APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 27 of 68)
ADDR
REGISTER NAME
5898
...Repeated for FlexLogic Timer 20
58A0
...Repeated for FlexLogic Timer 21
58A8
...Repeated for FlexLogic Timer 22
58B0
...Repeated for FlexLogic Timer 23
58B8
...Repeated for FlexLogic Timer 24
58C0
...Repeated for FlexLogic Timer 25
58C8
...Repeated for FlexLogic Timer 26
58D0
...Repeated for FlexLogic Timer 27
58D8
...Repeated for FlexLogic Timer 28
58E0
...Repeated for FlexLogic Timer 29
58E8
...Repeated for FlexLogic Timer 30
58F0
...Repeated for FlexLogic Timer 31
58F8
...Repeated for FlexLogic Timer 32
Phase Time Overcurrent (Read/Write Grouped Setting)
5900
Phase Time Overcurrent 1 Function
5901
Phase Time Overcurrent 1 Signal Source
5902
Phase Time Overcurrent 1 Input
5903
Phase Time Overcurrent 1 Pickup
5904
Phase Time Overcurrent 1 Curve
5905
Phase Time Overcurrent 1 Multiplier
5906
Phase Time Overcurrent 1 Reset
5907
Phase Time Overcurrent 1 Voltage Restraint
5908
Phase TOC 1 Block For Each Phase (3 items)
590F
Phase Time Overcurrent 1 Target
5910
Phase Time Overcurrent 1 Events
5911
Reserved (3 items)
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (2 modules)
5A00
Phase Instantaneous Overcurrent 1 Function
5A01
Phase Instantaneous Overcurrent 1 Signal Source
5A02
Phase Instantaneous Overcurrent 1 Pickup
5A03
Phase Instantaneous Overcurrent 1 Delay
5A04
Phase Instantaneous Overcurrent 1 Reset Delay
5A05
Phase IOC1 Block For Each Phase (3 items)
5A0B
Phase Instantaneous Overcurrent 1 Target
5A0C
Phase Instantaneous Overcurrent 1 Events
5A0D
Reserved (6 items)
5A13
...Repeated for Phase Instantaneous Overcurrent 2
Neutral Time Overcurrent (Read/Write Grouped Setting)
5B00
Neutral Time Overcurrent 1 Function
5B01
Neutral Time Overcurrent 1 Signal Source
5B02
Neutral Time Overcurrent 1 Input
5B03
Neutral Time Overcurrent 1 Pickup
5B04
Neutral Time Overcurrent 1 Curve
5B05
Neutral Time Overcurrent 1 Multiplier
5B06
Neutral Time Overcurrent 1 Reset
5B07
Neutral Time Overcurrent 1 Block
5B09
Neutral Time Overcurrent 1 Target
5B0A
Neutral Time Overcurrent 1 Events
5B0B
Reserved (6 items)
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting)
5C00
Neutral Instantaneous Overcurrent 1 Function
5C01
Neutral Instantaneous Overcurrent 1 Signal Source
5C02
Neutral Instantaneous Overcurrent 1 Pickup
5C03
Neutral Instantaneous Overcurrent 1 Delay
GE Multilin
RANGE
0 to 1
0 to 5
0 to 1
0 to 30
0 to 16
0 to 600
0 to 1
0 to 1
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 30
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1
0 to 30
0 to 16
0 to 600
0 to 1
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 30
0 to 600
G60 Generator Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
---
1
F122
pu
0.001
F001
---
1
F103
0 (IEEE Mod Inv)
---
0.01
F001
---
1
F104
0 (Instantaneous)
---
1
F102
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F122
pu
0.001
F001
---
1
F103
0 (IEEE Mod Inv)
---
0.01
F001
---
1
F104
0 (Instantaneous)
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
DEFAULT
B
0 (Disabled)
0 (SRC 1)
0 (Phasor)
1000
100
0 (Disabled)
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Phasor)
1000
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
0