5 Configuration
5.1.6
Digital inputs
Toggling the oper-
ating mode to
phase-angle con-
trol
External toggling of
setpoint specifica-
tion
Setpoint specifica-
tion when toggling
Value when tog-
gling
68
There are 2 digital inputs and one additional digital input for firing pulse inhibit
available, to which a potential-free contact can be connected.
The following functions can be triggered with digital input 1 and 2:
h
Switch to the configuration level
Value / settings
Switched off
Digital input1
Digital input2
Ext. digital input1
Ext. digital input2
Switched off
Digital input1
Digital input2
Ext. digital input1
Ext. digital input2
Voltage input
Current input
Value, adjustable
0% to 100 %
k
/ bold = default setting
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
r
Binary inputs using the
Description
Note:
The toggling to phase-angle operation mode is only possible if
r
r
Power controller
Operating mode
has been selected in the configuration level.
No toggling
Toggling is controlled by digital input1
Toggling is controlled by digital input2
Toggling is controlled via an interface
Toggling is controlled via an interface
No external toggling of setpoint specification
Toggling is controlled by digital input1
Toggling is controlled by digital input2
Toggling is controlled via an interface
Toggling is controlled via an interface
Selects the source that is used to specify the setpoint value
when external toggling of the setpoint specification is activat-
ed.
Note:
The only analog inputs that are available here are those that
have not yet been populated by a setpoint specification, for
example.
Note:
This parameter is available only if "Value, adjustable" is se-
lected for setpoint specification when toggling.
key
r
Burst firing mode