GE G60 Instruction Manual page 413

Ur series generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5 SETTINGS
The field ground fault detector function logic is shown below.
Figure 5–135: FIELD GROUND FAULT DETECTOR FUNCTION LOGIC
c) FIELD CURRENT

PATH: SETTINGS
GROUPED ELEMENTS
 FIELD
 CURRENT
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The following settings are available for the field current fault detector function.
FIELD CURRENT ORIGIN: This setting selects the dcmA input to be used for the field current protection element. A
dcmA input can be selected from up to 24 possible inputs, depending on the number of installed transducer modules.
GE Multilin
SETTING GROUP 1(6)
FIELD GROUND PROTECTION
FIELD CURRENT
FUNCTION: Disabled
FIELD CURRENT ORIGIN:
Off
FIELD OVER CURRENT
PICKUP: 0.80 pu
FIELD OVER CURRENT
DELAY:
1.00 s
FIELD UNDER CURRENT
PICKUP: 0.20 pu
FIELD UNDER CURRENT
DELAY:
1.00 s
FIELD CURRENT BLK:
Off
FIELD CURRENT
TARGET: Self-reset
FIELD CURRENT
EVENTS: Disabled
G60 Generator Protection System
5.6 GROUPED ELEMENTS

FIELD CURRENT
Range: Disabled, Enabled
Range: Off, dcmA 1, dcmA 2,..., dcmA 24, TRD1,
TRD2,..., TRD8
Range: 0.05 to 1.00 pu in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.05 to 1.00 pu in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5
5-253

Advertisement

Table of Contents
loading

Table of Contents