GE G60 Instruction Manual page 50

Ur series generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

2.2 SPECIFICATIONS
SUB-HARMONIC STATOR GROUND
Stator ground resistance pickup accuracy: ±5% of reading from 1
Total stator capacitance to ground: 200 nF to 2 μF
Sub-harmonic voltage metering accuracy: ±2% of reading or 0.2 V
2
Sub-harmonic current metering accuracy: ±2% of reading or 5 mA
Sub-harmonic element operating time: 0.6 to 1.2 s
Sub-harmonic element dropout level accuracy: 102 to 103% of
Time delay accuracy:
FIELD GROUND
Measured field ground resistance: 1 kΩ to 20 MΩ
Ground resistance accuracy:±5% of reading ±250 Ω from 1 to 500
Field winding capacitance: 1 to 10 μF
Maximum field voltage: 600 V DC rated field voltage / 1000 V
Field voltage measurement range: 15 to 800 V
Field voltage measurement accuracy: ±1 V or ±3% of reading (for
Field ground RMS current accuracy: ±5% of reading
Fault location accuracy: ±5% of reading
Field ground resistance typical operating time: 1.1 s + (1 / injection
Field ground element dropout level accuracy: 102 to 103% of
Time delay accuracy:
FIELD CURRENT
Field current measurement (dcmA) accuracy: ±0.2% of full scale
Field overcurrent and undercurrent operating time: 1 power sys-
Field current element dropout level accuracy: 102 to 103% of
Time delay accuracy: ±3% of time delay setting or ±4 ms which-
2-18
to 10 kΩ, ±10% of reading from 10 to 20
kΩ
from 0.5 to 25 V AC
from 5 to 200 mA
pickup
±3% of time delay setting or ± 4 ms,
whichever is greater
kΩ
ripple peak for single box option; 800
V DC rated field voltage / 2000 V ripple
peak for external resistor box option
GPM-F-L); ±1 V or ±5% of reading (for
GPM-F-H)
frequency)
pickup
±3% of time delay setting or ±4ms,
whichever is greater
tem cycle
pickup for undercurrent and 97 to 98% of
pickup for overcurrent
ever is greater
G60 Generator Protection System
2 PRODUCT DESCRIPTION
UNDERFREQUENCY
Minimum signal:
0.10 to 1.25 pu in steps of 0.01
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
pickup + 0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by
±0.5 cycles.
OVERFREQUENCY
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
pickup – 0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by
±0.5 cycles.
RATE OF CHANGE OF FREQUENCY
df/dt trend:
increasing, decreasing, bi-directional
df/dt pickup level:
0.10 to 15.00 Hz/s in steps of 0.01
df/dt dropout level:
96% of pickup
df/dt level accuracy:
80 mHz/s or 3.5%, whichever is greater
Overvoltage supv.:
0.100 to 3.000 pu in steps of 0.001
Overcurrent supv.:
0.000 to 30.000 pu in steps of 0.001
Pickup delay:
0 to 65.535 s in steps of 0.001
Reset delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
95% settling time for df/dt: <24 cycles
Operate time:
typically 9.5 cycles at 2 × pickup
typically 8.5 cycles at 3 × pickup
typically 6.5 cycles at 5 × pickup
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by
±0.5 cycles.
TURBINE FREQUENCY OUT-OF-BAND (OOB)
ACCUMULATED OPERATING TIME
Frequency OOB accumulation: 7 sets; 20 to 70 Hz in steps of 0.01
Frequency OOB accumulation pickup: 1 to 65536 s in steps of 1
Frequency OOB accumulator preset: 1 to 65536 s in steps of 1
Level accuracy:
±0.01 Hz
Minimum volt/amp supervision: 0.1 to 1.25 pu of V_1 or I_1
Timer accuracy of accumulation: ±1% or 1 second, whichever is
greater