1.5 Standards, approvals, and conformity

V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Device properties are inspected on the basis of the Low Voltage Directive DIN
EN 50178.
The EMC Directive is inspected on the basis of DIN EN 61326-1.
Electrical connection
Protection type IP20 built-in devic-
es
Climatic ambient conditions
Air temperature and rel. humidity
Storage temperature class 1K5
Operating conditions
Pollution degree
Overvoltage category
Test voltages
Residual current circuit breaker
Electromagnetic compatibility
Interference emission
Interference immunity
Mechanical tests:
Vibration test 3M2
Toppling test class 2M1
Labels, identification marking
Approvals
Standard
UL 508 (Category NRNT), pollution degree 2
C22.2 NO. 14-10 Industrial Control Equip-
ment (Category NRNT7)
UL 508 (Category NRNT)
C22.2 NO. 14-10 Industrial Control Equip-
ment (Category NRNT7)
Can be used for current circuits with a short-circuit current capacity of
≤ 100 kA (the admissible mains voltage must correspond to the nominal voltage of
the thyristor controller).
For plant protection, a fuse up to class RK5 may be used.
CE conformi-
Low Voltage Directives 2006/95/EC
ty
Marking Directives 93/68/EEC
EMC Directives 2004/108/EC
Conformity
RoHS
Standard
DIN VDE 0100
DIN EN 60529
Class 3K3
DIN EN 60721-3-3
DIN EN 60721-3-1
DIN EN 50178
2
III
DIN EN 50178
DIN EN 50178
DIN EN 61326-1
Class A- For industrial applications only
Industrial requirements
DIN EN 60068-2-6, DIN EN 60721-3-3
DIN EN 60068-2-31, DIN EN 60721-3-2
DIN EN 50178, DIN EN 61010-1
Standard
2002/95/EC
1 Introduction
Type
709061/X-XX-020-...
Load current 20 A
709061/X-XX-032...
709061/X-XX-050...
709061/X-XX-100...
709061/X-XX-150...
709061/X-XX-200...
709061/X-XX-250...
Load
current
32 to 250 A