Analog Output; Signal Type, Actual Value Output; Value To Be Output; Signal Range Start Value - JUMO 709061/8-01-032 Operating Manual

Tya 201 single-phase thyristor power controller
Table of Contents

Advertisement

5.1.8

Analog output

Signal type, actual
value output

Value to be output

Signal range start
value
Signal range end
value
5.1.9

RS422/485

Baud rate

Data format

Device address

Min. response time 0 to 500ms
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
The actual value output is an analog output at which different internal values
can be output as a standard signal.
Value / settings
Switched off
0 to 20 mA
4 to 20 mA
0 to 10 V
2 to 10 V
0 to 5 V
1 to 5 V
Load voltage
2
Load voltage
Load current
2
Load current
Power (in W)
Power (in kW)
Resistance
Mains voltage
Device temperature
Setpoint value
0 to 9999.9
0 to 9999.9
k
/ bold = default setting
Interface parameters for RS422/485 (see interface description B709061.2)
Value / settings
9600
19200
38400
8-1-none
8-1-odd
8-1-even
8-2-none
1 to 255
k
/ bold = default setting
Description
This setting specifies the standard signal that should be out-
put at the actual value output.
The actual value output does not issue a signal.
The actual value output outputs the "Value to be output" in the
form of a current signal.
The actual value output outputs the "Value to be output" in the
form of a voltage signal.
This setting specifies the value that should be output at the
actual value output.
Example:
The load voltage can vary between 0 and 500 V depending on
the device type.
As the default setting for the signal range is 0 to 9999.9, the
end value must be adjusted to 500.0 to make use of the full
signal range.
The following must be observed for master-slave switching:
These measured values are determined in the master branch.
Exception:
When selecting the power (in W or kW), the three-phase power
is output at the actual value output.
Note:
2
Load voltage
= load voltage squared
Lower limit for the "Value to be output"
Upper limit for the "Value to be output"
Description
Data bits-stop bits-parity check
5 Configuration
73

Hide quick links:

Advertisement

Table of Contents
loading