Field And Stator Ground Modules - GE G60 Instruction Manual

Ur series generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
GPM-F MODULE CONTACT INPUTS
Internal wetting:
24 V DC
Input comparator threshold: 6 V DC
External contact:
dry
Current when energized: < 10 mA
Debounce time:
10 ms
GPM-F MODULE CRITICAL FAILURE RELAY
Make and carry:
30 A for 0.2 s as per ANSI C37.90
Continuous carry:
8 A
Break (DC inductive, L/R = 40 ms): 1 A at 24 V, 0.5 A at 48 V,
0.3 A at 125 V, 0.2 A at 250 V
Operate time:
< 8 ms
Contact material:
silver alloy
GPM-F MODULE POWER SUPPLY
GPM-F-L:
100 to 240V AC at 50/60Hz and 10 VA
125 to 250V DC at 10W
GPM-F-HM:
100 to 240V AC at 50/60Hz and 10 VA
125 to 250V DC at 10W
GPM-S-G MODULE CONTACT INPUTS
Internal wetting:
24 V DC
Input comparator threshold: 6 V DC
External contact:
dry
Current when energized: < 10 mA
Debounce time:
10 ms
GE Multilin

2.2.8 FIELD AND STATOR GROUND MODULES

GPM-S-G MODULE POWER SUPPLY
Power supply:
Output ratings:
GPM-S-B MODULE
Power rating:
Input ratings:
GPM-F-R MODULE
Current limiting resistor: 12.5 Ω × 4
Voltage divider resistor: 5 Ω × 3
STATOR GROUND PROTECTION CT
Part number:
Turns ratio:
Rating factor (RF):
Frequency:
Voltage insulation:
Basic impulse level (BIL): 10 kV
G60 Generator Protection System
2.2 SPECIFICATIONS
100 to 240 V AC at 50/60 Hz and 110VA
125 to 250 V DC at 110W
26 V rectangular at 20 Hz, load capabil-
ity 80 VA
80VA
maximum 30 V rectangular at 20 Hz
204-SD-43737
400:5A
3.0
20 Hz
600 V
2
2-25