3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES
Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the follow-
ing figure.
3
The clock configuration LED status is as follows:
Flashing green — loop timing mode while receiving a valid data packet
Flashing yellow — internal mode while receiving a valid data packet
Solid red — (switch to) internal timing mode while not receiving a valid data packet
The link/activity LED status is as follows:
Flashing green — FPGA is receiving a valid data packet
Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit"
Solid red — FPGA is not receiving a valid packet or the packet received is invalid
3-42
Figure 3–46: STATUS LEDS