Model 3100 accessory
Relays module
UL and CSA approvals
ATEX approvals
Model 3500/3700 liquid flow performance
(1)(2)
Mass flow accuracy
(1) (2)
Volume flow accuracy
(2)
Repeatability
(1) Stated flow accuracy includes the combined effects of repeatability, linearity, and hysteresis.
(2) For the details of flow accuracy and repeatability specifications, refer to the product data sheet for each sensor family.
®
10
Micro Motion
Series 3000 Transmitters and Discrete Controllers
Three relays
Solid state, SPST
Rated at 24–250 VAC, 40 mA to 5 A; or 0–70 VDC, 5 A
Energized by discrete outputs
NEMA 4X (IP65) enclosure (optional)
Class I, Div. 2, Groups A, B, C, and D
Suitable for installation in Zone 2, when properly installed in a suitable enclosure, complying with
ATEX Directive (94/9/EC) for Group II, Category 3G, according to CENELEC standard EN 50021
(1998) and marked as:
EEx n V II T4
KEMA 97 ATEX4940X
Ambient temperature –20 to +60 °C (–4 to +140 °F)
Additional installation-specific requirements are described in detail in the Series 3000 instruction
manual.
Sensor model
®
ELITE
F-Series
H-Series
T-Series
R-Series
ELITE
F-Series
H-Series
T-Series
R-Series
ELITE
F-Series
H-Series
T-Series
R-Series
±0.05% of rate
±0.10% of rate
±0.10% of rate
±0.15% of rate
±0.50% of rate
±0.05% of rate
±0.15% of rate
±0.15% of rate
±0.25% of rate
±0.50% of rate
±0.025% of rate
±0.05% of rate
±0.05% of rate
±0.05% of rate
±0.25% of rate