Overcurrent; Loss Of Bus Voltage; Settings Example; Overview - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

CHAPTER 8: APPLICATION OF SETTINGS

8.3.5 Overcurrent

Phase and neutral time overcurrent elements can be applied with normal settings without encountering false operations
due to inrush currents. The desirable minimum pickup is 135% of nominal phase current for grounded wye banks or 125%
for ungrounded banks. Set the instantaneous elements (if used) high to override inrush or outrush transients.
For effectively grounded systems with grounded wye capacitor banks, the high-frequency outrush current into an external
ground fault does not normally operate the 51N ground element. The unbalanced capacitor bank load current caused by
an external ground fault can be sufficient to cause the element to pick up and trip the capacitor bank if the 51N is set too
low. To prevent this inadvertent tripping, the trip of the 51N element is normally set above the capacitor phase current.

8.3.6 Loss of bus voltage

In some cases, it is necessary to trip a shunt capacitor bank if the supply bus voltage is lost. Two conditions that need to be
considered are:
Re-energizing a bank with a trapped charge
Energizing a capacitor bank without parallel load through a previously unenergized transformer
The undervoltage element (ANSI device 27B) detects loss of system voltage and trip the capacitor bank after a time delay.
This delay prevents tripping of the bank for system faults external to the bank. Set the undervoltage element so that the
element does not operate for voltages that require the capacitor bank to remain in service. Because this tripping is also not
due to a fault within the capacitor bank (like system overvoltage tripping), the bank is not locked out.

8.4 Settings example

8.4.1 Overview

Consider protection of a capacitor bank with the following characteristics:
V
= 138 kV fuseless
LL
Q
= 21 Mvar
B
Two parallel strings (S = 2) in each phase with N = 7 capacitor units rated Q
Each capacitor unit consisting of n = 6 series capacitors
The figure shows details. Phase capacitors are connected to ground through a neutral capacitor rated Q
= 0.825 kV.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
SETTINGS EXAMPLE
= 500 kvar, V
= 11.62 kV
C
C
= 167 kvar, V
CN
CN
8
8-11

Advertisement

Table of Contents
loading

Table of Contents