5.2 PRODUCT SETUP
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. Refer to the Introduction to FlexLogic section in this chapter for the full range
of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
 ANALOG INPUT / MME
 POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point are ignored.
NOTE
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the G60 is restarted.
NOTE
5
k) IEC 61850 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 IEC 61850 PROTOCOL
5-40

COMMUNICATIONS
Point:
Off
Point:
MESSAGE
Off
Point:
MESSAGE
Off

COMMUNICATIONS
 GSSE / GOOSE
 CONFIGURATION
 SERVER
MESSAGE
 CONFIGURATION
 IEC 61850 LOGICAL
MESSAGE
 NODE NAME PREFIXES
 MMXU DEADBANDS
MESSAGE
 GGIO1 STATUS
MESSAGE
 CONFIGURATION
 GGIO2 CONTROL
MESSAGE
 CONFIGURATION
 GGIO4 ANALOG
MESSAGE
 CONFIGURATION
 GGIO5 UINTEGER
MESSAGE
 CONFIGURATION
 REPORT CONTROL
MESSAGE
 CONFIGURATION
 XCBR
MESSAGE
 CONFIGURATION
 XSWI
MESSAGE
 CONFIGURATION
G60 Generator Protection System

DNP / IEC104 POINT LISTS
Range: any FlexAnalog parameter
0
Range: any FlexAnalog parameter
1
Range: any FlexAnalog parameter
255
