Advertisement

4 Operation

4.2 Operating level

H
Editing a pa-
rameter

4.2.1 Device data

50
All parameters for the maximum device extension level are listed in the fol-
lowing tables. Depending on the order details (see nameplate or device infor-
mation) or the current configuration, parameters that are not required are hid-
den.
Here you will find the parameters that can be modified during ongoing oper-
ation.
They can be accessed without a password per default, but can also be pro-
tected with a 4-digit code if necessary.
v Chapter 5.1.12 "Changing codes"
During ongoing operation, the power controller can be adapted to the plant
and optimized.
h In the measured value overview, press the
h Select the operating level and press
The changes are effective immediately.
Once the correct setting (e.g. for display contrast) has been found, the param-
eter can be stored by pressing
If you do not wish to apply the value, the entry can be canceled by pressing
.
Value range
deutsch
english
francais
National language4
0...50...100 %
0000 to 1440 min
k
/ bold = default setting
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
.
Description
German (deutsch), English, and French (francais) are perma-
nently stored in the device
1 additional national language can be subsequently loaded via
Setup.
50 % is set per default.
0000 minutes are set per default,
which means the display is not switched off.