5 SETTINGS
The volts/hertz inverse C curves are shown below.
Figure 5–121: VOLTS-PER-HERTZ CURVES, INVERSE CURVE C

PATH: SETTINGS
GROUPED ELEMENTS
 LOSS OF
 EXCITATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
Multiples of volts per hertz pickup

SETTING GROUP 1(6)

LOSS OF EXCITATION

LOSS OF EXCITATION
FUNCTION: Disabled
LOSS OF EXCITATION
SOURCE: SRC 1
LOSS OF EXCITATION
CENTER 1: 10.00 ohm
LOSS OF EXCITATION
RADIUS 1: 8.00 ohm
EXCITATION V SUPV 1:
Enabled
LOSS OF EXCITATION
PKP DELAY1: 0.050 s
LOSS OF EXCITATION
CENTER 2: 12.00 ohm
LOSS OF EXCITATION
RADIUS 2: 10.00 ohm
LOSS OF EXCITATION
V SUPV 2: Enabled
LOSS OF EXCITATION
PKP DELAY2: 0.500 s
LOSS OF EXCITATION
UV SUPV: 0.700 pu
LOSS OF EXCIT BLK:
Off
G60 Generator Protection System
5.6 GROUPED ELEMENTS
Time
delay
setting
830740A1.CDR
5.6.14 LOSS OF EXCITATION
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.01
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.01
Range: 0.000 to 1.250 pu in steps of 0.001
Range: FlexLogic operand
5
5-233