Range: 40 to 140° in steps of 1 POWER SWING INNER MESSAGE LIMIT ANGLE: 60° 5-162 T60 Transformer Protection System GE Multilin...
  • Page 301 Different protection elements respond differently to power swings. If tripping is required for faults during power swing condi- tions, some elements may be blocked permanently (using the operand), and others may be blocked POWER SWING BLOCK and dynamically unblocked upon fault detection (using the operand). POWER SWING UN/BLOCK GE Multilin T60 Transformer Protection System 5-163...
  • Page 302 The element can be set to use either lens (mho) or rectangular (quadrilateral) characteristics as illustrated below. When set to “Mho”, the element applies the right and left blinders as well. If the blinders are not required, their settings should be set high enough to effectively disable the blinders. 5-164 T60 Transformer Protection System GE Multilin...
  • Page 303 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–79: POWER SWING DETECT MHO OPERATING CHARACTERISTICS Figure 5–80: EFFECTS OF BLINDERS ON THE MHO CHARACTERISTICS GE Multilin T60 Transformer Protection System 5-165...
  • Page 304 POWER SWING SHAPE: This setting selects the shapes (either “Mho” or “Quad”) of the outer, middle and, inner char- acteristics of the power swing detect element. The operating principle is not affected. The “Mho” characteristics use the left and right blinders. 5-166 T60 Transformer Protection System GE Multilin...
  • Page 305 (the actual trip may be delayed as per the setting). Therefore, this angle must be selected in consider- TRIP MODE ation to the power swing angle beyond which the system becomes unstable and cannot recover. GE Multilin T60 Transformer Protection System 5-167...
  • Page 306 The power swing blocking function is operational all the time as long as the element is enabled. The blocking signal resets the output operand but does not stop the out-of-step tripping sequence. POWER SWING TRIP 5-168 T60 Transformer Protection System GE Multilin...
  • Page 307 K_0, K_2 - three times the average change over last power cycle 842008A1.CDR K_1 - four times the average change over last power cycle Figure 5–83: POWER SWING DETECT SCHEME LOGIC (2 of 3) GE Multilin T60 Transformer Protection System 5-169...
  • Page 308 POWER SWING BLK: L1 AND L4 LATCHES ARE SET DOMINANT L2, L3 AND L5 LATCHES ARE RESET DOMINANT Off=0 FLEXLOGIC OPERAND POWER SWING OUTGOING 827841A4.CDR Figure 5–84: POWER SWING DETECT SCHEME LOGIC (3 of 3) 5-170 T60 Transformer Protection System GE Multilin...
  • Page 309: Load Encroachment

    The element operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be used to block selected protection elements such as distance or phase overcurrent. The following figure shows an effect of the load encroachment characteristics used to block the quadrilateral distance element. GE Multilin T60 Transformer Protection System 5-171...
  • Page 310 LOAD ENCHR DPO Load Encroachment LOAD ENCROACHMENT LOAD ENCROACHMENT LOAD ENCHR OP Characteristic SOURCE: MIN VOLT: Pos Seq Voltage (V_1) V_1 > Pickup Pos Seq Current (I_1) 827847A2.CDR Figure 5–87: LOAD ENCROACHMENT SCHEME LOGIC 5-172 T60 Transformer Protection System GE Multilin...
  • Page 311: Transformer Elements

    IEEE standards C57.91-1995: “IEEE Guide for Loading Mineral-Oil-Immersed Transformers” and C57.96-1989: “IEEE Guide for Loading Dry-Type Distribution Transformers”. The computations are based on transformer loading conditions, ambient temperature, and the entered transformer data. GE Multilin T60 Transformer Protection System 5-173...
  • Page 312 × (EQ 5.28) comp comp comp comp comp The element operates if I > PKP and I > I , where PKP represents a differential pickup setting and K is a restraint factor. 5-174 T60 Transformer Protection System GE Multilin...
  • Page 313 Onload tap changer operation: it adjusts the transformer ratio and consequently the winding currents. CT saturation. Breakpoint 2 Transition region Slope 2 (cubic spline) region Breakpoint 1 Pickup 828750A1.CDR Figure 5–89: PERCENT DIFFERENTIAL OPERATING CHARACTERISTIC GE Multilin T60 Transformer Protection System 5-175...
  • Page 314 OVEREXCITATION INHIBIT LEVEL: This setting is provided to block the differential protection during overexcitation. When the 5th harmonic level exceeds the specified setting (5th harmonic ratio) the differential element is blocked. The overexcitation inhibit works on a per-phase basis. 5-176 T60 Transformer Protection System GE Multilin...
  • Page 315 Iad5 LEVEL ACTUAL VALUES XFMR PCNT DIFF 5TH B > Ibd5 LEVEL DIFF 5TH HARM XFMR PCNT DIFF 5TH C > Icd5 LEVEL Iad5 Ibd5 Icd5 828001A6.CDR Figure 5–90: PERCENT DIFFERENTIAL SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-177...
  • Page 316 The Hottest-Spot Temperature element provides a mechanism for detecting abnormal winding hottest-spot temperatures inside the transformer. It can be set to alarm or trip in cases where the computed hottest-spot temperature is above the pickup threshold for a user-specified time (considered as transformer overheating). 5-178 T60 Transformer Protection System GE Multilin...
  • Page 317 AGING FACTOR PICKUP DELAY: SETTING FLEXLOGIC OPERANDS AGING FACTOR AGING FACTOR PKP BLOCK: FAA > PKP Off=0 AGING FACTOR DPO ACTUAL VALUE AGING FACTOR OP AGING FACTOR-FAA 828733A2.CDR Figure 5–93: AGING FACTOR LOGIC GE Multilin T60 Transformer Protection System 5-179...
  • Page 318 PICKUP: SETTING LOSS OF LIFE BLOCK: FLEXLOGIC OPERANDS Off=0 LOSS OF LIFE PKP LOL > PKP ACTUAL VALUE LOSS OF LIFE OP XFMR LIFE LOST 828732A2.CDR Figure 5–94: TRANSFORMER LOSS OF LIFE LOGIC 5-180 T60 Transformer Protection System GE Multilin...
  • Page 319: Phase Current

    INVERSE TOC CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 320 5.041 4.827 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 5-182 T60 Transformer Protection System GE Multilin...
  • Page 321 0.60 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 GE Multilin T60 Transformer Protection System 5-183...
  • Page 322 = characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–20: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...
  • Page 323 = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The T60 uses the FlexCurve™ feature to facilitate programming of 41 recloser curves. Please refer to the FlexCurve™ sec- tion in this chapter for additional details. GE Multilin T60 Transformer Protection System 5-185...
  • Page 324 (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic curve (see the figure below); the pickup level is calculated as ‘Mvr’ times the setting. If the voltage restraint feature PHASE TOC1 PICKUP is disabled, the pickup level always remains at the setting value. 5-186 T60 Transformer Protection System GE Multilin...
  • Page 325 PHASE TOC1 C DPO Multiplier-Phase C PHASE TOC1 C OP SETTING PHASE TOC1 PKP PHASE TOC1 VOLT RESTRAINT: PHASE TOC1 OP Enabled PHASE TOC1 DPO 827072A4.CDR Figure 5–96: PHASE TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-187...
  • Page 326 The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a definite time element. The input current is the fundamental phasor magnitude. The phase instantaneous overcurrent timing curves are shown below for form-A contacts in a 60 Hz system. 5-188 T60 Transformer Protection System GE Multilin...
  • Page 327 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–97: PHASE INSTANTANEOUS OVERCURRENT TIMING CURVES Figure 5–98: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-189...
  • Page 328 30° +90° Phasors for Phase A Polarization: × VPol = VBC (1/_ECA) = polarizing voltage IA = operating current ECA = Element Characteristic Angle at 30° 827800A2.CDR Figure 5–99: PHASE A DIRECTIONAL POLARIZATION 5-190 T60 Transformer Protection System GE Multilin...
  • Page 329 When set to "Yes", the directional element blocks the operation of any phase overcurrent element under directional control, when voltage memory expires; when set to "No", the directional element allows tripping of phase overcurrent elements under directional control. GE Multilin T60 Transformer Protection System 5-191...
  • Page 330 FLEXLOGIC OPERAND PHASE B LOGIC SIMILAR TO PHASE A PH DIR1 BLK B FLEXLOGIC OPERAND PHASE C LOGIC SIMILAR TO PHASE A PH DIR1 BLK C 827078A6.CDR Figure 5–100: PHASE DIRECTIONAL SCHEME LOGIC 5-192 T60 Transformer Protection System GE Multilin...
  • Page 331: Neutral Current

    MESSAGE   NEUTRAL IOC1 MESSAGE See page 5–195.   NEUTRAL IOC2 MESSAGE See page 5–195.  ↓  NEUTRAL IOC12 MESSAGE   NEUTRAL MESSAGE See page 5–196.  DIRECTIONAL OC1 GE Multilin T60 Transformer Protection System 5-193...
  • Page 332 SETTING NEUTRAL TOC1 PKP RESET: NEUTRAL TOC1 IN ≥ PICKUP NEUTRAL TOC1 DPO SOURCE: NEUTRAL TOC1 OP SETTING NEUTRAL TOC1 BLOCK: Off = 0 827034A3.VSD Figure 5–101: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC 5-194 T60 Transformer Protection System GE Multilin...
  • Page 333 NEUTRAL IOC1 PICKUP: RESET DELAY : SETTING NEUTRAL IOC1 DPO NEUTRAL IOC1 OP 3( _0 - K _1 ) PICKUP NEUTRAL IOC1 BLOCK: Off=0 SETTING NEUTRAL IOC1 SOURCE: 827035A4.CDR Figure 5–102: NEUTRAL IOC1 SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-195...
  • Page 334 × × (EQ 5.38) – The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents resulting from: • System unbalances under heavy load conditions. 5-196 T60 Transformer Protection System GE Multilin...
  • Page 335 REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation) The above bias should be taken into account when using the neutral directional overcurrent element to directionalize other protection elements. GE Multilin T60 Transformer Protection System 5-197...
  • Page 336 If “Dual” polarizing is selected, the element performs both directional comparisons as described above. A given direction is confirmed if either voltage or current comparators indicate so. If a conflicting (simultaneous forward and reverse) indication occurs, the forward direction overrides the reverse direction. 5-198 T60 Transformer Protection System GE Multilin...
  • Page 337 NEUTRAL DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the reverse direction. When selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique for the “Calculated 3I0” mode of operation. GE Multilin T60 Transformer Protection System 5-199...
  • Page 338 3) POSITIVE SEQUENCE RESTRAINT IS NOT APPLIED WHEN _1 IS BELOW 0.8pu NEUTRAL DIR OC1 POS- SEQ RESTRAINT: 3( _0 - K _1 ) PICKUP 827077AB.CDR PICKUP Figure 5–104: NEUTRAL DIRECTIONAL OVERCURRENT LOGIC 5-200 T60 Transformer Protection System GE Multilin...
  • Page 339: Ground Current

     RESTRICTED GROUND MESSAGE See page 5–204.  FAULT 1 ↓  RESTRICTED GROUND MESSAGE  FAULT 6 For additional information on the Ground Time Overcurrent curves, refer to Inverse TOC Characteristics on page 5–181. GE Multilin T60 Transformer Protection System 5-201...
  • Page 340 ETT NG GROUND TOC1 PKP RESET: GROUND TOC1 GROUND TOC1 DPO IG ≥ PICKUP SOURCE: GROUND TOC1 OP ETT NG GROUND TOC1 BLOCK: Off = 0 827036A3.VSD Figure 5–105: GROUND TOC1 SCHEME LOGIC 5-202 T60 Transformer Protection System GE Multilin...
  • Page 341 ETT NG DELAY: GROUND IOC1 GROUND IOC1 RESET ETT NG PICKUP: DELAY: GROUND IOC1 SOURCE: IG ≥ PICKUP ETT NG GROUND IOC1 BLOCK: 827037A4.VSD Off = 0 Figure 5–106: GROUND IOC1 SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-203...
  • Page 342 Application of the restricted ground fault pro- tection extends the coverage towards the neutral point (see the RGF and Percent Differential Zones of Protection diagram). WINDING DIFFERENTIAL ZONE ZONE 842731A1.CDR Figure 5–107: RGF AND PERCENT DIFFERENTIAL ZONES OF PROTECTION 5-204 T60 Transformer Protection System GE Multilin...
  • Page 343 (EQ 5.40) The zero-sequence component of the restraining signal (IR0) is meant to provide maximum restraint during external ground faults, and therefore is calculated as a vectorial difference of the ground and neutral currents: GE Multilin T60 Transformer Protection System 5-205...
  • Page 344 RST RESTD GND FT1 SLOPE: RESTD GND FT1 SOURCE: Differential > SLOPE * Restraining Currents ACTUAL VALUES RGF 1 gd Mag RGF 1 gr Mag 828002A2.CDR Figure 5–109: RESTRICTED GROUND FAULT SCHEME LOGIC 5-206 T60 Transformer Protection System GE Multilin...
  • Page 345 Igd = abs(3 × 3.3 + 0.0) = 10 pu, IR0 = abs(3 × 3.3 – (0.0)) = 10 pu, IR2 = 3 × 3.3 = 10 pu, IR1 = 3 × (3.33 – 3.33) = 0 pu, and Igr = 10 pu The differential current is 100% of the restraining current. GE Multilin T60 Transformer Protection System 5-207...
  • Page 346: Breaker Failure

    Range: 0.001 to 30.000 pu in steps of 0.001 BF1 N AMP HISET MESSAGE PICKUP: 1.050 pu Range: 0.001 to 30.000 pu in steps of 0.001 BF1 PH AMP LOSET MESSAGE PICKUP: 1.050 pu 5-208 T60 Transformer Protection System GE Multilin...
  • Page 347 This can also occur in breaker-and-a-half or ring bus configurations where the first breaker closes into a fault; the protection trips and attempts to initiate breaker failure for the second breaker, which is in the process of closing, but does not yet have current flowing through it. GE Multilin T60 Transformer Protection System 5-209...
  • Page 348 BREAKER FAILURE TIMER No. 2 (±1/8 cycle) INITIATE (1/8 cycle) BREAKER FAILURE CURRENT DETECTOR PICKUP (1/8 cycle) BREAKER FAILURE OUTPUT RELAY PICKUP (1/4 cycle) FAULT cycles OCCURS 827083A6.CDR Figure 5–110: BREAKER FAILURE MAIN PATH SEQUENCE 5-210 T60 Transformer Protection System GE Multilin...
  • Page 349 BF1 TIMER 3 PICKUP DELAY: Timer 3 is set to the same interval as timer 2, plus an increased safety margin. Because this path is intended to operate only for low level faults, the delay can be in the order of 300 to 500 ms. GE Multilin T60 Transformer Protection System...
  • Page 350 Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command should be given via output operand BKR FAIL 1 TRIP OP 5-212 T60 Transformer Protection System GE Multilin...
  • Page 351 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–112: SINGLE-POLE BREAKER FAILURE, INITIATE GE Multilin T60 Transformer Protection System 5-213...
  • Page 352 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–113: SINGLE-POLE BREAKER FAILURE, TIMERS 5-214 T60 Transformer Protection System GE Multilin...
  • Page 353 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–114: THREE-POLE BREAKER FAILURE, INITIATE GE Multilin T60 Transformer Protection System 5-215...
  • Page 354 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–115: THREE-POLE BREAKER FAILURE, TIMERS 5-216 T60 Transformer Protection System GE Multilin...
  • Page 355: Voltage Elements

    The time delay is adjustable from 0 to 600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay char- acteristic. GE Multilin T60 Transformer Protection System 5-217...
  • Page 356 V = secondary voltage applied to the relay = pickup level pickup % of voltage pickup 842788A1.CDR Figure 5–116: INVERSE TIME UNDERVOLTAGE CURVES At 0% of pickup, the operating time equals the setting. UNDERVOLTAGE DELAY NOTE 5-218 T60 Transformer Protection System GE Multilin...
  • Page 357 Source VT = Wye FLEXLOGIC OPERAND SETTING PHASE UV1 PKP PHASE UV1 MODE: FLEXLOGIC OPERAND Phase to Ground Phase to Phase PHASE UV1 OP FLEXLOGIC OPERAND PHASE UV1 DPO 827039AB.CDR Figure 5–117: PHASE UNDERVOLTAGE1 SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-219...
  • Page 358 FLEXLOGIC OPERAND PHASE OV1 PKP 827066A7.CDR Figure 5–118: PHASE OVERVOLTAGE SCHEME LOGIC > × If the source VT is wye-connected, then the phase overvoltage pickup condition is Pickup for V and V NOTE 5-220 T60 Transformer Protection System GE Multilin...
  • Page 359 “Definite time”. The source assigned to this element must be configured for a phase VT. NEUTRAL OV1 CURVE VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to be wye-connected. Figure 5–119: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-221...
  • Page 360 Vx Pickup AUX UV1 PKP AUX UV1 DPO SETTING SETTING AUX UV1 OP AUX UV1 MINIMUM AUX UV1 SIGNAL VOLTAGE: SOURCE: < AUX VOLT Vx Vx Minimum 827849A2.CDR Figure 5–120: AUXILIARY UNDERVOLTAGE SCHEME LOGIC 5-222 T60 Transformer Protection System GE Multilin...
  • Page 361 AUX OV1 RESET Off=0 DELAY : FLEXLOGIC OPERANDS < Vx Pickup AUX OV1 OP SETTING AUX OV1 DPO AUX OV1 SIGNAL AUX OV1 PKP SOURCE: AUXILIARY VOLT (Vx) 827836A2.CDR Figure 5–121: AUXILIARY OVERVOLTAGE SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-223...
  • Page 362 Step 1 above. If the measured voltage of all three phase voltages is 0, than the per- unit value becomes automatically 0 regardless of the presence of auxiliary voltage. 5-224 T60 Transformer Protection System GE Multilin...
  • Page 363 F = frequency of voltage signal (pu) Pickup = volts-per-hertz pickup setpoint (pu) The volts/hertz inverse A curves are shown below. Time delay setting Multiples of volts per hertz pickup 830738A1.CDR Figure 5–123: VOLTS-PER-HERTZ CURVES, INVERSE CURVE A GE Multilin T60 Transformer Protection System 5-225...
  • Page 364 T = Operating Time TDM = Time Delay Multiplier (delay in sec.) V = fundamental RMS value of voltage (pu) F = frequency of voltage signal (pu) Pickup = volts-per-hertz pickup setpoint (pu) 5-226 T60 Transformer Protection System GE Multilin...
  • Page 365 5 SETTINGS 5.6 GROUPED ELEMENTS The volts/hertz inverse C curves are shown below. Time delay setting Multiples of volts per hertz pickup 830740A1.CDR Figure 5–125: VOLTS-PER-HERTZ CURVES, INVERSE CURVE C GE Multilin T60 Transformer Protection System 5-227...
  • Page 366: Control Elements

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. 5-228 T60 Transformer Protection System GE Multilin...
  • Page 367 TRIP BUS 1 PKP = Enabled TRIP BUS 1 BLOCK = Off SETTINGS TRIP BUS 1 LATCHING = Enabled TRIP BUS 1 RESET = Off FLEXLOGIC OPERAND RESET OP 842023A1.CDR Figure 5–127: TRIP BUS LOGIC GE Multilin T60 Transformer Protection System 5-229...
  • Page 368: Setting Groups

    The assigned operand is used to control the “On” state of a particular settings group. VIRTUAL OUTPUT 1 5-230 T60 Transformer Protection System GE Multilin...
  • Page 369: Selector Switch

    Range: FlexLogic™ operand SELECTOR 1 3BIT ACK: MESSAGE Range: Restore, Synchronize, Sync/Restore SELECTOR 1 POWER-UP MESSAGE MODE: Restore Range: Self-reset, Latched, Disabled SELECTOR 1 TARGETS: MESSAGE Self-reset Range: Disabled, Enabled SELECTOR 1 EVENTS: MESSAGE Disabled GE Multilin T60 Transformer Protection System 5-231...
  • Page 370 • SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con- trol word pre-selects the position using the following encoding convention: POSITION rest 5-232 T60 Transformer Protection System GE Multilin...
  • Page 371 The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. GE Multilin T60 Transformer Protection System 5-233...
  • Page 372 3BIT A1 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–129: TIME-OUT MODE 5-234 T60 Transformer Protection System GE Multilin...
  • Page 373 Make the following changes to selector switch element in the    SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 GE Multilin T60 Transformer Protection System 5-235...
  • Page 374 3-bit acknowledge SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–131: SELECTOR SWITCH LOGIC 5-236 T60 Transformer Protection System GE Multilin...
  • Page 375: Underfrequency

    SETTING ≤ 0 < f PICKUP UNDERFREQ 1 OP UNDERFREQ 1 ACTUAL VALUES MIN VOLT / AMP: UNDERFREQ 1 SOURCE: ≥ Level Minimum VOLT / AMP Frequency 827079A8.CDR Figure 5–132: UNDERFREQUENCY SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-237...
  • Page 376: Overfrequency

    OVERFREQ 1 BLOCK: OVERFREQ 1 RESET OVERFREQ 1 PKP DELAY : Off = 0 OVERFREQ 1 DPO OVERFREQ 1 OP SETTING ≥ PICKUP OVERFREQ 1 SOURCE: Frequency 827832A5.CDR Figure 5–133: OVERFREQUENCY SCHEME LOGIC 5-238 T60 Transformer Protection System GE Multilin...
  • Page 377: Synchrocheck

    V1 or V2 to traverse an angle equal to 2 × ΔΦ at a frequency equal to the frequency difference ΔF. This time can be calculated by: GE Multilin T60 Transformer Protection System...
  • Page 378 SYNCHK1 LIVE V2 MIN VOLT: This setting establishes a minimum voltage magnitude for V2 in ‘pu’. Above this mag- nitude, the V2 voltage input used for synchrocheck will be considered “Live” or energized. 5-240 T60 Transformer Protection System GE Multilin...
  • Page 379 The relay will use the phase channel of a three-phase set of voltages if pro- grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as part of the Source and a three-phase set is not. GE Multilin T60 Transformer Protection System 5-241...
  • Page 380 5.7 CONTROL ELEMENTS 5 SETTINGS Figure 5–134: SYNCHROCHECK SCHEME LOGIC 5-242 T60 Transformer Protection System GE Multilin...
  • Page 381: Digital Elements

    DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”. • DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to “Disabled”, the operation of the pickup LED is blocked. GE Multilin T60 Transformer Protection System 5-243...
  • Page 382 In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. Figure 5–136: TRIP CIRCUIT EXAMPLE 1 5-244 T60 Transformer Protection System GE Multilin...
  • Page 383 In this case, it is not required to supervise the monitoring circuit with the breaker position – the setting is BLOCK selected to “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). Figure 5–137: TRIP CIRCUIT EXAMPLE 2 GE Multilin T60 Transformer Protection System 5-245...
  • Page 384: Digital Counters

    –2,147,483,648 counts, the counter will rollover to +2,147,483,647. • COUNTER 1 BLOCK: Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are blocked. 5-246 T60 Transformer Protection System GE Multilin...
  • Page 385 COUNTER 1 RESET: COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A1.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–138: DIGITAL COUNTER SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-247...
  • Page 386: Monitoring Elements

    See page 5–258.   VT FUSE FAILURE 5 MESSAGE See page 5–258.   VT FUSE FAILURE 6 MESSAGE See page 5–258.   THERMAL OVERLOAD MESSAGE See page 5–259.  PROTECTION 5-248 T60 Transformer Protection System GE Multilin...
  • Page 387 • BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set. GE Multilin T60 Transformer Protection System 5-249...
  • Page 388 BKR 1 ARCING AMP C Φ 827071A3.CDR BKR 1 OPERATING TIME A Φ BKR 1 OPERATING TIME B Φ BKR 1 OPERATING TIME C Φ BKR 1 OPERATING TIME Figure 5–140: BREAKER ARCING CURRENT SCHEME LOGIC 5-250 T60 Transformer Protection System GE Multilin...
  • Page 389 Voltage drop measured from either side of the breaker during the flashover period, Voltage difference drop, and Measured flashover current through the breaker. Furthermore, the scheme is applicable for cases where either one or two sets of three-phase voltages are available across the breaker. GE Multilin T60 Transformer Protection System 5-251...
  • Page 390 This application does not require detection of breaker status via a 52a contact, as it uses a voltage difference larger than setting. However, monitoring the breaker contact will ensure scheme stability. BRK 1 FLSHOVR DIFF V PKP 5-252 T60 Transformer Protection System GE Multilin...
  • Page 391 Depending on the flashover protection application, the flashover current can vary from levels of the charging current when the line is de-energized (all line breakers open), to well above the maximum line (feeder) load (line/feeder con- nected to load). GE Multilin T60 Transformer Protection System 5-253...
  • Page 392 BRK 1 FLSHOVR DIFF V SRC: PKP: SRC 1 SRC 2 SRC 6 , … , , none ΔVA > PKP Δ VA = VA - Va 842018A2.CDR Figure 5–141: BREAKER FLASHOVER SCHEME LOGIC 5-254 T60 Transformer Protection System GE Multilin...
  • Page 393 A restrike event (FlexLogic™ operand) is declared if all of the following hold: • The current is initially interrupted. GE Multilin T60 Transformer Protection System 5-255...
  • Page 394 “1” when breaker is opened, either manually or from protection logic. • BRK RSTR 1 CLS CMD: This setting assigns a FlexLogic™ operand indicating a breaker close command. It must be logic “1” when breaker is closed. 5-256 T60 Transformer Protection System GE Multilin...
  • Page 395 BKR RSTR 1 BKR OPEN = Off FLEXLOGIC OPERAND BKR RESTRIKE 1 OP SETTING BKR RSTR 1 OPEN CMD = Off SETTING BKR RSTR 1 CLS CMD = Off 834012A1.CDR Figure 5–144: BREAKER RESTRIKE SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-257...
  • Page 396 An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized; positive- sequence voltage and current are both below threshold levels. The function setting enables and disables the fuse failure feature for each source. Figure 5–145: VT FUSE FAIL SCHEME LOGIC 5-258 T60 Transformer Protection System GE Multilin...
  • Page 397 I = measured overload RMS current. • = measured load RMS current before overload occurs. • k= IEC 255-8 k-factor applied to I , defining maximum permissible current above nominal current. • = protected element base (nominal) current. GE Multilin T60 Transformer Protection System 5-259...
  • Page 398 , element starts increasing the thermal energy: t Δ -------------- - (EQ 5.52) – op In When current is less than the dropout level, I > 0.97 × k × I , the element starts decreasing the thermal energy: 5-260 T60 Transformer Protection System GE Multilin...
  • Page 399 30 minutes Busbar 60 minutes 20 minutes Underground cable 20 to 60 minutes 60 minutes The logic for the thermal overload protection element is shown below. Figure 5–147: THERMAL OVERLOAD PROTECTION SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-261...
  • Page 400: Pilot Schemes

    POTT RX PICKUP DELAY: This setting enables the relay to cope with spurious receive signals. The delay should be set longer than the longest spurious signal that can occur simultaneously with the zone 2 pickup. The selected delay will increase the response time of the scheme. 5-262 T60 Transformer Protection System GE Multilin...
  • Page 401 Typically, the output operand should be programmed to initiate a trip, breaker fail, and autoreclose, and drive a user-programmable LED as per user application. GE Multilin T60 Transformer Protection System...
  • Page 402 POTT TX DELAY: FLEXLOGIC OPERAND ECHO DURATION: LINE PICKUP LEO PKP ECHO LOCKOUT: SETTING Echo duration and lockout logic POTT PERMISSIVE ECHO: Disabled = 0 Enabled = 1 837014A9.CDR Figure 5–148: POTT SCHEME LOGIC 5-264 T60 Transformer Protection System GE Multilin...
  • Page 403: Inputs And Outputs

    The update is performed at the beginning of the protection pass so all protection and control functions, as well as FlexLogic™ equations, are fed with the updated states of the contact inputs. GE Multilin T60 Transformer Protection System...
  • Page 404 Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. 5-266 T60 Transformer Protection System GE Multilin...
  • Page 405: Virtual Inputs

    SETTING “Virtual Input 1 to OFF = 0” VIRTUAL INPUT 1 ID: (Flexlogic Operand) SETTING Virt Ip 1 VIRTUAL INPUT 1 TYPE: Latched Self - Reset 827080A2.CDR Figure 5–150: VIRTUAL INPUTS SCHEME LOGIC GE Multilin T60 Transformer Protection System 5-267...
  • Page 406: Contact Outputs

    L-Cont Op 1 Range: FlexLogic™ operand OUTPUT H1a OPERATE: MESSAGE Range: FlexLogic™ operand OUTPUT H1a RESET: MESSAGE Range: Operate-dominant, Reset-dominant OUTPUT H1a TYPE: MESSAGE Operate-dominant Range: Disabled, Enabled OUTPUT H1a EVENTS: MESSAGE Disabled 5-268 T60 Transformer Protection System GE Multilin...
  • Page 407 Application Example 3: A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement this functionality as described below: GE Multilin T60 Transformer Protection System 5-269...
  • Page 408: Virtual Outputs

    FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings would be programmed as follows: 5-270 T60 Transformer Protection System GE Multilin...
  • Page 409: Remote Devices

    SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE    setting. CONFIGURATION TRANSMISSION GSSE GSSE ID In T60 releases previous to 5.0x, these name strings were represented by the setting. RELAY NAME GE Multilin T60 Transformer Protection System 5-271...
  • Page 410: Remote Inputs

    (see the Remote devices section). The setting selects the specific bits of the REMOTE DEVICE (16) ID REMOTE IN 1 ITEM GSSE/GOOSE message required. 5-272 T60 Transformer Protection System GE Multilin...
  • Page 411: Remote Double-Point Status Inputs

    REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUTPUTS DNA- 1(32) BIT PAIR Range: FlexLogic™ operand  REMOTE OUTPUTS DNA- 1 OPERAND:  DNA- 1 BIT PAIR Range: Disabled, Enabled DNA- 1 EVENTS: MESSAGE Disabled GE Multilin T60 Transformer Protection System 5-273...
  • Page 412: Remote Outputs

    RESET OP to identify the source of the command. The setting RESET OP (PUSHBUTTON) RESET OP (COMMS) RESET OP (OPERAND) shown above selects the operand that will create the operand. RESET OP (OPERAND) 5-274 T60 Transformer Protection System GE Multilin...
  • Page 413: Direct Inputs And Outputs

    FlexLogic™ operand that determines the state of this direct output. c) APPLICATION EXAMPLES The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs. GE Multilin T60 Transformer Protection System 5-275...
  • Page 414 DIRECT INPUT 7 DEFAULT STATE : "3" DIRECT INPUT 8 DEVICE ID : "3" DIRECT INPUT 8 BIT NUMBER : select "On" for security, select "Off" for dependability DIRECT INPUT 8 DEFAULT STATE 5-276 T60 Transformer Protection System GE Multilin...
  • Page 415 "3" (effectively, this is a message from IED 1) DIRECT INPUT 6 BIT NUMBER: UR IED 2: "1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "3" DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: GE Multilin T60 Transformer Protection System 5-277...
  • Page 416: Teleprotection Inputs And Outputs

    Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-1 MESSAGE DEFAULT: Off Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-2 MESSAGE DEFAULT: Off ↓ Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-16 MESSAGE DEFAULT: Off 5-278 T60 Transformer Protection System GE Multilin...
  • Page 417 (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel failure between any pair of relays. GE Multilin T60 Transformer Protection System 5-279...
  • Page 418: Iec 61850 Goose Analogs

    GOOSE analog input value. GOOSE Analogs are floating-point values, with no units. The GOOSE UNIT and PU base settings allow the user to configure GOOSE Analog, so that it can be used in a FlexElement. 5-280 T60 Transformer Protection System GE Multilin...
  • Page 419: Iec 61850 Goose Integers

    MESSAGE MODE: Default Value The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger™ values between any two UR- series devices. The following settings are available for each GOOSE uinteger input. GE Multilin T60 Transformer Protection System 5-281...
  • Page 420 “Default Value”, then the value of the GOOSE uinteger input is defined by the setting. UINTEGER 1 DEFAULT The GOOSE integer input FlexInteger™ values are available for use in other T60 functions that use FlexInteger™ values. 5-282 T60 Transformer Protection System GE Multilin...
  • Page 421: Transducer Inputs And Outputs

    –20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT F1 MIN VALUE DCMA INPUT F1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE GE Multilin T60 Transformer Protection System 5-283...
  • Page 422: Rtd Inputs

    1.5 pu. FlexElement™ operands are available to FlexLogic™ for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. 5-284 T60 Transformer Protection System GE Multilin...
  • Page 423: Rrtd Inputs

     RRTD See page 5-286.    RRTD MESSAGE See page 5-286.  ↓  RRTD 12 MESSAGE See page 5-286.  Menus are available to configure each of the remote RTDs. GE Multilin T60 Transformer Protection System 5-285...
  • Page 424 “None”. RRTD 1 FUNCTION RRTD1 APPLICATION • If the settings are changes, then these settings are immediately written to the RRTD 1 APPLICATION RRTD 1 TYPE RRTD device. 5-286 T60 Transformer Protection System GE Multilin...
  • Page 425 172.46 291.96 231.6 16.39 175.84 303.46 16.78 An RRTD open condition is detected when actual RRTD resistance is greater than 1000 ohms and RRTD open is dis- played as “250°C” in the T60. GE Multilin T60 Transformer Protection System 5-287...
  • Page 426 RTDs are detected and corrective action may be taken. • RRTD 1 BLOCK: This setting is used to block remote RTD operation. 5-288 T60 Transformer Protection System GE Multilin...
  • Page 427: Dcma Outputs

    . The follow- MIN VAL MAX VAL RANGE ing equation is applied: < if x  MIN VAL  if x >  MAX VAL (EQ 5.54)  otherwise  – MIN VAL GE Multilin T60 Transformer Protection System 5-289...
  • Page 428 20% overload compared to the nominal. The nominal three-phase power is: × × × 13.8 kV 0.8 kA 17.21 MW (EQ 5.56) The three-phase power with 20% overload margin is: × 1.2 17.21 MW 20.65 MW (EQ 5.57) 5-290 T60 Transformer Protection System GE Multilin...
  • Page 429 400 kV 400 kV × ------------------ - × ------------------ - 161.66 kV, 254.03 kV (EQ 5.63) The base unit for voltage (refer to the FlexElements section in this chapter for additional details) is: GE Multilin T60 Transformer Protection System 5-291...
  • Page 430 254.03 kV 1.27 kV – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. 5-292 T60 Transformer Protection System GE Multilin...
  • Page 431: Testing

    The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED indicator, and by the critical fail relay, as shown in the following table. GE Multilin T60 Transformer Protection System...
  • Page 432: Force Contact Inputs

    Mode LED will be on, indicating that the relay is in test mode. The state of each contact input may be programmed as “Dis- abled”, “Open”, or “Closed”. All contact input operations return to normal when all settings for this feature are disabled. 5-294 T60 Transformer Protection System GE Multilin...
  • Page 433: Force Contact Outputs

    PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu:   SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin T60 Transformer Protection System 5-295...
  • Page 434: Phasor Measurement Unit Test Values

    The relay must be in test mode to use the PMU test mode. That is, the  setting must be TESTING TEST MODE FUNCTION “Enabled” and the  initiating signal must be “On”. TESTING TEST MODE INITIATE 5-296 T60 Transformer Protection System GE Multilin...
  • Page 435 When required, it is recommended to use the user-pro- grammable digital channels to signal the C37.118 client that test values are being sent in place of the real measurements. GE Multilin T60 Transformer Protection System...
  • Page 436 5.10 TESTING 5 SETTINGS 5-298 T60 Transformer Protection System GE Multilin...
  • Page 437: Actual Values

     TELEPROT CH TESTS See page 6-10.   ETHERNET SWITCH See page 6-10.   ACTUAL VALUES  TRANSFORMER See page 6-14.  METERING   SOURCE SRC 1 See page 6-15.  GE Multilin T60 Transformer Protection System...
  • Page 438  FAULT REPORTS  EVENT RECORDS See page 6-25.   OSCILLOGRAPHY See page 6-25.   DATA LOGGER See page 6-26.   PMU See page 6-27.  RECORDS  MAINTENANCE See page 6-27.  T60 Transformer Protection System GE Multilin...
  • Page 439 6 ACTUAL VALUES 6.1 OVERVIEW  ACTUAL VALUES  MODEL INFORMATION See page 6-28.  PRODUCT INFO   FIRMWARE REVISIONS See page 6-28.  GE Multilin T60 Transformer Protection System...
  • Page 440: Virtual Inputs

    The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. T60 Transformer Protection System GE Multilin...
  • Page 441: Teleprotection Inputs

    For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn. For form-C contact outputs, the state is displayed as Off or On. NOTE GE Multilin T60 Transformer Protection System...
  • Page 442: Virtual Outputs

    DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incremented whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented. T60 Transformer Protection System GE Multilin...
  • Page 443: Digital Counters

    STATUS ETHERNET Range: Fail, OK  ETHERNET ETHERNET PRI LINK  STATUS: OK Range: Fail, OK ETHERNET SEC LINK MESSAGE STATUS: OK These values indicate the status of the primary and secondary Ethernet links. GE Multilin T60 Transformer Protection System...
  • Page 444: Direct Inputs

     STATUS STATUS: Offline Range: Offline, Online DIRECT DEVICE 2 MESSAGE STATUS: Offline ↓ Range: Offline, Online DIRECT DEVICE 16 MESSAGE STATUS: Offline These actual values represent the state of direct devices 1 through 16. T60 Transformer Protection System GE Multilin...
  • Page 445: Iec 61850 Goose Integers

     SIGNATURE: SLOW EXCHANGE 1 MESSAGE DATA LENGTH: These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size for the slow EGD exchanges are displayed. GE Multilin T60 Transformer Protection System...
  • Page 446: Teleprotection Channel Tests

    Ethernet switch. If the value is “OK”, then data is being received from the remote terminal; If the value is “FAIL”, then data is not being received from the remote terminal or the port is not connected. • SWITCH MAC ADDRESS: This value displays the MAC address assigned to the Ethernet switch module. 6-10 T60 Transformer Protection System GE Multilin...
  • Page 447: Metering Conventions

    PF = Lag WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS GE Multilin T60 Transformer Protection System 6-11...
  • Page 448 ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. 6-12 T60 Transformer Protection System GE Multilin...
  • Page 449 SYSTEM SETUP POWER SYSTEM FREQUENCY AND PHASE REFERENCE The example above is illustrated in the following figure. SYSTEM VOLTAGES SYMMETRICAL COMPONENTS WYE VTs DELTA VTs 827844A1.CDR Figure 6–3: MEASUREMENT CONVENTION FOR SYMMETRICAL COMPONENTS GE Multilin T60 Transformer Protection System 6-13...
  • Page 450: Transformer

    PATH: ACTUAL VALUES METERING TRANSFORMER THERMAL ELEMENTS  THERMAL TOP OIL °C:  ELEMENTS 70°C HOTTEST-SPOT °C: MESSAGE 130° AGING FACTOR: MESSAGE DAILY RATE LOL: MESSAGE 15 hrs XFMR LIFE LOST: MESSAGE 100000 hrs 6-14 T60 Transformer Protection System GE Multilin...
  • Page 451: Sources

    0.000 SRC 1 RMS Ib: MESSAGE 0.000 SRC 1 RMS Ic: MESSAGE 0.000 SRC 1 RMS In: MESSAGE 0.000 SRC 1 PHASOR Ia: MESSAGE 0.000 0.0° SRC 1 PHASOR Ib: MESSAGE 0.000 0.0° GE Multilin T60 Transformer Protection System 6-15...
  • Page 452 0.0° SRC 1 PHASOR Vbg: MESSAGE 0.000 0.0° SRC 1 PHASOR Vcg: MESSAGE 0.000 0.0° SRC 1 RMS Vab: MESSAGE 0.00 SRC 1 RMS Vbc: MESSAGE 0.00 SRC 1 RMS Vca: MESSAGE 0.00 6-16 T60 Transformer Protection System GE Multilin...
  • Page 453 REACTIVE PWR MESSAGE 3φ: 0.000 SRC 1 REACTIVE PWR MESSAGE φa: 0.000 SRC 1 REACTIVE PWR MESSAGE φb: 0.000 SRC 1 REACTIVE PWR MESSAGE φc: 0.000 SRC 1 APPARENT PWR MESSAGE 3φ: 0.000 GE Multilin T60 Transformer Protection System 6-17...
  • Page 454 (see   SETTINGS SYSTEM SETUP SIGNAL SOURCES Because energy values are accumulated, these values should be recorded and then reset immediately prior to changing CT or VT characteristics. 6-18 T60 Transformer Protection System GE Multilin...
  • Page 455 These parameters can be monitored to reduce supplier demand penalties or for statistical metering purposes. Demand calculations are based on the measurement type selected in the  SETTINGS PRODUCT SETUP GE Multilin T60 Transformer Protection System 6-19...
  • Page 456: Synchrocheck

    0.00 Hz The actual values menu for synchrocheck 2 is identical to that of synchrocheck 1. If a synchrocheck function setting is "Dis- abled", the corresponding actual values menu item will not be displayed. 6-20 T60 Transformer Protection System GE Multilin...
  • Page 457: Tracking Frequency

    The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the setting in the   menu. Refer to the FREQUENCY AND PHASE REFERENCE SETTINGS SYSTEM SETUP POWER SYSTEM Power System section of chapter 5 for additional details. GE Multilin T60 Transformer Protection System 6-21...
  • Page 458: Flexelements

      PATH: ACTUAL VALUES METERING IEC 61850 GOOSE ANALOGS  IEC 61850 ANALOG INPUT  GOOSE ANALOGS 0.000 ANALOG INPUT MESSAGE 0.000 ANALOG INPUT MESSAGE 0.000 ↓ ANALOG INPUT 32 MESSAGE 0.000 6-22 T60 Transformer Protection System GE Multilin...
  • Page 459: Phasor Measurement Unit

    MESSAGE COUNTER: 0 The above actual values are displayed without the corresponding time stamp as they become available per the recording rate setting. Also, the recording post-filtering setting is applied to these values. GE Multilin T60 Transformer Protection System 6-23...
  • Page 460: Volts Per Hertz

    RTD INPUT xx  -50 °C Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value. 6-24 T60 Transformer Protection System GE Multilin...
  • Page 461: Records

    This menu allows the user to view the number of triggers involved and number of oscillography traces available. The value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog- CYCLES PER RECORD raphy section of chapter 5 for additional details. GE Multilin T60 Transformer Protection System 6-25...
  • Page 462: Data Logger

    It counts up at the defined sampling rate. If the data logger channels are defined, then both values are static. Refer to the  menu for clearing data logger records. COMMANDS CLEAR RECORDS 6-26 T60 Transformer Protection System GE Multilin...
  • Page 463: Phasor Measurement Unit Records

    BKR 1 ARCING AMP  menu for clearing breaker arcing current records. The COMMANDS CLEAR RECORDS BREAKER OPERATING TIME defined as the slowest operating time of breaker poles that were initiated to open. GE Multilin T60 Transformer Protection System 6-27...
  • Page 464: Product Information

    6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION   PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE multilin order code format;  MODEL INFORMATION ORDER CODE LINE 1: example order code shown  T60-E00-HCH-F8H-H6A Range: standard GE multilin order code format...
  • Page 465: Commands And Targets

    The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin T60 Transformer Protection System...
  • Page 466: Clear Records

    24-hour clock. The complete date, as a minimum, must be entered to allow execution of this com- mand. The new time will take effect at the moment the ENTER key is clicked. T60 Transformer Protection System GE Multilin...
  • Page 467: Relay Maintenance

    PMU under test. With reference to the figure below, the PMU one-shot function (when enabled) controls three FlexLogic™ operands: GE Multilin T60 Transformer Protection System...
  • Page 468 PMU and not to the absolute UTC time. Therefore a simple IRIG-B genera- tor could be used instead. Also, the test set does not have to support GPS synchronization. Any stable signal source can T60 Transformer Protection System GE Multilin...
  • Page 469 The one-shot feature can be used for ad hoc collection of synchronized measurements in the network. Two or more PMU can be pre-scheduled to freeze their measurements at the same time. When frozen the measurements could be collected using EnerVista UR Setup or a protocol client. GE Multilin T60 Transformer Protection System...
  • Page 470: Targets Menu

    The critical fail relay on the power supply module is de-energized. • All other output relays are de-energized and are prevented from further operation. • The faceplate In Service LED indicator is turned off. T60 Transformer Protection System GE Multilin...
  • Page 471 Most of the minor self-test errors can be disabled. Refer to the settings in the User-programmable self-tests section in the Settings chapter for additional details. MODULE FAILURE___: Contact Factory (xxx) • Latched target message: Yes. • Description of problem: Module hardware failure detected. GE Multilin T60 Transformer Protection System...
  • Page 472 How often the test is performed: The battery is monitored every five seconds. The error message displays after 60 sec- onds if the problem persists • What to do: Return the power supply module to GE Digital Energy for battery replacement. MAINTENANCE ALERT: Direct I/O Ring Break •...
  • Page 473 What to do: Verify the state of the output contact and contact the factory if the problem persists. MAINTENANCE ALERT: GGIO Ind xxx oscill • Latched target message: No. • Description of problem: A data item in a configurable GOOSE data set is oscillating. GE Multilin T60 Transformer Protection System...
  • Page 474 Description of problem: Abnormal restart from modules being removed or inserted while the T60 is powered-up, when there is an abnormal DC supply, or as a result of internal relay failure. • How often the test is performed: Event driven. • What to do: Contact the factory. 7-10 T60 Transformer Protection System GE Multilin...
  • Page 475: Security

    • ACCESS REM CMND ON: Asserted when remote command access is enabled. The appropriate events are also logged in the Event Recorder as well. The FlexLogic™ operands and events are updated every five seconds. GE Multilin T60 Transformer Protection System...
  • Page 476: Password Security Menu

    ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both com- mands and settings. NOTE If a remote connection is established, local passcodes are not visible. NOTE T60 Transformer Protection System GE Multilin...
  • Page 477: Remote Passwords

    If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password value. If you establish a local connection to the relay (serial), you cannot view remote passcodes. NOTE GE Multilin T60 Transformer Protection System...
  • Page 478: Access Supervision

    Range: selected FlexLogic™ operands (see below)  DUAL PERMISSION LOCAL SETTING AUTH:  SECURITY ACCESS Range: FlexLogic™ operand REMOTE SETTING AUTH: MESSAGE Range: 5 to 480 minutes in steps of 1 ACCESS AUTH MESSAGE TIMEOUT: 30 min. T60 Transformer Protection System GE Multilin...
  • Page 479 If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. GE Multilin T60 Transformer Protection System...
  • Page 480: Settings Security

    Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable. T60 Transformer Protection System GE Multilin...
  • Page 481 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin T60 Transformer Protection System...
  • Page 482 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 8–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND T60 Transformer Protection System GE Multilin...
  • Page 483 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin T60 Transformer Protection System...
  • Page 484: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. 8-10 T60 Transformer Protection System GE Multilin...
  • Page 485 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin T60 Transformer Protection System 8-11...
  • Page 486: Settings File Traceability

    UR-series device to determine if security SENT BACK TO ENERVISTA AND has been compromised. ADDED TO SETTINGS FILE. 842864A1.CDR Figure 8–11: SETTINGS FILE TRACEABILITY MECHANISM With respect to the above diagram, the traceability feature is used as follows. 8-12 T60 Transformer Protection System GE Multilin...
  • Page 487 Figure 8–12: DEVICE DEFINITION SHOWING TRACEABILITY DATA This information is also available in printed settings file reports as shown in the example below. Traceability data in settings report 842862A1.CDR Figure 8–13: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA GE Multilin T60 Transformer Protection System 8-13...
  • Page 488 If the user converts an existing settings file to another revision, then any existing traceability information is removed from the settings file. • If the user duplicates an existing settings file, then any traceability information is transferred to the duplicate settings file. 8-14 T60 Transformer Protection System GE Multilin...
  • Page 489: Enervista Security Management System

    Select the Security > User Management menu item to open the user management configuration window. Enter a username in the User field. The username must be between 4 and 20 characters in length. GE Multilin T60 Transformer Protection System 8-15...
  • Page 490: Modifying User Privileges

    The EnerVista security management system must be enabled. The following procedure describes how to modify user privileges. Select the Security > User Management menu item to open the user management configuration window. Locate the username in the User field. 8-16 T60 Transformer Protection System GE Multilin...
  • Page 491 When this box is checked, the user will become an EnerVista URPlus Setup administrator, therefore receiving all of the administrative rights. Exercise caution when granting administrator rights. Click OK to save the changes to user to the security management system. GE Multilin T60 Transformer Protection System 8-17...
  • Page 492 8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8-18 T60 Transformer Protection System GE Multilin...
  • Page 493 CT is the 1 A or 5 A tap, and M[1] is the calculated magnitude compensation factor (see the Transformer section in Chapter 5 for details on calculating the M[1] and M[2] factors). GE Multilin T60 Transformer Protection System...
  • Page 494 2 current as restraint and repeat the steps above by substituting the Breakpoint 2 value in the equations above with the new per-unit restraint current value. The above two tests can be repeated for Phases B and C. (pu) (pu) Figure 9–1: DIFFERENTIAL RESTRAINT CHARACTERISTIC T60 Transformer Protection System GE Multilin...
  • Page 495: Differential Characteristic Test Examples

    This allows the tester to define and confirm various points on the operating characteristic. The spreadsheet can be found at GE Multilin website (look for the T35/T60 Percent Differential Element Simulator in the support documents for the product).
  • Page 496: Test Example 1

    Not within zone Grounding Within zone Slope 2 Angle WRT 0° Angle WRT 0° Resistance 3Ph 10.000 ohms Resistance 3Ph 10.000 ohms APPLICATION OF EXCESSIVE CURRENT (> 3 × In) FOR EXTENDED PERIODS DAMAGES THE RELAY! T60 Transformer Protection System GE Multilin...
  • Page 497 Verify that the Percent Differential element operates and the following are displayed in the actual values menu: PHASE DIFFERENTIAL CURRENT (I PHASE RESTRAINT CURRENT (I 0 ∠0° 0 ∠0° 0.136 ∠0° 0.367 pu ∠–180° 0.136 ∠0° 0.367 pu ∠0° GE Multilin T60 Transformer Protection System...
  • Page 498 DIFFERENTIAL CURRENT (I PHASE RESTRAINT CURRENT (I 0 ∠0° 0 ∠0° 0.170 pu ∠0° 1 pu ∠–180° 0.170 pu ∠0° 1 pu ∠0° ⁄ The actual ratio is now 17%. Verify that the element operates correctly. T60 Transformer Protection System GE Multilin...
  • Page 499 3.5 pu Due to the mathematical complexity involved in shaping the curve between Breakpoint 1 and Breakpoint 2, an Excel-based simulation tool is available from the GE Multilin website at (look in the support documents for the NOTE ⁄...
  • Page 500 I until the relay operates. Use the Excel tool to compare the actual and expected operating values. A blank result table is provided at the end of this chapter for convenience. T60 Transformer Protection System GE Multilin...
  • Page 501: Test Example 2

    0 ∠0° 7.915 ∠0° 8.646 ∠0° Slope 2 0.2 ∠0° 15 ∠–180° 7.918 ∠–180° 8.650 ∠–180° Operate = 95.7% 0 ∠0° 0 ∠0° 0 ∠0° 0 ∠0° 0.2 ∠–180° 0 ∠0° 7.916 ∠0° 8.650 ∠0° GE Multilin T60 Transformer Protection System...
  • Page 502: Test Example 3

    4 ∠0° 0 ∠0° 0 ∠0° 0 ∠0° Slope 2 Operate = 95.7% 8 ∠–180° 0.6 ∠0° 12.13 ∠–180° 12.73 ∠0° > Slope 2 = 95% 4 ∠0° 0.6 ∠–180° 12.13 ∠0° 12.73 ∠–180° 9-10 T60 Transformer Protection System GE Multilin...
  • Page 503: Test Example 4

    Slope 2 0 ∠0° 0 ∠0° 0 ∠0° 0 ∠0° Operate = 96% 0.18 ∠–90° 8.33 ∠–270° 8 ∠–270° 8.33 ∠–270° > Slope 2 = 95% 0.18 ∠–270° 8.33 ∠–90° 8 ∠–90° 8.33 ∠–90° GE Multilin T60 Transformer Protection System 9-11...
  • Page 504: Inrush Inhibit Test Procedure

    Apply a second harmonic to Phase A with a level greater than the set threshold and monitor the operation of the Per- cent Differential element. The element should drop out when the injected second harmonic level becomes three times larger than the set threshold. 9-12 T60 Transformer Protection System GE Multilin...
  • Page 505: Overexcitation Inhibit Test Procedure

    9.5% 2 A ∠–180° 2 pu 4 pu Block 2 A ∠0° 4 A ∠–180° 8.5% 2 pu 4 pu Operate 2 A ∠0° 4 A ∠–180° 9.5% 2 pu 4 pu Block GE Multilin T60 Transformer Protection System 9-13...
  • Page 506: Frequency Element Tests

    The injected frequency should smoothly ramp through the set threshold, with the ramp starting frequency sufficiently out- side the threshold so the relay becomes conditioned to the trend before operation. For typical interconnected power sys- tems, the recommended testing ramp rate is 0.20 Hz/s. 9-14 T60 Transformer Protection System GE Multilin...
  • Page 507 20 ms. The tracking frequency should not be used in timing measurements, as its algorithm involves phase locking, which purposely sets its frequency high or low to allow the T60 sample clock to catch-up or wait as necessary to reach synchro- nism with the power system. GE Multilin T60 Transformer Protection System 9-15...
  • Page 508: Commissioning Test Tables

    Slope 2 Status: ____________ = _____________ 9.6.2 INRUSH INHIBIT TESTS Table 9–4: INRUSH INHIBIT TEST TABLE PHASE INJECTED DISPLAYED STATUS (BLOCK/ W1 2ND W2 2ND (PU) (PU) OPERATE) CURRENT HARMONIC CURRENT HARMONIC HARMONIC 9-16 T60 Transformer Protection System GE Multilin...
  • Page 509: Overexcitation Inhibit Tests

    9 COMMISSIONING 9.6 COMMISSIONING TEST TABLES 9.6.3 OVEREXCITATION INHIBIT TESTS Table 9–5: OVEREXCITATION INHIBIT TEST RESULTS PHASE INJECTED DISPLAYED STATUS W1 5TH W2 5TH (PU) (PU) (BLOCK/ CURRENT HARMONIC CURRENT HARMONIC HARMONIC OPERATE) GE Multilin T60 Transformer Protection System 9-17...
  • Page 510 9.6 COMMISSIONING TEST TABLES 9 COMMISSIONING 9-18 T60 Transformer Protection System GE Multilin...
  • Page 511: Maintenance

    Other files can be in standard formats, such as COMTRADE or .csv. You cannot erase directly the flash memory, but all records and settings in that memory can be deleted. Do this using the   command. SETTINGS PRODUCT SETUP CLEAR RELAY RECORDS GE Multilin T60 Transformer Protection System 10-1...
  • Page 512: Repairs

    Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty. • Fax a copy of the shipping information to the GE Digital Energy service department in Canada at +1 905 927 5098. Use the detailed return procedure outlined at https://www.gedigitalenergy.com/multilin/support/ret_proc.htm...
  • Page 513: Storage

    Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range outlined in the Specifications. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. GE Multilin T60 Transformer Protection System 10-3...
  • Page 514: Disposal

    European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove the modules as outlined earlier, dismantle the unit, and recycle the metal when possible. 10-4 T60 Transformer Protection System GE Multilin...
  • Page 515: Parameter Lists

    SRC 2 In RMS Amps Source 2 neutral current RMS 6216 SRC 2 Ia Mag Amps Source 2 phase A current magnitude 6218 SRC 2 Ia Angle Degrees Source 2 phase A current angle GE Multilin T60 Transformer Protection System...
  • Page 516 SRC 4 Ia Mag Amps Source 4 phase A current magnitude 6346 SRC 4 Ia Angle Degrees Source 4 phase A current angle 6347 SRC 4 Ib Mag Amps Source 4 phase B current magnitude T60 Transformer Protection System GE Multilin...
  • Page 517 SRC 6 Ia Angle Degrees Source 6 phase A current angle 6475 SRC 6 Ib Mag Amps Source 6 phase B current magnitude 6477 SRC 6 Ib Angle Degrees Source 6 phase B current angle GE Multilin T60 Transformer Protection System...
  • Page 518 SRC 2 Vcg RMS Volts Source 2 phase CG voltage RMS 6726 SRC 2 Vag Mag Volts Source 2 phase AG voltage magnitude 6728 SRC 2 Vag Angle Degrees Source 2 phase AG voltage angle T60 Transformer Protection System GE Multilin...
  • Page 519 Source 3 zero-sequence voltage magnitude 6821 SRC 3 V_0 Angle Degrees Source 3 zero-sequence voltage angle 6822 SRC 3 V_1 Mag Volts Source 3 positive-sequence voltage magnitude 6824 SRC 3 V_1 Angle Degrees Source 3 positive-sequence voltage angle GE Multilin T60 Transformer Protection System...
  • Page 520 SRC 5 Vbc Angle Degrees Source 5 phase BC voltage angle 6939 SRC 5 Vca Mag Volts Source 5 phase CA voltage magnitude 6941 SRC 5 Vca Angle Degrees Source 5 phase CA voltage angle T60 Transformer Protection System GE Multilin...
  • Page 521 Source 1 phase C reactive power 7184 SRC 1 S Source 1 three-phase apparent power 7186 SRC 1 Sa Source 1 phase A apparent power 7188 SRC 1 Sb Source 1 phase B apparent power GE Multilin T60 Transformer Protection System...
  • Page 522 Source 4 phase B reactive power 7278 SRC 4 Qc Vars Source 4 phase C reactive power 7280 SRC 4 S Source 4 three-phase apparent power 7282 SRC 4 Sa Source 4 phase A apparent power T60 Transformer Protection System GE Multilin...
  • Page 523 SRC 1 Demand Ia Amps Source 1 phase A current demand 7682 SRC 1 Demand Ib Amps Source 1 phase B current demand 7684 SRC 1 Demand Ic Amps Source 1 phase C current demand GE Multilin T60 Transformer Protection System...
  • Page 524 Xfmr Ibr Mag Transformer restraint phase B current magnitude 8972 Xfmr Ibr Angle Degrees Transformer restraint phase B current angle 8973 Xfmr Harm2 Ibd Mag Transformer differential phase B second harmonic current magnitude A-10 T60 Transformer Protection System GE Multilin...
  • Page 525 Phasor measurement unit 1 positive-sequence current magnitude 9571 PMU 1 I1 Angle Degrees Phasor measurement unit 1 positive-sequence current angle 9572 PMU 1 I2 Mag Amps Phasor measurement unit 1 negative-sequence current magnitude GE Multilin T60 Transformer Protection System A-11...
  • Page 526 SRC 1 Ib Harm[12] Source 1 phase B current fourteenth harmonic 10287 SRC 1 Ib Harm[13] Source 1 phase B current fifteenth harmonic 10288 SRC 1 Ib Harm[14] Source 1 phase B current sixteenth harmonic A-12 T60 Transformer Protection System GE Multilin...
  • Page 527 SRC 2 Ia Harm[9] Source 2 phase A current eleventh harmonic 10350 SRC 2 Ia Harm[10] Source 2 phase A current twelfth harmonic 10351 SRC 2 Ia Harm[11] Source 2 phase A current thirteenth harmonic GE Multilin T60 Transformer Protection System A-13...
  • Page 528 SRC 2 Ic Harm[6] Source 2 phase C current eighth harmonic 10413 SRC 2 Ic Harm[7] Source 2 phase C current ninth harmonic 10414 SRC 2 Ic Harm[8] Source 2 phase C current tenth harmonic A-14 T60 Transformer Protection System GE Multilin...
  • Page 529 SRC 3 Ib Harm[3] Source 3 phase B current fifth harmonic 10476 SRC 3 Ib Harm[4] Source 3 phase B current sixth harmonic 10477 SRC 3 Ib Harm[5] Source 3 phase B current seventh harmonic GE Multilin T60 Transformer Protection System A-15...
  • Page 530 SRC 4 Ia Harm[0] Source 4 phase A current second harmonic 10539 SRC 4 Ia Harm[1] Source 4 phase A current third harmonic 10540 SRC 4 Ia Harm[2] Source 4 phase A current fourth harmonic A-16 T60 Transformer Protection System GE Multilin...
  • Page 531 SRC 4 Ib Harm[22] Source 4 phase B current twenty-fourth harmonic 10594 SRC 4 Ib Harm[23] Source 4 phase B current twenty-fifth harmonic 10603 SRC 4 Ic THD Source 4 phase C current total harmonic distortion GE Multilin T60 Transformer Protection System A-17...
  • Page 532 SRC 5 Ia Harm[19] Source 5 phase A current twenty-first harmonic 10649 SRC 5 Ia Harm[20] Source 5 phase A current twenty-second harmonic 10650 SRC 5 Ia Harm[21] Source 5 phase A current twenty-third harmonic A-18 T60 Transformer Protection System GE Multilin...
  • Page 533 SRC 5 Ic Harm[16] Source 5 phase C current eighteenth harmonic 10696 SRC 5 Ic Harm[17] Source 5 phase C current nineteenth harmonic 10697 SRC 5 Ic Harm[18] Source 5 phase C current twentieth harmonic GE Multilin T60 Transformer Protection System A-19...
  • Page 534 SRC 6 Ib Harm[13] Source 6 phase B current fifteenth harmonic 10743 SRC 6 Ib Harm[14] Source 6 phase B current sixteenth harmonic 10744 SRC 6 Ib Harm[15] Source 6 phase B current seventeenth harmonic A-20 T60 Transformer Protection System GE Multilin...
  • Page 535 DCmA input 10 actual value 13524 DCmA Inputs 11 Value DCmA input 11 actual value 13526 DCmA Inputs 12 Value DCmA input 12 actual value 13528 DCmA Inputs 13 Value DCmA input 13 actual value GE Multilin T60 Transformer Protection System A-21...
  • Page 536 RTD input 33 actual value 13585 RTD Inputs 34 Value RTD input 34 actual value 13586 RTD Inputs 35 Value RTD input 35 actual value 13587 RTD Inputs 36 Value RTD input 36 actual value A-22 T60 Transformer Protection System GE Multilin...
  • Page 537 45584 GOOSE Analog In 1 IEC 61850 GOOSE analog input 1 45586 GOOSE Analog In 2 IEC 61850 GOOSE analog input 2 45588 GOOSE Analog In 3 IEC 61850 GOOSE analog input 3 GE Multilin T60 Transformer Protection System A-23...
  • Page 538: Flexinteger Items

    IEC61850 GOOSE UInteger input 13 9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 A-24 T60 Transformer Protection System GE Multilin...
  • Page 539: Modbus Communications

    See the Supported Function Codes section for complete details. An exception response from the slave is indi- cated by setting the high order bit of the function code in the response packet. See the Exception Responses section for further details. GE Multilin T60 Transformer Protection System...
  • Page 540: Modbus Rtu Crc-16 Algorithm

    This algorithm requires the characteristic polynomial to be reverse bit ordered. The most significant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder. A C programming language implementation of the CRC algorithm will be provided upon request. T60 Transformer Protection System GE Multilin...
  • Page 541 No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC GE Multilin T60 Transformer Protection System...
  • Page 542: Modbus Function Codes

    1 to 127 though only a small subset is generally needed. The relay supports some of these functions, as summarized in the following table. Subsequent sections describe each function code in detail. FUNCTION CODE MODBUS DEFINITION GE MULTILIN DEFINITION Read holding registers Read actual values or settings Read holding registers...
  • Page 543: Execute Operation (Function Code 05H

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high GE Multilin T60 Transformer Protection System...
  • Page 544: Store Multiple Settings (Function Code 10H

    PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte T60 Transformer Protection System GE Multilin...
  • Page 545: B.3.1 Obtaining Relay Files Via Modbus

    Cleared Date to the present date and time. To read binary COMTRADE oscillography files, read the following filenames: OSCnnnn.CFG and OSCnnn.DAT Replace “nnn” with the desired oscillography trigger number. For ASCII format, use the following file names OSCAnnnn.CFG and OSCAnnn.DAT GE Multilin T60 Transformer Protection System...
  • Page 546: File Transfers

    EVTnnn.TXT (replace nnn with the desired starting record number) To read from a specific record to another specific record, use the following filename: EVT.TXT xxxxx yyyyy (replace xxxxx with the starting record number and yyyyy with the ending record number) T60 Transformer Protection System GE Multilin...
  • Page 547: Memory Mapping

    0 (Off) 0412 Virtual Input 19 State 0 to 1 F108 0 (Off) 0413 Virtual Input 20 State 0 to 1 F108 0 (Off) 0414 Virtual Input 21 State 0 to 1 F108 0 (Off) GE Multilin T60 Transformer Protection System...
  • Page 548 Digital Counter 1 Frozen Time Stamp us (microsecond 0 to 4294967295 F003 part of time stamp) 0808 ...Repeated for Digital Counter 2 0810 ...Repeated for Digital Counter 3 0818 ...Repeated for Digital Counter 4 0820 ...Repeated for Digital Counter 5 B-10 T60 Transformer Protection System GE Multilin...
  • Page 549 0 to 65535 F500 1603 Field Shared Input States 0 to 65535 F500 1604 Field Shared Input Channel States 0 to 65535 F500 1605 Field Shared Input Test States 0 to 65535 F500 GE Multilin T60 Transformer Protection System B-11...
  • Page 550 Source 1 Phase B Current Angle -359.9 to 0 degrees F002 180E Source 1 Phase C Current Magnitude 0 to 999999.999 0.001 F060 1810 Source 1 Phase C Current Angle -359.9 to 0 degrees F002 B-12 T60 Transformer Protection System GE Multilin...
  • Page 551 -359.9 to 0 degrees F002 1A2C Reserved (20 items) F001 1A40 ...Repeated for Source 2 1A80 ...Repeated for Source 3 1AC0 ...Repeated for Source 4 1B00 ...Repeated for Source 5 1B40 ...Repeated for Source 6 GE Multilin T60 Transformer Protection System B-13...
  • Page 552 Frequency for Source 6 2 to 90 0.001 F003 Source Demand (Read Only) (6 modules) 1E00 Source 1 Demand Ia 0 to 999999.999 0.001 F060 1E02 Source 1 Demand Ib 0 to 999999.999 0.001 F060 B-14 T60 Transformer Protection System GE Multilin...
  • Page 553 Breaker 1 Arcing Current Amp Phase C 0 to 99999999 -cyc F060 21E6 Breaker 1 Operating Time Phase A 0 to 65535 F001 21E7 Breaker 1 Operating Time Phase B 0 to 65535 F001 GE Multilin T60 Transformer Protection System B-15...
  • Page 554 ...Repeated for Synchrocheck 2 Filed Unit Raw Data Settings (Read/Write Setting) 2460 Field Raw Data Port 0 to 7 F244 6 (H1a) 2461 Filed Raw Data Freeze 0 to 1 F102 0 (Disabled) B-16 T60 Transformer Protection System GE Multilin...
  • Page 555 IEC 61850 GGIO5 uinteger Input 4 Operand F612 26B4 IEC 61850 GGIO5 uinteger Input 5 Operand F612 26B5 IEC 61850 GGIO5 uinteger Input 6 Operand F612 26B6 IEC 61850 GGIO5 uinteger Input 7 Operand F612 GE Multilin T60 Transformer Protection System B-17...
  • Page 556 Oscillography Number of Triggers 0 to 65535 F001 3001 Oscillography Available Records 0 to 65535 F001 3002 Oscillography Last Cleared Date 0 to 400000000 F050 3004 Oscillography Number of Cycles Per Record 0 to 65535 F001 B-18 T60 Transformer Protection System GE Multilin...
  • Page 557 -9999.999 to 9999.999 0.001 F004 34E8 DCmA Inputs 21 Value -9999.999 to 9999.999 0.001 F004 34EA DCmA Inputs 22 Value -9999.999 to 9999.999 0.001 F004 34EC DCmA Inputs 23 Value -9999.999 to 9999.999 0.001 F004 GE Multilin T60 Transformer Protection System B-19...
  • Page 558 RTD Input 48 Value -32768 to 32767 °C F002 Ohm Input Values (Read Only) (2 modules) 3520 Ohm Inputs 1 Value 0 to 65535 F001 3521 Ohm Inputs 2 Value 0 to 65535 F001 B-20 T60 Transformer Protection System GE Multilin...
  • Page 559 Field Contact Input 1 Failsafe Value 0 to 1 F108 0 (Off) 3909 Field Contact Input 1 Debounce Time 0 to 16 F001 390A Field Contact Input 1 Events 0 to 1 F102 1 (Enabled) GE Multilin T60 Transformer Protection System B-21...
  • Page 560 ...Repeated for Field Shared Input 7 3B3F ...Repeated for Field Shared Input 8 3B48 ...Repeated for Field Shared Input 9 3B51 ...Repeated for Field Shared Input 10 3B5A ...Repeated for Field Shared Input 11 B-22 T60 Transformer Protection System GE Multilin...
  • Page 561 ...Repeated for Field Shared Output 12 3E50 ...Repeated for Field Shared Output 13 3E5C ...Repeated for Field Shared Output 14 3E68 ...Repeated for Field Shared Output 15 3E74 ...Repeated for Field Shared Output 16 GE Multilin T60 Transformer Protection System B-23...
  • Page 562 Invalid Password Attempts (before lockout) 2 to 5 F001 4015 Password Lockout Duration 5 to 60 minutes F001 4016 Password Access Events 0 to 1 F102 0 (Disabled) 4017 Local Setting Authorization 1 to 65535 F300 B-24 T60 Transformer Protection System GE Multilin...
  • Page 563 2 (1) 40B2 DNP Power Scale Factor 0 to 8 F194 2 (1) 40B3 DNP Other Scale Factor 0 to 8 F194 2 (1) 40B4 DNP Current Default Deadband 0 to 100000000 F003 30000 GE Multilin T60 Transformer Protection System B-25...
  • Page 564 4158 Ethernet Switch Port 5 Status 0 to 2 F134 0 (Fail) 4159 Ethernet Switch Port 6 Status 0 to 2 F134 0 (Fail) 415A Switch Firmware Version 0.00 to 99.99 0.01 F001 B-26 T60 Transformer Protection System GE Multilin...
  • Page 565 ...Repeated for User-Programmable LED 8 4290 ...Repeated for User-Programmable LED 9 4292 ...Repeated for User-Programmable LED 10 4294 ...Repeated for User-Programmable LED 11 4296 ...Repeated for User-Programmable LED 12 4298 ...Repeated for User-Programmable LED 13 GE Multilin T60 Transformer Protection System B-27...
  • Page 566 4481 Phase CT 1 Secondary 0 to 1 F123 0 (1 A) 4482 Ground CT 1 Primary 1 to 65000 F001 4483 Ground CT 1 Secondary 0 to 1 F123 0 (1 A) B-28 T60 Transformer Protection System GE Multilin...
  • Page 567 Transformer Winding 1 Angle w.r.t. Winding 1 -359.9 to 0 degrees F002 4651 Transformer Winding 1 Resistance 0.0001 to 100 ohms 0.0001 F003 100000 4653 ...Repeated for Transformer Winding 2 4666 ...Repeated for Transformer Winding 3 GE Multilin T60 Transformer Protection System B-29...
  • Page 568 0 to 2 F139 0 (Thermal Exponentia 47D1 Demand Power Method 0 to 2 F139 0 (Thermal Exponentia 47D2 Demand Interval 0 to 5 F132 2 (15 MIN) 47D3 Demand Input 0 to 65535 F300 B-30 T60 Transformer Protection System GE Multilin...
  • Page 569 Raw Field Data Brick Transceiver Temperature 0 to 1 degree F002 4E21 Raw Field Data Brick Transceiver Voltage 0 to 0.01 0.01 F001 4E22 Raw Field Data Brick Transceiver Current 0 to 1 F001 GE Multilin T60 Transformer Protection System B-31...
  • Page 570 ...Repeated for RTD Input 29 5627 ...Repeated for RTD Input 30 563A ...Repeated for RTD Input 31 564D ...Repeated for RTD Input 32 5660 ...Repeated for RTD Input 33 5673 ...Repeated for RTD Input 34 B-32 T60 Transformer Protection System GE Multilin...
  • Page 571 Phase Time Overcurrent 1 Function 0 to 1 F102 0 (Disabled) 5901 Phase Time Overcurrent 1 Signal Source 0 to 5 F167 0 (SRC 1) 5902 Phase Time Overcurrent 1 Input 0 to 1 F122 0 (Phasor) GE Multilin T60 Transformer Protection System B-33...
  • Page 572 ...Repeated for Neutral Time Overcurrent 2 5B20 ...Repeated for Neutral Time Overcurrent 3 5B30 ...Repeated for Neutral Time Overcurrent 4 5B40 ...Repeated for Neutral Time Overcurrent 5 5B50 ...Repeated for Neutral Time Overcurrent 6 B-34 T60 Transformer Protection System GE Multilin...
  • Page 573 ...Repeated for Ground Instantaneous Overcurrent 3 5E30 ...Repeated for Ground Instantaneous Overcurrent 4 5E40 ...Repeated for Ground Instantaneous Overcurrent 5 5E50 ...Repeated for Ground Instantaneous Overcurrent 6 5E60 ...Repeated for Ground Instantaneous Overcurrent 7 GE Multilin T60 Transformer Protection System B-35...
  • Page 574 -60 to 60 °C F002 6178 June Average Ambient Temperature -60 to 60 °C F002 6179 July Average Ambient Temperature -60 to 60 °C F002 617A August Average Ambient Temperature -60 to 60 °C F002 B-36 T60 Transformer Protection System GE Multilin...
  • Page 575 Power Swing Detect Inner Limit Angle 40 to 140 degrees F001 65CB Power Swing Detect Delay 1 Pickup 0 to 65.535 0.001 F001 65CC Power Swing Detect Delay 1 Reset 0 to 65.535 0.001 F001 GE Multilin T60 Transformer Protection System B-37...
  • Page 576 0.01 F001 7045 Phase Overvoltage 1 Block 0 to 65535 F300 7046 Phase Overvoltage 1 Target 0 to 2 F109 0 (Self-reset) 7047 Phase Overvoltage 1 Events 0 to 1 F102 0 (Disabled) B-38 T60 Transformer Protection System GE Multilin...
  • Page 577 0.02 to 500 ohms 0.01 F001 1000 7142 Ground Distance Zone 1 Quad Left Blinder RCA 60 to 90 degrees F001 7143 Ground Distance Zone 1 Z0M Z1 Magnitude 0 to 7 0.01 F001 GE Multilin T60 Transformer Protection System B-39...
  • Page 578 DCmA Inputs (Read/Write Setting) (24 modules) 7300 DCmA Inputs 1 Function 0 to 1 F102 0 (Disabled) 7301 DCmA Inputs 1 ID F205 “DCmA Ip 1" 7307 Reserved 1 (4 items) 0 to 65535 F001 B-40 T60 Transformer Protection System GE Multilin...
  • Page 579 ...Repeated for Disconnect Switch 4 7594 ...Repeated for Disconnect Switch 5 75A9 ...Repeated for Disconnect Switch 6 75BE ...Repeated for Disconnect Switch 7 75D3 ...Repeated for Disconnect Switch 8 75E8 ...Repeated for Disconnect Switch 9 GE Multilin T60 Transformer Protection System B-41...
  • Page 580 PMU 1 Voltage Trigger Block (3 items) 0 to 65535 F300 7894 PMU 1 Voltage Trigger Target 0 to 2 F109 0 (Self-reset) 7895 PMU 1 Voltage Trigger Events 0 to 1 F102 0 (Disabled) B-42 T60 Transformer Protection System GE Multilin...
  • Page 581 PMU 1 Ia Calibration Angle -5 to 5 ° 0.05 F002 797E PMU 1 Ib Calibration Angle -5 to 5 ° 0.05 F002 797F PMU 1 Ic Calibration Angle -5 to 5 ° 0.05 F002 GE Multilin T60 Transformer Protection System B-43...
  • Page 582 ...Repeated for User Programmable Pushbutton 12 7D64 ...Repeated for User Programmable Pushbutton 13 7D8F ...Repeated for User Programmable Pushbutton 14 7DBA ...Repeated for User Programmable Pushbutton 15 7DE5 ...Repeated for User Programmable Pushbutton 16 B-44 T60 Transformer Protection System GE Multilin...
  • Page 583 0 (Self-reset) 7F68 Auxiliary Undervoltage 1 Events 0 to 1 F102 0 (Disabled) 7F69 Reserved (7 items) 0 to 65535 F001 7F70 ...Repeated for Auxiliary Undervoltage 2 7F80 ...Repeated for Auxiliary Undervoltage 3 GE Multilin T60 Transformer Protection System B-45...
  • Page 584 Breaker Failure 1 Breaker Status 1 Phase A/3P 0 to 65535 F300 8610 Breaker Failure 1 Breaker Status 2 Phase A/3P 0 to 65535 F300 8611 Breaker Failure 1 Breaker Test On 0 to 65535 F300 B-46 T60 Transformer Protection System GE Multilin...
  • Page 585 0 to 200 °C F002 87C4 Remote RTD 5 Value 0 to 200 °C F002 87C5 Remote RTD 6 Value 0 to 200 °C F002 87C6 Remote RTD 7 Value 0 to 200 °C F002 GE Multilin T60 Transformer Protection System B-47...
  • Page 586 ...Repeated for Digital Element 32 8C80 ...Repeated for Digital Element 33 8C94 ...Repeated for Digital Element 34 8CA8 ...Repeated for Digital Element 35 8CBC ...Repeated for Digital Element 36 8CD0 ...Repeated for Digital Element 37 B-48 T60 Transformer Protection System GE Multilin...
  • Page 587 0.1 to 50 F001 900A FlexElement™ 1 Pickup -90 to 90 0.001 F004 1000 900C FlexElement™ 1 DeltaT Units 0 to 2 F518 0 (Milliseconds) 900D FlexElement™ 1 DeltaT 20 to 86400 F003 GE Multilin T60 Transformer Protection System B-49...
  • Page 588 “Dir Ip 1” 9406 Direct Output 1 Name 1 to 96 F205 “Dir Out 1” 940C ...Repeated for Direct Input/Output 2 9418 ...Repeated for Direct Input/Output 3 9424 ...Repeated for Direct Input/Output 4 B-50 T60 Transformer Protection System GE Multilin...
  • Page 589 FlexElement™ 4 Actual -2147483.647 to 2147483.647 0.001 F004 9A09 FlexElement™ 5 Actual 0.001 F004 -2147483.647 to 2147483.647 9A0B FlexElement™ 6 Actual 0.001 F004 -2147483.647 to 2147483.647 9A0D FlexElement™ 7 Actual -2147483.647 to 2147483.647 0.001 F004 GE Multilin T60 Transformer Protection System B-51...
  • Page 590 0 to 1 F102 0 (Disabled) A041 ...Repeated for VT Fuse Failure 2 A042 ...Repeated for VT Fuse Failure 3 A043 ...Repeated for VT Fuse Failure 4 A044 ...Repeated for VT Fuse Failure 5 B-52 T60 Transformer Protection System GE Multilin...
  • Page 591 ...Repeated for Volts Per Hertz 2 Volts Per Hertz Actual Values (Read Only) (2 modules) A5A0 Volts Per Hertz 1 0 to 65.535 0.001 F001 A5A1 Volts Per Hertz 2 0 to 65.535 0.001 F001 GE Multilin T60 Transformer Protection System B-53...
  • Page 592 0 (SRC 1) A962 Restricted Ground Fault 1 Pickup 0.005 to 30 0.001 F001 A963 Restricted Ground Fault 1 Slope 0 to 100 F001 A964 Restricted Ground Fault 1 Delay 0 to 600 0.01 F001 B-54 T60 Transformer Protection System GE Multilin...
  • Page 593 Command to Clear XCBR3 OpCnt (Operation Counter) 0 to 1 F126 0 (No) AB2A Operand for IEC 61850 XCBR4.ST.Loc Status 0 to 65535 F300 AB2B Command to Clear XCBR4 OpCnt (Operation Counter) 0 to 1 F126 0 (No) GE Multilin T60 Transformer Protection System B-55...
  • Page 594 AF00 Number of Analog Input Points in GGIO4 4 to 32 F001 IEC 61850 GGIO4 Analog Input Points Configuration Settings (Read/Write Setting) (32 modules) AF10 IEC 61850 GGIO4 Analog Input 1 Value F600 B-56 T60 Transformer Protection System GE Multilin...
  • Page 595 IEC 61850 LPHD Location 0 to 65534 F204 “Location” B0B5 Include Non-IEC 61850 Data 0 to 1 F102 0 (Disabled) B06B IEC 61850 Server Data Scanning Function 0 to 1 F102 0 (Disabled) GE Multilin T60 Transformer Protection System B-57...
  • Page 596 ...Repeated for Received Analog 13 B22A ...Repeated for Received Analog 14 B22C ...Repeated for Received Analog 15 B22E ...Repeated for Received Analog 16 B230 ...Repeated for Received Analog 17 B232 ...Repeated for Received Analog 18 B-58 T60 Transformer Protection System GE Multilin...
  • Page 597 ...Repeated for Module 8 BA00 ...Repeated for Module 9 BA20 ...Repeated for Module 10 BA40 ...Repeated for Module 11 BA60 ...Repeated for Module 12 BA80 ...Repeated for Module 13 BAA0 ...Repeated for Module 14 GE Multilin T60 Transformer Protection System B-59...
  • Page 598 ...Repeated for Contact Input 44 BC60 ...Repeated for Contact Input 45 BC68 ...Repeated for Contact Input 46 BC70 ...Repeated for Contact Input 47 BC78 ...Repeated for Contact Input 48 BC80 ...Repeated for Contact Input 49 B-60 T60 Transformer Protection System GE Multilin...
  • Page 599 0 (Disabled) BE31 Virtual Input 1 Name F205 “Virt Ip 1“ BE37 Virtual Input 1 Programmed Type 0 to 1 F127 0 (Latched) BE38 Virtual Input 1 Events 0 to 1 F102 0 (Disabled) GE Multilin T60 Transformer Protection System B-61...
  • Page 600 ...Repeated for Virtual Input 49 C07C ...Repeated for Virtual Input 50 C088 ...Repeated for Virtual Input 51 C094 ...Repeated for Virtual Input 52 C0A0 ...Repeated for Virtual Input 53 C0AC ...Repeated for Virtual Input 54 B-62 T60 Transformer Protection System GE Multilin...
  • Page 601 ...Repeated for Virtual Output 36 C250 ...Repeated for Virtual Output 37 C258 ...Repeated for Virtual Output 38 C260 ...Repeated for Virtual Output 39 C268 ...Repeated for Virtual Output 40 C270 ...Repeated for Virtual Output 41 GE Multilin T60 Transformer Protection System B-63...
  • Page 602 ...Repeated for Virtual Output 90 C400 ...Repeated for Virtual Output 91 C408 ...Repeated for Virtual Output 92 C410 ...Repeated for Virtual Output 93 C418 ...Repeated for Virtual Output 94 C420 ...Repeated for Virtual Output 95 B-64 T60 Transformer Protection System GE Multilin...
  • Page 603 ...Repeated for Contact Output 32 C5C0 ...Repeated for Contact Output 33 C5CC ...Repeated for Contact Output 34 C5D8 ...Repeated for Contact Output 35 C5E4 ...Repeated for Contact Output 36 C5F0 ...Repeated for Contact Output 37 GE Multilin T60 Transformer Protection System B-65...
  • Page 604 Clear Platform Direct Input/Output Statistics Operand 0 to 65535 F300 C783 Reserved (13 items) F001 Force Contact Inputs/Outputs (Read/Write Settings) C7A0 Force Contact Input x State (96 items) 0 to 2 F144 0 (Disabled) B-66 T60 Transformer Protection System GE Multilin...
  • Page 605 ...Repeated for Direct Output 2 CA14 ...Repeated for Direct Output 3 CA16 ...Repeated for Direct Output 4 CA18 ...Repeated for Direct Output 5 CA1A ...Repeated for Direct Output 6 CA1C ...Repeated for Direct Output 7 GE Multilin T60 Transformer Protection System B-67...
  • Page 606 0 to 1 F102 0 (Disabled) Alarm Events CAEC Reserved (4 items) 1 to 1000 F001 Remote Devices (Read/Write Setting) (16 modules) CB00 Remote Device 1 GSSE/GOOSE Application ID (GOID) F209 “Remote Device 1“ B-68 T60 Transformer Protection System GE Multilin...
  • Page 607 ...Repeated for Remote Input 26 D0A4 ...Repeated for Remote Input 27 D0AE ...Repeated for Remote Input 28 D0B8 ...Repeated for Remote Input 29 D0C2 ...Repeated for Remote Input 30 D0CC ...Repeated for Remote Input 31 GE Multilin T60 Transformer Protection System B-69...
  • Page 608 ...Repeated for Remote Output 10 D2C8 ...Repeated for Remote Output 11 D2CC ...Repeated for Remote Output 12 D2D0 ...Repeated for Remote Output 13 D2D4 ...Repeated for Remote Output 14 D2D8 ...Repeated for Remote Output 15 B-70 T60 Transformer Protection System GE Multilin...
  • Page 609 IEC 61850 GGIO2.CF.SPCSO33.ctlModel Value 0 to 2 F001 D341 IEC 61850 GGIO2.CF.SPCSO34.ctlModel Value 0 to 2 F001 D342 IEC 61850 GGIO2.CF.SPCSO35.ctlModel Value 0 to 2 F001 D343 IEC 61850 GGIO2.CF.SPCSO36.ctlModel Value 0 to 2 F001 GE Multilin T60 Transformer Protection System B-71...
  • Page 610 0 to 14 F543 1 (Va) D41F PMU 1 Port 3 PHS-x (14 items) 0 to 14 F543 1 (Va) D42D PMU 1 Communication Port 1 PHS-x Name (14 items) F203 “GE-UR-PMU-PHS 1” B-72 T60 Transformer Protection System GE Multilin...
  • Page 611 RANGE UNITS STEP FORMAT DEFAULT D49D PMU 1 Port 2 PHS-x Name (14 items) F203 “GE-UR-PMU-PHS 1” D50D PMU 1 Port 3 PHS-x Name (14 items) F203 “GE-UR-PMU-PHS 1” D57D PMU 1 Port 1 A-CH-x (8 items) 0 to 65535...
  • Page 612: Data Formats

    0 = 25%, 1 = 50%, 2 = 75%, 3 = 100% UR_UINT32 TIME in SR format (alternate format for F050) First 16 bits are Hours/Minutes (HH:MM:xx.xxx). Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm. Minutes: 0 to 59 in steps of 1. B-74 T60 Transformer Protection System GE Multilin...
  • Page 613 1200 19200 14400 0.76 2.30 5.30 17.50 2400 38400 28800 0.78 2.40 5.40 18.00 4800 57600 33600 0.80 2.50 5.50 18.50 0.82 2.60 5.60 19.00 0.84 2.70 5.70 19.50 0.86 2.80 5.80 20.00 GE Multilin T60 Transformer Protection System B-75...
  • Page 614 Neutral Instantaneous Overcurrent 11 POTT Neutral Instantaneous Overcurrent 12 Power Swing Detect Neutral Time Overcurrent 1 Transformer Hottest Spot Neutral Time Overcurrent 2 Transformer Aging Factor Neutral Time Overcurrent 3 Transformer Loss of Life B-76 T60 Transformer Protection System GE Multilin...
  • Page 615 Digital Element 8 Control pushbutton 3 Digital Element 9 Control pushbutton 4 Digital Element 10 Control pushbutton 5 Digital Element 11 Control pushbutton 6 Digital Element 12 Control pushbutton 7 Digital Element 13 GE Multilin T60 Transformer Protection System B-77...
  • Page 616 User-Programmable Pushbutton 6 RTD Input 2 User-Programmable Pushbutton 7 RTD Input 3 User-Programmable Pushbutton 8 RTD Input 4 User-Programmable Pushbutton 9 RTD Input 5 User-Programmable Pushbutton 10 RTD Input 6 User-Programmable Pushbutton 11 B-78 T60 Transformer Protection System GE Multilin...
  • Page 617 Remote RTD Input 10 1001 Remote RTD Input 11 1002 Remote RTD Input 12 F141 ENUMERATION: SELF TEST ERRORS 1012 Thermal overload protection 1 1013 Thermal overload protection 2 Bitmask Error Any Self Tests IRIG-B Failure GE Multilin T60 Transformer Protection System B-79...
  • Page 618 Module Failure 12 ENUMERATION: SETTING GROUP 0 = Active Group, 1 = Group 1, 2 = Group 2, 3 = Group 3 4 = Group 4, 5 = Group 5, 6 = Group 6 B-80 T60 Transformer Protection System GE Multilin...
  • Page 619 4 = SRC 5, 5 = SRC 6 DNA-24 UserSt-27 DNA-25 UserSt-28 DNA-26 UserSt-29 F168 DNA-27 UserSt-30 ENUMERATION: INRUSH INHIBIT FUNCTION DNA-28 UserSt-31 0 = Disabled, 1 = Adapt. 2nd, 2 = Trad. 2nd GE Multilin T60 Transformer Protection System B-81...
  • Page 620 ENUMERATION: MEASUREMENT MODE DV1 Xor DV2 DV1 and DV2 0 = Phase to Ground, 1 = Phase to Phase F189 ENUMERATION: INRUSH INHIBIT MODE 0 = Per Phase, 1 = 2-out-of-3, 2 = Average B-82 T60 Transformer Protection System GE Multilin...
  • Page 621 20 registers, 16 Bits: 1st Char MSB, 2nd Char LSB 0 = Calculated V0, 1 = Measured VX F202 TEXT20: 20-CHARACTER ASCII TEXT 10 registers, 16 Bits: 1st Char MSB, 2nd Char LSB GE Multilin T60 Transformer Protection System B-83...
  • Page 622 MMXU3.MX.TotPF.mag.f MMXU1.MX.W.phsA.cVal.mag.f MMXU3.MX.Hz.mag.f MMXU1.MX.W.phsB.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.mag.f MMXU1.MX.W.phsC.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.ang.f MMXU1.MX.VAr.phsA.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.mag.f MMXU1.MX.VAr.phsB.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.ang.f MMXU1.MX.VAr.phsC.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.mag.f MMXU1.MX.VA.phsA.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.ang.f MMXU1.MX.VA.phsB.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.mag.f MMXU1.MX.VA.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU1.MX.PF.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU1.MX.PF.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU1.MX.PF.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU2.MX.TotW.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU2.MX.TotVAr.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU2.MX.TotVA.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU2.MX.TotPF.mag.f MMXU3.MX.A.phsB.cVal.mag.f B-84 T60 Transformer Protection System GE Multilin...
  • Page 623 MMXU5.MX.PF.phsB.cVal.mag.f MMXU4.MX.A.phsB.cVal.ang.f MMXU5.MX.PF.phsC.cVal.mag.f MMXU4.MX.A.phsC.cVal.mag.f MMXU6.MX.TotW.mag.f MMXU4.MX.A.phsC.cVal.ang.f MMXU6.MX.TotVAr.mag.f MMXU4.MX.A.neut.cVal.mag.f MMXU6.MX.TotVA.mag.f MMXU4.MX.A.neut.cVal.ang.f MMXU6.MX.TotPF.mag.f MMXU4.MX.W.phsA.cVal.mag.f MMXU6.MX.Hz.mag.f MMXU4.MX.W.phsB.cVal.mag.f MMXU6.MX.PPV.phsAB.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU6.MX.PPV.phsAB.cVal.ang.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f MMXU4.MX.VA.phsA.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f GE Multilin T60 Transformer Protection System B-85...
  • Page 624 IEC 61850 GOOSE Rx dataset GGIO4.MX.AnIn17.mag.f item GGIO4.MX.AnIn18.mag.f None GGIO4.MX.AnIn19.mag.f GGIO3.ST.Ind1.q GGIO4.MX.AnIn20.mag.f GGIO3.ST.Ind1.stVal GGIO4.MX.AnIn21.mag.f GGIO3.ST.Ind2.q GGIO4.MX.AnIn22.mag.f GGIO3.ST.Ind2.stVal GGIO4.MX.AnIn23.mag.f ↓ ↓ GGIO4.MX.AnIn24.mag.f GGIO1.ST.Ind64q GGIO4.MX.AnIn25.mag.f GGIO1.ST.Ind64.stVal GGIO4.MX.AnIn26.mag.f GGIO3.MX.AnIn1.mag.f GGIO4.MX.AnIn27.mag.f GGIO3.MX.AnIn2.mag.f GGIO4.MX.AnIn28.mag.f GGIO3.MX.AnIn3.mag.f GGIO4.MX.AnIn29.mag.f GGIO3.MX.AnIn4.mag.f GGIO4.MX.AnIn30.mag.f GGIO3.MX.AnIn5.mag.f GGIO4.MX.AnIn31.mag.f B-86 T60 Transformer Protection System GE Multilin...
  • Page 625 Wednesday GGIO3.ST.UIntIn4.stVal Thursday GGIO3.ST.UIntIn5.q Friday GGIO3.ST.UIntIn5.stVal Saturday GGIO3.ST.UIntIn6.q GGIO3.ST.UIntIn6.stVal GGIO3.ST.UIntIn7.q F239 GGIO3.ST.UIntIn7.stVal ENUMERATION: REAL TIME CLOCK DAYLIGHT SAVINGS TIME START DAY INSTANCE GGIO3.ST.UIntIn8.q GGIO3.ST.UIntIn8.stVal Value Instance GGIO3.ST.UIntIn9.q First GGIO3.ST.UIntIn9.stVal Second GGIO3.ST.UIntIn10.q Third GGIO3.ST.UIntIn10.stVal GE Multilin T60 Transformer Protection System B-87...
  • Page 626 Description 0...20mA None 4...20mA U1/DC1 potentiometer U1/DC2 tap position U1/DC3 U2/DC1 F247 ENUMERATION: BRICK AC BANK ORIGIN U8/DC3 Value Description None F256 U1/AC1..3 ENUMERATION: BRICK ORIGIN/DESTINATION U1/AC5..7 U2/AC1..3 Value Description U2/AC5..7 None U3/AC1..3 B-88 T60 Transformer Protection System GE Multilin...
  • Page 627 [16] DIRECT INPUTS (1 to 96) ENUMERATION: ANALOG INPUT MODE [18] REMOTE OUTPUT DNA BIT PAIRS (1 to 32) 0 = Default Value, 1 = Last Known [20] REMOTE OUTPUT UserSt BIT PAIRS (1 to 32) GE Multilin T60 Transformer Protection System B-89...
  • Page 628 ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION 0 = Signed, 1 = Absolute Bitmask Default variation F516 ENUMERATION ELEMENT COMPARE MODE 0 = Level, 1 = Delta F517 ENUMERATION: ELEMENT DIRECTION OPERATION 0 = Over, 1 = Under B-90 T60 Transformer Protection System GE Multilin...
  • Page 629 UR_UINT16: FLEXANALOG PARAMETER Corresponds to the Modbus address of the value used when this parameter is selected. Only certain values can be used as FlexAn- alogs (basically all metering quantities used in protection). GE Multilin T60 Transformer Protection System B-91...
  • Page 630 Remote RTD 12 PDIF3.ST.Op.general PDIF4.ST.Str.general PDIF4.ST.Op.general F605 ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT PDIS1.ST.Str.general STATUS PDIS1.ST.Op.general PDIS2.ST.Str.general Enumeration Remote DPS input status PDIS2.ST.Op.general Intermediate PDIS3.ST.Str.general PDIS3.ST.Op.general PDIS4.ST.Str.general PDIS4.ST.Op.general PDIS5.ST.Str.general PDIS5.ST.Op.general PDIS6.ST.Str.general PDIS6.ST.Op.general PDIS7.ST.Str.general PDIS7.ST.Op.general B-92 T60 Transformer Protection System GE Multilin...
  • Page 631 PIOC42.ST.Op.general PIOC16.ST.Op.general PIOC43.ST.Str.general PIOC17.ST.Str.general PIOC43.ST.Op.general PIOC17.ST.Op.general PIOC44.ST.Str.general PIOC18.ST.Str.general PIOC44.ST.Op.general PIOC18.ST.Op.general PIOC45.ST.Str.general PIOC19.ST.Str.general PIOC45.ST.Op.general PIOC19.ST.Op.general PIOC46.ST.Str.general PIOC20.ST.Str.general PIOC46.ST.Op.general PIOC20.ST.Op.general PIOC47.ST.Str.general PIOC21.ST.Str.general PIOC47.ST.Op.general PIOC21.ST.Op.general PIOC48.ST.Str.general PIOC22.ST.Str.general PIOC48.ST.Op.general PIOC22.ST.Op.general PIOC49.ST.Str.general PIOC23.ST.Str.general PIOC49.ST.Op.general PIOC23.ST.Op.general PIOC50.ST.Str.general PIOC24.ST.Str.general PIOC50.ST.Op.general GE Multilin T60 Transformer Protection System B-93...
  • Page 632 PTOC23.ST.Op.general PIOC69.ST.Op.general PTOC24.ST.Str.general PIOC70.ST.Str.general PTOC24.ST.Op.general PIOC70.ST.Op.general PTOV1.ST.Str.general PIOC71.ST.Str.general PTOV1.ST.Op.general PIOC71.ST.Op.general PTOV2.ST.Str.general PIOC72.ST.Str.general PTOV2.ST.Op.general PIOC72.ST.Op.general PTOV3.ST.Str.general PTOC1.ST.Str.general PTOV3.ST.Op.general PTOC1.ST.Op.general PTOV4.ST.Str.general PTOC2.ST.Str.general PTOV4.ST.Op.general PTOC2.ST.Op.general PTOV5.ST.Str.general PTOC3.ST.Str.general PTOV5.ST.Op.general PTOC3.ST.Op.general PTOV6.ST.Str.general PTOC4.ST.Str.general PTOV6.ST.Op.general PTOC4.ST.Op.general PTOV7.ST.Str.general PTOC5.ST.Str.general PTOV7.ST.Op.general B-94 T60 Transformer Protection System GE Multilin...
  • Page 633 RBRF23.ST.OpIn.general PTUV10.ST.Op.general RBRF24.ST.OpEx.general PTUV11.ST.Str.general RBRF24.ST.OpIn.general PTUV11.ST.Op.general RFLO1.MX.FltDiskm.mag.f PTUV12.ST.Str.general RFLO2.MX.FltDiskm.mag.f PTUV12.ST.Op.general RFLO3.MX.FltDiskm.mag.f PTUV13.ST.Str.general RFLO4.MX.FltDiskm.mag.f PTUV13.ST.Op.general RFLO5.MX.FltDiskm.mag.f RBRF1.ST.OpEx.general RPSB1.ST.Str.general RBRF1.ST.OpIn.general RPSB1.ST.Op.general RBRF2.ST.OpEx.general RPSB1.ST.BlkZn.stVal RBRF2.ST.OpIn.general RREC1.ST.Op.general RBRF3.ST.OpEx.general RREC1.ST.AutoRecSt.stVal RBRF3.ST.OpIn.general RREC2.ST.Op.general RBRF4.ST.OpEx.general RREC2.ST.AutoRecSt.stVal RBRF4.ST.OpIn.general RREC3.ST.Op.general RBRF5.ST.OpEx.general RREC3.ST.AutoRecSt.stVal GE Multilin T60 Transformer Protection System B-95...
  • Page 634 GGIO1.ST.Ind24.stVal CSWI16.ST.Pos.stVal GGIO1.ST.Ind25.stVal CSWI17.ST.Loc.stVal GGIO1.ST.Ind26.stVal CSWI17.ST.Pos.stVal GGIO1.ST.Ind27.stVal CSWI18.ST.Loc.stVal GGIO1.ST.Ind28.stVal CSWI18.ST.Pos.stVal GGIO1.ST.Ind29.stVal CSWI19.ST.Loc.stVal GGIO1.ST.Ind30.stVal CSWI19.ST.Pos.stVal GGIO1.ST.Ind31.stVal CSWI20.ST.Loc.stVal GGIO1.ST.Ind32.stVal CSWI20.ST.Pos.stVal GGIO1.ST.Ind33.stVal CSWI21.ST.Loc.stVal GGIO1.ST.Ind34.stVal CSWI21.ST.Pos.stVal GGIO1.ST.Ind35.stVal CSWI22.ST.Loc.stVal GGIO1.ST.Ind36.stVal CSWI22.ST.Pos.stVal GGIO1.ST.Ind37.stVal CSWI23.ST.Loc.stVal GGIO1.ST.Ind38.stVal CSWI23.ST.Pos.stVal GGIO1.ST.Ind39.stVal CSWI24.ST.Loc.stVal GGIO1.ST.Ind40.stVal B-96 T60 Transformer Protection System GE Multilin...
  • Page 635 MMXU1.MX.TotVAr.mag.f GGIO1.ST.Ind78.stVal MMXU1.MX.TotVA.mag.f GGIO1.ST.Ind79.stVal MMXU1.MX.TotPF.mag.f GGIO1.ST.Ind80.stVal MMXU1.MX.Hz.mag.f GGIO1.ST.Ind81.stVal MMXU1.MX.PPV.phsAB.cVal.mag.f GGIO1.ST.Ind82.stVal MMXU1.MX.PPV.phsAB.cVal.ang.f GGIO1.ST.Ind83.stVal MMXU1.MX.PPV.phsBC.cVal.mag.f GGIO1.ST.Ind84.stVal MMXU1.MX.PPV.phsBC.cVal.ang.f GGIO1.ST.Ind85.stVal MMXU1.MX.PPV.phsCA.cVal.mag.f GGIO1.ST.Ind86.stVal MMXU1.MX.PPV.phsCA.cVal.ang.f GGIO1.ST.Ind87.stVal MMXU1.MX.PhV.phsA.cVal.mag.f GGIO1.ST.Ind88.stVal MMXU1.MX.PhV.phsA.cVal.ang.f GGIO1.ST.Ind89.stVal MMXU1.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind90.stVal MMXU1.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind91.stVal MMXU1.MX.PhV.phsC.cVal.mag.f GGIO1.ST.Ind92.stVal MMXU1.MX.PhV.phsC.cVal.ang.f GGIO1.ST.Ind93.stVal MMXU1.MX.A.phsA.cVal.mag.f GE Multilin T60 Transformer Protection System B-97...
  • Page 636 MMXU3.MX.VA.phsC.cVal.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU2.MX.A.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU2.MX.A.phsB.cVal.ang.f MMXU3.MX.PF.phsC.cVal.mag.f MMXU2.MX.A.phsC.cVal.mag.f MMXU4.MX.TotW.mag.f MMXU2.MX.A.phsC.cVal.ang.f MMXU4.MX.TotVAr.mag.f MMXU2.MX.A.neut.cVal.mag.f MMXU4.MX.TotVA.mag.f MMXU2.MX.A.neut.cVal.ang.f MMXU4.MX.TotPF.mag.f MMXU2.MX.W.phsA.cVal.mag.f MMXU4.MX.Hz.mag.f MMXU2.MX.W.phsB.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.W.phsC.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.ang.f MMXU2.MX.VAr.phsA.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.mag.f MMXU2.MX.VAr.phsB.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.ang.f MMXU2.MX.VAr.phsC.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.mag.f MMXU2.MX.VA.phsA.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.ang.f MMXU2.MX.VA.phsB.cVal.mag.f MMXU4.MX.PhV.phsA.cVal.mag.f MMXU2.MX.VA.phsC.cVal.mag.f MMXU4.MX.PhV.phsA.cVal.ang.f B-98 T60 Transformer Protection System GE Multilin...
  • Page 637 MMXU6.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU6.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU6.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.mag.f MMXU6.MX.VA.phsA.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.ang.f MMXU6.MX.VA.phsB.cVal.mag.f MMXU5.MX.A.phsA.cVal.mag.f MMXU6.MX.VA.phsC.cVal.mag.f MMXU5.MX.A.phsA.cVal.ang.f MMXU6.MX.PF.phsA.cVal.mag.f MMXU5.MX.A.phsB.cVal.mag.f MMXU6.MX.PF.phsB.cVal.mag.f MMXU5.MX.A.phsB.cVal.ang.f MMXU6.MX.PF.phsC.cVal.mag.f MMXU5.MX.A.phsC.cVal.mag.f GGIO4.MX.AnIn1.mag.f MMXU5.MX.A.phsC.cVal.ang.f GGIO4.MX.AnIn2.mag.f MMXU5.MX.A.neut.cVal.mag.f GGIO4.MX.AnIn3.mag.f MMXU5.MX.A.neut.cVal.ang.f GGIO4.MX.AnIn4.mag.f MMXU5.MX.W.phsA.cVal.mag.f GGIO4.MX.AnIn5.mag.f MMXU5.MX.W.phsB.cVal.mag.f GGIO4.MX.AnIn6.mag.f MMXU5.MX.W.phsC.cVal.mag.f GGIO4.MX.AnIn7.mag.f MMXU5.MX.VAr.phsA.cVal.mag.f GGIO4.MX.AnIn8.mag.f GE Multilin T60 Transformer Protection System B-99...
  • Page 638 XSWI7.ST.Loc.stVal GGIO1.ST.Ind1.q XSWI7.ST.Pos.stVal GGIO1.ST.Ind1.stVal XSWI8.ST.Loc.stVal GGIO1.ST.Ind2.q XSWI8.ST.Pos.stVal GGIO1.ST.Ind2.stVal XSWI9.ST.Loc.stVal GGIO1.ST.Ind3.q XSWI9.ST.Pos.stVal GGIO1.ST.Ind3.stVal XSWI10.ST.Loc.stVal GGIO1.ST.Ind4.q XSWI10.ST.Pos.stVal GGIO1.ST.Ind4.stVal XSWI11.ST.Loc.stVal GGIO1.ST.Ind5.q XSWI11.ST.Pos.stVal GGIO1.ST.Ind5.stVal XSWI12.ST.Loc.stVal GGIO1.ST.Ind6.q XSWI12.ST.Pos.stVal GGIO1.ST.Ind6.stVal XSWI13.ST.Loc.stVal GGIO1.ST.Ind7.q XSWI13.ST.Pos.stVal GGIO1.ST.Ind7.stVal XSWI14.ST.Loc.stVal GGIO1.ST.Ind8.q XSWI14.ST.Pos.stVal GGIO1.ST.Ind8.stVal XSWI15.ST.Loc.stVal B-100 T60 Transformer Protection System GE Multilin...
  • Page 639 GGIO1.ST.Ind53.stVal GGIO1.ST.Ind27.stVal GGIO1.ST.Ind54.q GGIO1.ST.Ind28.q GGIO1.ST.Ind54.stVal GGIO1.ST.Ind28.stVal GGIO1.ST.Ind55.q GGIO1.ST.Ind29.q GGIO1.ST.Ind55.stVal GGIO1.ST.Ind29.stVal GGIO1.ST.Ind56.q GGIO1.ST.Ind30.q GGIO1.ST.Ind56.stVal GGIO1.ST.Ind30.stVal GGIO1.ST.Ind57.q GGIO1.ST.Ind31.q GGIO1.ST.Ind57.stVal GGIO1.ST.Ind31.stVal GGIO1.ST.Ind58.q GGIO1.ST.Ind32.q GGIO1.ST.Ind58.stVal GGIO1.ST.Ind32.stVal GGIO1.ST.Ind59.q GGIO1.ST.Ind33.q GGIO1.ST.Ind59.stVal GGIO1.ST.Ind33.stVal GGIO1.ST.Ind60.q GGIO1.ST.Ind34.q GGIO1.ST.Ind60.stVal GGIO1.ST.Ind34.stVal GGIO1.ST.Ind61.q GGIO1.ST.Ind35.q GGIO1.ST.Ind61.stVal GE Multilin T60 Transformer Protection System B-101...
  • Page 640 GGIO1.ST.Ind106.stVal GGIO1.ST.Ind80.stVal GGIO1.ST.Ind107.q GGIO1.ST.Ind81.q GGIO1.ST.Ind107.stVal GGIO1.ST.Ind81.stVal GGIO1.ST.Ind108.q GGIO1.ST.Ind82.q GGIO1.ST.Ind108.stVal GGIO1.ST.Ind82.stVal GGIO1.ST.Ind109.q GGIO1.ST.Ind83.q GGIO1.ST.Ind109.stVal GGIO1.ST.Ind83.stVal GGIO1.ST.Ind110.q GGIO1.ST.Ind84.q GGIO1.ST.Ind110.stVal GGIO1.ST.Ind84.stVal GGIO1.ST.Ind111.q GGIO1.ST.Ind85.q GGIO1.ST.Ind111.stVal GGIO1.ST.Ind85.stVal GGIO1.ST.Ind112.q GGIO1.ST.Ind86.q GGIO1.ST.Ind112.stVal GGIO1.ST.Ind86.stVal GGIO1.ST.Ind113.q GGIO1.ST.Ind87.q GGIO1.ST.Ind113.stVal GGIO1.ST.Ind87.stVal GGIO1.ST.Ind114.q GGIO1.ST.Ind88.q GGIO1.ST.Ind114.stVal B-102 T60 Transformer Protection System GE Multilin...
  • Page 641 MMXU2.MX.A.neut.cVal.ang.f MMXU1.MX.PPV.phsCA.cVal.mag.f MMXU2.MX.W.phsA.cVal.mag.f MMXU1.MX.PPV.phsCA.cVal.ang.f MMXU2.MX.W.phsB.cVal.mag.f MMXU1.MX.PhV.phsA.cVal.mag.f MMXU2.MX.W.phsC.cVal.mag.f MMXU1.MX.PhV.phsA.cVal.ang.f MMXU2.MX.VAr.phsA.cVal.mag.f MMXU1.MX.PhV.phsB.cVal.mag.f MMXU2.MX.VAr.phsB.cVal.mag.f MMXU1.MX.PhV.phsB.cVal.ang.f MMXU2.MX.VAr.phsC.cVal.mag.f MMXU1.MX.PhV.phsC.cVal.mag.f MMXU2.MX.VA.phsA.cVal.mag.f MMXU1.MX.PhV.phsC.cVal.ang.f MMXU2.MX.VA.phsB.cVal.mag.f MMXU1.MX.A.phsA.cVal.mag.f MMXU2.MX.VA.phsC.cVal.mag.f MMXU1.MX.A.phsA.cVal.ang.f MMXU2.MX.PF.phsA.cVal.mag.f MMXU1.MX.A.phsB.cVal.mag.f MMXU2.MX.PF.phsB.cVal.mag.f MMXU1.MX.A.phsB.cVal.ang.f MMXU2.MX.PF.phsC.cVal.mag.f MMXU1.MX.A.phsC.cVal.mag.f MMXU3.MX.TotW.mag.f MMXU1.MX.A.phsC.cVal.ang.f MMXU3.MX.TotVAr.mag.f MMXU1.MX.A.neut.cVal.mag.f MMXU3.MX.TotVA.mag.f MMXU1.MX.A.neut.cVal.ang.f MMXU3.MX.TotPF.mag.f GE Multilin T60 Transformer Protection System B-103...
  • Page 642 MMXU5.MX.A.phsB.cVal.mag.f MMXU4.MX.Hz.mag.f MMXU5.MX.A.phsB.cVal.ang.f MMXU4.MX.PPV.phsAB.cVal.mag.f MMXU5.MX.A.phsC.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.ang.f MMXU5.MX.A.phsC.cVal.ang.f MMXU4.MX.PPV.phsBC.cVal.mag.f MMXU5.MX.A.neut.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.ang.f MMXU5.MX.A.neut.cVal.ang.f MMXU4.MX.PPV.phsCA.cVal.mag.f MMXU5.MX.W.phsA.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.ang.f MMXU5.MX.W.phsB.cVal.mag.f MMXU4.MX.PhV.phsA.cVal.mag.f MMXU5.MX.W.phsC.cVal.mag.f MMXU4.MX.PhV.phsA.cVal.ang.f MMXU5.MX.VAr.phsA.cVal.mag.f MMXU4.MX.PhV.phsB.cVal.mag.f MMXU5.MX.VAr.phsB.cVal.mag.f MMXU4.MX.PhV.phsB.cVal.ang.f MMXU5.MX.VAr.phsC.cVal.mag.f MMXU4.MX.PhV.phsC.cVal.mag.f MMXU5.MX.VA.phsA.cVal.mag.f MMXU4.MX.PhV.phsC.cVal.ang.f MMXU5.MX.VA.phsB.cVal.mag.f MMXU4.MX.A.phsA.cVal.mag.f MMXU5.MX.VA.phsC.cVal.mag.f MMXU4.MX.A.phsA.cVal.ang.f MMXU5.MX.PF.phsA.cVal.mag.f MMXU4.MX.A.phsB.cVal.mag.f MMXU5.MX.PF.phsB.cVal.mag.f B-104 T60 Transformer Protection System GE Multilin...
  • Page 643 GGIO5.ST.UIntIn10.stVal MMXU6.MX.PF.phsC.cVal.mag.f GGIO5.ST.UIntIn11.q GGIO4.MX.AnIn1.mag.f GGIO5.ST.UIntIn11.stVal GGIO4.MX.AnIn2.mag.f GGIO5.ST.UIntIn12.q GGIO4.MX.AnIn3.mag.f GGIO5.ST.UIntIn12.stVal GGIO4.MX.AnIn4.mag.f GGIO5.ST.UIntIn13.q GGIO4.MX.AnIn5.mag.f GGIO5.ST.UIntIn13.stVal GGIO4.MX.AnIn6.mag.f GGIO5.ST.UIntIn14.q GGIO4.MX.AnIn7.mag.f GGIO5.ST.UIntIn14.stVal GGIO4.MX.AnIn8.mag.f GGIO5.ST.UIntIn15.q GGIO4.MX.AnIn9.mag.f GGIO5.ST.UIntIn15.stVal GGIO4.MX.AnIn10.mag.f GGIO5.ST.UIntIn16.q GGIO4.MX.AnIn11.mag.f GGIO5.ST.UIntIn16.stVal GGIO4.MX.AnIn12.mag.f PDIF1.ST.Str.general GGIO4.MX.AnIn13.mag.f PDIF1.ST.Op.general GGIO4.MX.AnIn14.mag.f PDIF2.ST.Str.general GGIO4.MX.AnIn15.mag.f PDIF2.ST.Op.general GE Multilin T60 Transformer Protection System B-105...
  • Page 644 PIOC33.ST.Op.general PIOC7.ST.Op.general PIOC34.ST.Str.general PIOC8.ST.Str.general PIOC34.ST.Op.general PIOC8.ST.Op.general PIOC35.ST.Str.general PIOC9.ST.Str.general PIOC35.ST.Op.general PIOC9.ST.Op.general PIOC36.ST.Str.general PIOC10.ST.Str.general PIOC36.ST.Op.general PIOC10.ST.Op.general PIOC37.ST.Str.general PIOC11.ST.Str.general PIOC37.ST.Op.general PIOC11.ST.Op.general PIOC38.ST.Str.general PIOC12.ST.Str.general PIOC38.ST.Op.general PIOC12.ST.Op.general PIOC39.ST.Str.general PIOC13.ST.Str.general PIOC39.ST.Op.general PIOC13.ST.Op.general PIOC40.ST.Str.general PIOC14.ST.Str.general PIOC40.ST.Op.general PIOC14.ST.Op.general PIOC41.ST.Str.general PIOC15.ST.Str.general PIOC41.ST.Op.general B-106 T60 Transformer Protection System GE Multilin...
  • Page 645 PTOC14.ST.Op.general PIOC60.ST.Op.general PTOC15.ST.Str.general PIOC61.ST.Str.general PTOC15.ST.Op.general PIOC61.ST.Op.general PTOC16.ST.Str.general PIOC62.ST.Str.general PTOC16.ST.Op.general PIOC62.ST.Op.general PTOC17.ST.Str.general PIOC63.ST.Str.general PTOC17.ST.Op.general PIOC63.ST.Op.general PTOC18.ST.Str.general PIOC64.ST.Str.general PTOC18.ST.Op.general PIOC64.ST.Op.general PTOC19.ST.Str.general PIOC65.ST.Str.general PTOC19.ST.Op.general PIOC65.ST.Op.general PTOC20.ST.Str.general PIOC66.ST.Str.general PTOC20.ST.Op.general PIOC66.ST.Op.general PTOC21.ST.Str.general PIOC67.ST.Str.general PTOC21.ST.Op.general PIOC67.ST.Op.general PTOC22.ST.Str.general PIOC68.ST.Str.general PTOC22.ST.Op.general GE Multilin T60 Transformer Protection System B-107...
  • Page 646 RBRF14.ST.OpIn.general PTUV1.ST.Op.general RBRF15.ST.OpEx.general PTUV2.ST.Str.general RBRF15.ST.OpIn.general PTUV2.ST.Op.general RBRF16.ST.OpEx.general PTUV3.ST.Str.general RBRF16.ST.OpIn.general PTUV3.ST.Op.general RBRF17.ST.OpEx.general PTUV4.ST.Str.general RBRF17.ST.OpIn.general PTUV4.ST.Op.general RBRF18.ST.OpEx.general PTUV5.ST.Str.general RBRF18.ST.OpIn.general PTUV5.ST.Op.general RBRF19.ST.OpEx.general PTUV6.ST.Str.general RBRF19.ST.OpIn.general PTUV6.ST.Op.general RBRF20.ST.OpEx.general PTUV7.ST.Str.general RBRF20.ST.OpIn.general PTUV7.ST.Op.general RBRF21.ST.OpEx.general PTUV8.ST.Str.general RBRF21.ST.OpIn.general PTUV8.ST.Op.general RBRF22.ST.OpEx.general PTUV9.ST.Str.general RBRF22.ST.OpIn.general B-108 T60 Transformer Protection System GE Multilin...
  • Page 647 XSWI3.ST.Pos.stVal CSWI7.ST.Pos.stVal XSWI4.ST.Loc.stVal CSWI8.ST.Loc.stVal XSWI4.ST.Pos.stVal CSWI8.ST.Pos.stVal XSWI5.ST.Loc.stVal CSWI9.ST.Loc.stVal XSWI5.ST.Pos.stVal CSWI9.ST.Pos.stVal XSWI6.ST.Loc.stVal CSWI10.ST.Loc.stVal XSWI6.ST.Pos.stVal CSWI10.ST.Pos.stVal XSWI7.ST.Loc.stVal CSWI11.ST.Loc.stVal XSWI7.ST.Pos.stVal CSWI11.ST.Pos.stVal XSWI8.ST.Loc.stVal CSWI12.ST.Loc.stVal XSWI8.ST.Pos.stVal CSWI12.ST.Pos.stVal XSWI9.ST.Loc.stVal CSWI13.ST.Loc.stVal XSWI9.ST.Pos.stVal CSWI13.ST.Pos.stVal XSWI10.ST.Loc.stVal CSWI14.ST.Loc.stVal XSWI10.ST.Pos.stVal CSWI14.ST.Pos.stVal XSWI11.ST.Loc.stVal CSWI15.ST.Loc.stVal XSWI11.ST.Pos.stVal GE Multilin T60 Transformer Protection System B-109...
  • Page 648 XSWI19.ST.Loc.stVal XSWI19.ST.Pos.stVal XSWI20.ST.Loc.stVal XSWI20.ST.Pos.stVal XSWI21.ST.Loc.stVal XSWI21.ST.Pos.stVal XSWI22.ST.Loc.stVal XSWI22.ST.Pos.stVal XSWI23.ST.Loc.stVal XSWI23.ST.Pos.stVal XSWI24.ST.Loc.stVal XSWI24.ST.Pos.stVal XCBR1.ST.Loc.stVal XCBR1.ST.Pos.stVal XCBR2.ST.Loc.stVal 1000 XCBR2.ST.Pos.stVal 1001 XCBR3.ST.Loc.stVal 1002 XCBR3.ST.Pos.stVal 1003 XCBR4.ST.Loc.stVal 1004 XCBR4.ST.Pos.stVal 1005 XCBR5.ST.Loc.stVal 1006 XCBR5.ST.Pos.stVal 1007 XCBR6.ST.Loc.stVal 1008 XCBR6.ST.Pos.stVal B-110 T60 Transformer Protection System GE Multilin...
  • Page 649: Iec 61850

    System Specification Description (SSD) file. The entire substation con- figuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individ- ual ICD files and the SSD file. GE Multilin T60 Transformer Protection System...
  • Page 650: File Transfer By Iec 61850

    With the Copy option active, select a file to transfer and click the Go button. The file is copied and displays in the Local list on the left side of the window. Repeat the process to transfer any other files. Figure 0–1: FILE TRANSFER BY IEC 61850 T60 Transformer Protection System GE Multilin...
  • Page 651: Server Data Organization

    GGIO4 (4 to 32) and the choice of the FlexAnalog™ values that determine the value of the GGIO4 analog inputs. Clients can utilize polling or the IEC 61850 unbuffered reporting feature available from GGIO4 in order to obtain the analog values provided by GGIO4. GE Multilin T60 Transformer Protection System...
  • Page 652: Mmxu: Analog Measured Values

    The following list describes the protection elements for all UR-series relays. The T60 relay will contain a subset of protec- tion elements from this list. • PDIF: bus differential, transformer instantaneous differential, transformer percent differential, current differential T60 Transformer Protection System GE Multilin...
  • Page 653 IEC 61850 control model. • XCBR1.CO.BlkCls: This is where IEC 61850 clients can issue block close commands to the breaker. Direct control with normal security is the only supported IEC 61850 control model. GE Multilin T60 Transformer Protection System...
  • Page 654: Server Features And Configuration

    T60. This attribute is programmed through the setting and its LOCATION default value is “Location”. This value should be changed to describe the actual physical location of the T60. T60 Transformer Protection System GE Multilin...
  • Page 655: Logical Node Name Prefixes

    The exact structure and values of the supported IEC 61850 logical nodes can be seen by connecting to a T60 relay with an MMS browser, such as the “MMS Object Explorer and AXS4-MMS” DDE/OPC server from Sisco Inc. GE Multilin T60 Transformer Protection System...
  • Page 656: Generic Substation Event Services: Gsse And Goose

    The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the T60. The T60 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data transfer between devices. T60 Transformer Protection System GE Multilin...
  • Page 657 Configure the GOOSE service settings by making the following changes in the  PRODUCT SETUP COMMUNICATION      IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIGURABLE GOOSE CONFIGU- settings menu: RABLE GOOSE 1 GE Multilin T60 Transformer Protection System...
  • Page 658: Ethernet Mac Address For Gsse/Goose

    (for example, 00 A0 F4 01 02 03). It is used in all Ethernet frames as the ‘source’ address of the frame. Each Ethernet frame also contains a destination address. The destination address can be different for each Ethernet frame depending on the intended destination of the frame. C-10 T60 Transformer Protection System GE Multilin...
  • Page 659: Gsse Id And Goose Id Settings

    DatSet - the name of the associated dataset, and GoCBRef - the reference (name) of the associated GOOSE control block. These strings are automatically populated and interpreted by the T60; no settings are required. GE Multilin T60 Transformer Protection System...
  • Page 660: Iec 61850 Implementation Via Enervista Ur Setup

    An ICD file is generated for the T60 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 661: Configuring Iec 61850 Settings

    It can also import a system SCL file (SCD) to set communication configuration parame- ters (that is, required addresses, reception GOOSE datasets, IDs of incoming GOOSE datasets, etc.) for the IED. The IED configurator functionality is implemented in the GE Multilin EnerVista UR Setup software. C.5.2 CONFIGURING IEC 61850 SETTINGS Before creating an ICD file, the user can customize the IEC 61850 related settings for the IED.
  • Page 662: About Icd Files

    Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
  • Page 663 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. GE Multilin T60 Transformer Protection System C-15...
  • Page 664 RptEnabled Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure C–4: ICD FILE STRUCTURE, IED NODE C-16 T60 Transformer Protection System GE Multilin...
  • Page 665 BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure C–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE GE Multilin T60 Transformer Protection System C-17...
  • Page 666: Creating An Icd File With Enervista Ur Setup

    C.5.5 ABOUT SCD FILES System configuration is performed in the system configurator. While many vendors (including GE Multilin) are working their own system configuration tools, there are some system configurators available in the market (for example, Siemens DIGSI version 4.6 or above and ASE Visual SCL Beta 0.12).
  • Page 667 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE GE Multilin T60 Transformer Protection System C-19...
  • Page 668 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. C-20 T60 Transformer Protection System GE Multilin...
  • Page 669: Importing An Scd File With Enervista Ur Setup

    The following procedure describes how to update the T60 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item. Select the saved SCD file and click Open. GE Multilin T60 Transformer Protection System C-21...
  • Page 670 The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
  • Page 671: Acsi Conformance

    Setting group control REPORTING Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion GE Multilin T60 Transformer Protection System C-23...
  • Page 672: Acsi Services Conformance Statement

    SERVER/ UR FAMILY PUBLISHER SERVER (CLAUSE 6) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 7) Associate Abort Release LOGICAL DEVICE (CLAUSE 8) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 9) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 10) GetDataValues SetDataValues GetDataDirectory GetDataDefinition C-24 T60 Transformer Protection System GE Multilin...
  • Page 673 (qchg) S27-3 data-update (dupd) GetURCBValues SetURCBValues LOGGING (CLAUSE 14) LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 14.3.5.3.4) GOOSE-CONTROL-BLOCK SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK SendGSSEMessage GetReference GE Multilin T60 Transformer Protection System C-25...
  • Page 674 (QueryLogByTime or QueryLogAfter) NOTE c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) C-26 T60 Transformer Protection System GE Multilin...
  • Page 675: C.7.1 Logical Nodes Table

    RDRE: Disturbance recorder function RADR: Disturbance recorder channel analogue RBDR: Disturbance recorder channel binary RDRS: Disturbance record handling RBRF: Breaker failure RDIR: Directional element RFLO: Fault locator RPSB: Power swing detection/blocking RREC: Autoreclosing GE Multilin T60 Transformer Protection System C-27...
  • Page 676: Logical Nodes Table

    T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TCTR: Current transformer TVTR: Voltage transformer Y: LOGICAL NODES FOR POWER TRANSFORMERS YEFN: Earth fault neutralizer (Peterson coil) YLTC: Tap changer YPSH: Power shunt YPTR: Power transformer C-28 T60 Transformer Protection System GE Multilin...
  • Page 677 ZCON: Converter ZGEN: Generator ZGIL: Gas insulated line ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component GE Multilin T60 Transformer Protection System C-29...
  • Page 678 C.7 LOGICAL NODES APPENDIX C C-30 T60 Transformer Protection System GE Multilin...
  • Page 679: Iec 60870-5-104 Protocol

    Balanced Transmission Not Present (Balanced Transmission Only)   Unbalanced Transmission One Octet  Two Octets  Structured  Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin T60 Transformer Protection System...
  • Page 680  <18> := Packed start events of protection equipment with time tag M_EP_TB_1  <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1  <20> := Packed single-point information with status change detection M_SP_NA_1 T60 Transformer Protection System GE Multilin...
  • Page 681  <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1  <104> := Test command C_TS_NA_1  <105> := Reset process command C_RP_NA_1  <106> := Delay acquisition command C_CD_NA_1  <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin T60 Transformer Protection System...
  • Page 682 •Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 T60 Transformer Protection System GE Multilin...
  • Page 683 <34> M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin T60 Transformer Protection System...
  • Page 684 <120> F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization:  Remote initialization Cyclic Data Transmission:  Cyclic data transmission Read Procedure:  Read procedure T60 Transformer Protection System GE Multilin...
  • Page 685  Mode B: Local freeze with counter interrogation  Mode C: Freeze and transmit by counter-interrogation commands  Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously  Counter read  Counter freeze without reset GE Multilin T60 Transformer Protection System...
  • Page 686 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs T60 Transformer Protection System GE Multilin...
  • Page 687: Point List

    D.1.2 POINT LIST The IEC 60870-5-104 data points are configured through the    SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin T60 Transformer Protection System...
  • Page 688 D.1 IEC 60870-5-104 PROTOCOL APPENDIX D D-10 T60 Transformer Protection System GE Multilin...
  • Page 689: Device Profile Document

    2048 Maximum Data Link Re-tries: Maximum Application Layer Re-tries:  None  None  Fixed at 3  Configurable  Configurable Requires Data Link Layer Confirmation:  Never  Always  Sometimes  Configurable GE Multilin T60 Transformer Protection System...
  • Page 690 FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. T60 Transformer Protection System GE Multilin...
  • Page 691  16 Bits (Counter 8) Default Variation: 1  32 Bits (Counters 0 to 7, 9)  Point-by-point list attached  Other Value: _____  Point-by-point list attached Sends Multi-Fragment Responses:  Yes  No GE Multilin T60 Transformer Protection System...
  • Page 692: E.1.2 Implementation Table

    Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the T60 is not restarted, but the DNP process is restarted. T60 Transformer Protection System GE Multilin...
  • Page 693 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the T60 is not restarted, but the DNP process is restarted. GE Multilin T60 Transformer Protection System...
  • Page 694 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the T60 is not restarted, but the DNP process is restarted. T60 Transformer Protection System GE Multilin...
  • Page 695 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the T60 is not restarted, but the DNP process is restarted. GE Multilin T60 Transformer Protection System...
  • Page 696: Dnp Point Lists

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 T60 Transformer Protection System GE Multilin...
  • Page 697: Binary And Control Relay Output

    Virtual Input 27 Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin T60 Transformer Protection System...
  • Page 698: Counters

    A counter freeze command has no meaning for counters 8 and 9. T60 Digital Counter values are represented as 32-bit inte- gers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values. E-10 T60 Transformer Protection System GE Multilin...
  • Page 699: E.2.4 Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin T60 Transformer Protection System E-11...
  • Page 700 E.2 DNP POINT LISTS APPENDIX E E-12 T60 Transformer Protection System GE Multilin...
  • Page 701: Change Notes

    7 December 2007 URX-253 1601-0090-S2 5.5x 22 February 2008 URX-258 1601-0090-S3 5.5x 12 March 2008 URX-260 1601-0090-T1 5.6x 27 June 2008 08-0390 1601-0090-U1 5.7x 29 May 2009 09-0938 1601-0090-U2 5.7x 30 September 2009 09-1165 GE Multilin T60 Transformer Protection System...
  • Page 702: Changes To The T60 Manual

    PAGE PAGE CHANGE DESCRIPTION (V1) (V2) Title Title Update Manual part number to 1601-0090-W1 Update Updated ORDERING section 2-10 2-10 Update Updated PROTECTION ELEMENTS specifications section 2-14 2-15 Update Updated MONTORING ELEMENTS specifications section T60 Transformer Protection System GE Multilin...
  • Page 703 Updated INVALID PASSWORD ENTRY section 5-10 5-10 Update Updated ACCESS SUPERVISION section 5-22 5-22 Update Updated IEC 61850 PROTOCOL section 5-131 5-132 Update Updated GROUND DISTANCE section 5-151 5-152 Update Updated PERCENT DIFFERENTIAL section GE Multilin T60 Transformer Protection System...
  • Page 704 2-19 Update Updated ENVIRONMENTAL specifications section 2-20 2-20 Update Updated TYPE TESTS specifications section Update Updated VERTICAL UNITS sub-section 3-13 3-14 Update Updated CONTACT INPUTS AND OUTPUTS section Update Updated USING SETTINGS FILES section T60 Transformer Protection System GE Multilin...
  • Page 705 Updated ORDERING section 2-13 Added PROCESS BUS MODULES section 5-11 Added DUAL PERMISSION SECURITY ACCESS section 5-20 5-22 Update Updated IEC 61850 PROTOCOL section 5-67 Added REMOTE RESOURCES section 5-97 5-101 Update Updated FLEXLOGIC OPERANDS table GE Multilin T60 Transformer Protection System...
  • Page 706 Updated COMMUNICATIONS specifications section 3-35 3-36 Update Updated IEEE C37.94 INTERFACE section 3-40 Added MANAGED ETHERNET SWITCH MODULES section 4-23 Added BREAKER CONTROL section Update Updated PASSWORD SECURITY section (now titled SECURITY) 5-30 Added ETHERNET SWITCH sub-section T60 Transformer Protection System GE Multilin...
  • Page 707 Updated USER-PROGRAMMABLE LEDS section 5-41 5-42 Update Updated CONTROL PUSHBUTTONS section 5-47 Update Updated USER-PROGRAMMABLE PUSHBUTTONS section 5-49 Update Updated DIRECT INPUTS AND OUTPUTS section 5-80 5-83 Update Updated FLEXLOGIC™ OPERANDS table 5-167 Added TRIP BUS section GE Multilin T60 Transformer Protection System...
  • Page 708 Updated MODBUS MEMORY MAP section for revision 5.2x Update Updated Appendix C: IEC 61850 COMMUNICATIONS Update Updated DNP V3.00 DEVICE PROFILE section Update Updated DNP IMPLEMENTATION TABLE section Update Updated BINARY INPUT POINTS section E-10 E-10 Update Updated COUNTERS section T60 Transformer Protection System GE Multilin...
  • Page 709 Title Update Manual part number to 1601-0090-M2 3-28 3-28 Update Updated RS422 INTERFACE section 4-13 4-13 Update Updated INVALID PASSWORD ENTRY sub-section Update Updated PASSWORD SECURITY section 5-90 5-90 Update Updated PERCENT DIFFERENTIAL section GE Multilin T60 Transformer Protection System...
  • Page 710 Updated SETTING GROUPS section 5-127 5-132 Update Updated SELECTOR SWITCH section 5-148 5-154 Update Updated REMOTE INPUTS section 5-150 5-156 Update Updated DIRECT INPUTS/OUTPUTS section 5-160 Added TELEPROTECTION INPUTS/OUTPUTS section Added TELEPROTECTION INPUTS section F-10 T60 Transformer Protection System GE Multilin...
  • Page 711 The LATCHING OUTPUTS section is now a sub-section of the CONTACT OUTPUTS 5-146 5-147 Update Updated REMOTE DEVICES section 5-148 5-149 Update Updated REMOTE OUTPUTS section Update Updated MODBUS MEMORY MAP for revision 4.6x Added IEC 61850 COMMUNICATIONS appendix Update Updated DNP IMPLEMENTATION section GE Multilin T60 Transformer Protection System F-11...
  • Page 712: Abbreviations

    AMP ....Ampere FWD....Forward ANG ....Angle ANSI....American National Standards Institute G ....Generator AR ....Automatic Reclosure GE....General Electric ASDU ..... Application-layer Service Data Unit GND....Ground ASYM ..... Asymmetry GNTR..... Generator AUTO ..... Automatic GOOSE..General Object Oriented Substation Event AUX....
  • Page 713 ROD ....Remote Open Detector WRT....With Respect To RST ....Reset RSTR ..... Restrained X .....Reactance RTD....Resistance Temperature Detector XDUCER..Transducer RTU....Remote Terminal Unit XFMR....Transformer RX (Rx) ..Receive, Receiver Z......Impedance, Zone GE Multilin T60 Transformer Protection System F-13...
  • Page 714: Warranty

    F.3.1 GE MULTILIN WARRANTY For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Digital Energy Terms and Conditions at https://www.gedigitalenergy.com/multilin/warranty.htm...
  • Page 715: Index

    Modbus registers ............B-66 BANKS ............. 5-6, 5-73, 5-74 settings ................. 5-14 BATTERY FAILURE ............7-8 CLOCK BINARY INPUT POINTS ............. E-8 setting date and time ............7-2 BINARY OUTPUT POINTS ..........E-9 settings ................. 5-42 GE Multilin T60 Transformer Protection System...
  • Page 716 CURRENT BANK ............. 5-73 FlexLogic™ operands ........... 5-124 CURRENT DEMAND ............5-47 logic ................5-244 CURRENT DIFFERENTIAL Modbus registers ............B-48 Modbus registers ............B-16 settings ................ 5-243 CURRENT ELEMENTS ........... 5-181 CURRENT HARMONICS ..........2-16 T60 Transformer Protection System GE Multilin...
  • Page 717 FACEPLATE ............... 3-1, 3-2 FACEPLATE PANELS ............4-14 FAST FORM-C RELAY ............. 2-18 EAC CERTIFICATION ............2-22 FAST TRANSIENT TESTING ..........2-21 FAX NUMBERS ..............1-1 FEATURES ................ 2-1 FILE TRANSFER BY IEC 61850 ......... C-2 GE Multilin T60 Transformer Protection System...
  • Page 718 2-14 G.703 ............ 3-32, 3-33, 3-34, 3-37 FLEXANALOG ..............A-1 G.703 WIRE SIZE .............3-32 FLEXCURVES™ GE TYPE IAC CURVES ..........5-184 equation ..............5-185 GROUND CURRENT METERING ........6-16 Modbus registers ..........B-31, B-54 GROUND DIRECTIONAL SUPERVISION ......5-161 settings ................. 5-98 GROUND DISTANCE specifications..............
  • Page 719 ..............2-16 settings ................. 5-42 harmonics ..............2-16 specifications ............2-17, 2-18 power ................2-15 ISO-9000 REGISTRATION ..........2-22 THD ................2-16 voltage ................2-15 METERING CONVENTIONS ..........6-12 MHO DISTANCE CHARACTERISTIC ......5-147 GE Multilin T60 Transformer Protection System...
  • Page 720 ................ 5-238 settings ............... 5-221 specifications ..............2-12 specifications..............2-12 OVERFRQUENCY NEUTRAL TIME OVERCURRENT Modbus registers ............B-37 see entry for NEUTRAL TOC OVERVOLTAGE auxiliary .............. 2-12, 5-223 neutral ..............2-12, 5-221 phase ..............2-12, 5-220 T60 Transformer Protection System GE Multilin...
  • Page 721 PHASE ROTATION ............5-75 PHASE TIME OVERCURRENT REACTIVE POWER ..........2-15, 6-17 see entry for PHASE TOC REAL POWER ............2-15, 6-17 REAL TIME CLOCK Modbus registers ............B-27 settings ................. 5-42 REAR TERMINAL ASSIGNMENTS ........3-8 GE Multilin T60 Transformer Protection System...
  • Page 722 RTD INPUTS example use of ...............5-77 actual values ..............6-24 metering ................6-15 Modbus registers ..........B-20, B-32 Modbus registers ........ B-12, B-13, B-14, B-29 settings .............5-284, 5-286 settings ................5-76 specifications ..............2-16 SPECIFICATIONS ............2-10 viii T60 Transformer Protection System GE Multilin...
  • Page 723 UNINSTALL ..............10-1 Modbus registers ............B-42 UNIT NOT PROGRAMMED ........5-71, 7-7 settings ............... 5-259 UNPACKING THE RELAY ...........1-1 specifications ..............2-13 UNRETURNED MESSAGES ALARM ......... 5-69 TIME ................. 7-2 UPDATING ORDER CODE ..........7-3 GE Multilin T60 Transformer Protection System...
  • Page 724 ..............6-6 FlexLogic™ operands ..........5-129 Modbus registers ............B-63 settings ............... 5-270 ZERO SEQUENCE CORE BALANCE .........3-13 VOLTAGE BANKS ............5-74 ZERO-SEQUENCE COMPENSATION ....... 5-86, 5-87 VOLTAGE DEVIATIONS ........... 2-21 VOLTAGE ELEMENTS ........... 5-217 T60 Transformer Protection System GE Multilin...

Table of Contents