Loss Of Communications - GE 850 Instruction Manual

Feeder protection system
Hide thumbs Also See for 850:
Table of Contents

Advertisement

CHAPTER 7: MONITORING

Loss of Communications

850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Introduction
This section covers the functionality of the 8 Series Loss of Communications element.
The 8 Series device monitors activity on an interface via the configured protocol for this
interface. The communications status is set for each protocol.
If communications is lost, the enabled interface will issue a "Loss of Comms" event and
operate a combination of output relays / states.
Path:
Setpoints > Monitoring > Loss of Comms
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
INTERFACE
Range: Serial, Serial + Ethernet, Ethernet, All
Default: Serial
Only the protocols associated with the selected interface are shown in this screen as
options. For example, if "Ethernet" is selected, select the Ethernet protocols to monitor.
The Ethernet protocols selection is defined as EthernetProtocolBitmask bitmasks.
MODBUS
Range: Off, On
Default: Off
PICKUP DELAY
Range: 0 to 600 s in steps of 1
Default: 2 s
OUTPUT RELAY X
For details see
Common
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Latched
Setpoints.
LOSS OF COMMUNICATIONS
7–51

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents