Operating mode

(Is displayed in the
info line in the mea-
sured value over-
view level)
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Value / settings
Burst-firing
mode
Phase-angle
control
Half-wave control
k
/ bold = default setting
Description
- For slow control loops
- For free-running economy circuit
- Low EMC interference through zero-voltage switching
- No reactive power is generated
u
- For fast control loops,
such as lighting controls
- No flickering
u
a
Note:
Subordinate control loop cannot be modified!
The half-wave control operating mode is only compatible with
single-phase power controller operation. It is a special type of
phase-angle operation mode used, for example, for vibrating
magnets. In half-wave control, one thyristor branch remains
permanently locked so that only the positive half-wave is al-
lowed to pass through.
The specified setpoint value is converted to a phase control
angle of 180 °el. to 0 °el.
In this operating mode, neither load voltage nor load current
can be measured, which makes a subordinate control loop im-
possible.