JUMO 709061/8-01-032 Operating Manual page 85

Tya 201 single-phase thyristor power controller
Table of Contents

Advertisement

0(4)...20mA
0(4)...20mA
Device 1
Output level 20%
Device
2
Output level 60%
Sum of all
Mains currents
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Device 1
Relay
Optocoupler
C
Ö
P
E
S
Semiconductor-
fuse
U2
U1
N/L2
V
L1
The two power controllers switch on at different times. Starting from the
dashed lines, the dispersion of energy takes place symmetrically to the left
and right (see arrows). For as long as the total output level of the two devices
is below 100 %, two device currents in a single phase are prevented from
overlapping. The next power level in the network is not started until the total
output level exceeds 100 %.
A
If one power controller performs a restart when the configuration
level is exited, it no longer operates synchronously with the others.
All power controllers have to be switched on again simultaneously
via a joint main switch!
I
Thy1
I
Thy2
I
mains
0 ms
250 ms
6 Special device functions
Device 2
Relay
Optocoupler
C
Ö
P
E
S
Semiconductor-
fuse
U2
U1
N/L2
V
L1
I
1 (Device2)
I
1 (Device1)
500 ms
750 ms
L1
L2 L3
N
PE
t
t
t
1 s
83