3 HARDWARE
Figure 3–71: REAR VIEW OF GPM-S-G MODULE SHOWING TERMINAL BLOCKS
The following tables outline the pin assignments for the stator ground 20 Hz generator module. Two contact inputs are pro-
vided. Upon closure of any one of the contact inputs, 20 Hz injection stops.
Table 3–14: GPM-S-G PIN ASSIGNMENTS FOR CONNECTOR A
PIN
LABEL
DEFINITION
1
A1
Contact input 1
2
A2
Contact input 2
3
A3
Alarm relay NC (normally closed)
4
A4
Not used
5
A5
Output 1
6
A6
Contact input common
7
A7
Alarm relay NO (normally open)
8
A8
Alarm relay common
9
A9
Not used
10
A10
Output 2
Table 3–15: GPM-S-G PIN ASSIGNMENTS FOR CONNECTOR B
PIN
LABEL
DEFINITION
1
B1
Not used
2
B2
Not used
3
B3
Not used
4
B4
Not used
5
B5
Not used
6
B6
Not used
7
B7
Not used
8
B8
Ground
9
B9
Power neutral / DC negative
10
B10
Power line / DC positive
There are two connectors on the stator ground protection band pass filter module, as shown in the following figure.
GE Multilin
3.4 FIELD AND STATOR GROUND MODULES
G60 Generator Protection System
3
3-63