Cycle Time; Min. On Period; Α Start; Α Start Angle - JUMO 709061/8-01-032 Operating Manual

Tya 201 single-phase thyristor power controller
Table of Contents

Advertisement

Cycle time

Min. ON period

α start
α start angle

Soft start

V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Value / settings
Fixed (500 ms)
(For slow heating ele-
ments)
Fastest possible
(For quick-response
heating elements)
None
3 full sine waves
No
Yes
0 to 75 to 90° el
No
k
/ bold = default setting
Description
Note:
This setting is only available in burst-firing operation mode.
For example, for a fixed period of 500 ms, 5 sine waves are
switched on and 20 switched off at an output level of 20 %.
u
5
The cycle time is variable with this setting. At the required out-
put level, the device attempts to find the shortest possible cy-
cle time for full sine waves. At an output level of 20 %, this re-
lates to one sine wave ON and four sine waves OFF.
u
1
4
100ms
Dependent on the cycle time setting.
At least three full sine waves are always let through.
At an output level of 50 % and with the fastest possible cycle
time,
3 sine waves are switched on and 3 switched off.
u
Note:
Particularly suitable for the control of transformer loads
Note:
This setting is available in continuous burst-firing operation
mode and in logic operation.
No: for resistive load
Yes: for transformer loads
If set to "Yes", the first half-wave of each pulse group is cut
with the set phase control angle α.
u
a
Phase control angle for α start
This setting determines the starting behavior of the power
controller after power ON and is deactivated ex works.
5 Configuration
20
500ms
a
t
t
t
t
59