7.2 TARGETS
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed module
(for example, F8L).
IEC 61850 DATA SET:
LLN0 GOOSE# Error
Latched target message: No.
Description of problem: A data item in a configurable GOOSE data set is not supported by the G60 order code.
How often the test is performed: On power up
What to do: Verify that all the items in the GOOSE data set are supported by the G60. The EnerVista UR Setup soft-
ware will list the valid items. An IEC61850 client will also show which nodes are available for the G60.
IEC 61850 DATA SET:
LLN0 BR# Error
Latched target message: No.
Description of problem: A data item in a configurable report data set is not supported by the G60 order code.
How often the test is performed: On power up
What to do: Verify that all the items in the configurable report data set are supported by the G60. The EnerVista UR
Setup software will list the valid items. An IEC61850 client will also show which nodes are available for the G60.
MAINTENANCE ALERT:
Replace Battery
Latched target message: Yes.
Description of problem: The battery is not functioning.
How often the test is performed: The battery is monitored every five seconds. The error message displays after 60 sec-
onds if the problem persists
What to do: Replace the battery as outlined in the Maintenance chapter.
MAINTENANCE ALERT:
Direct I/O Ring Break
7
Latched target message: No.
Description of problem: Direct input and output settings are configured for a ring, but the connection is not in a ring.
How often the test is performed: Every second
What to do: Check direct input and output configuration and wiring.
MAINTENANCE ALERT:
ENET PORT # OFFLINE
Latched target message: No.
Description of problem: The Ethernet connection has failed for the specified port.
How often the test is performed: Every five seconds.
What to do: Check the Ethernet port connection on the switch.
MAINTENANCE ALERT:
**Bad IRIG-B Signal**
Latched target message: No.
7-8
.
.
.
.
G60 Generator Protection System
7 COMMANDS AND TARGETS