5 SETTINGS

PATH: SETTINGS
GROUPED ELEMENTS
 SPLIT PHASE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Some generators, due to physical construction, have windings that consist of multiple adjacent turns. It is therefore possible
for faults to develop between turns on the same phase (inter-turn faults). These faults are not detected by the stator differ-
ential protection, as there is no difference between the neutral and at the terminal currents. Split phase protection may be
applied to detect inter-turn faults in the case that the generator is wound with two three-phase windings, each brought sep-
arately out of the machine and connected in parallel. The currents in the two windings are compared, any difference indicat-
ing an inter-turn fault.
GE Multilin

SETTING GROUP 1(6)
SPLIT PHASE
SPLIT PHASE
FUNCTION: Disabled
SPLIT PHASE SOURCE:
SRC 1
SPLIT PHASE LOAD
SOURCE: SRC 2
SPLIT PHASE A
PICKUP: 0.200 pu
SPLIT PHASE A
OFFSET: 0.000 pu
SPLIT PHASE A SLOPE:
0.0%
SPLIT PHASE B
PICKUP: 0.200 pu
SPLIT PHASE B
OFFSET: 0.000 pu
SPLIT PHASE B SLOPE:
0.0%
SPLIT PHASE C
PICKUP: 0.200 pu
SPLIT PHASE C
OFFSET: 0.000 pu
SPLIT PHASE C SLOPE:
0.0%
SPLIT PHASE MIN
LOAD: 0.00 pu
SPLIT PHASE MODE:
Over
SPLIT PHASE DELAY:
0.000 s
SPLIT PHASE BLK:
Off
SPLIT PHASE TARGET:
Self-Reset
SPLIT PHASE EVENTS:
Disabled
G60 Generator Protection System
5.6 GROUPED ELEMENTS
5.6.11 SPLIT PHASE PROTECTION
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.020 to 1.500 pu in steps of 0.001
Range: 0.000 to 1.000 pu in steps of 0.001
Range: 0.0 to 100% in steps of 0.1
Range: 0.020 to 1.500 pu in steps of 0.001
Range: 0.000 to 1.000 pu in steps of 0.001
Range: 0.0 to 100% in steps of 0.1
Range: 0.020 to 1.500 pu in steps of 0.001
Range: 0.000 to 1.000 pu in steps of 0.001
Range: 0.0 to 100% in steps of 0.1
Range: 0.00 to 1.00 pu in steps of 0.01
Range: Over, Over-Under
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
,
Range: Self-reset, Latched
Disabled
,
Range: Enabled
Disabled
5
5-209