Soft Start Type; Soft Start Duration - JUMO 709061/8-01-032 Operating Manual

Tya 201 single-phase thyristor power controller
Table of Contents

Advertisement

5 Configuration

Soft start type

Soft start duration

60
Value / settings
Yes
With phase-angle
control
With burst firing
1 to 65535 s
k
/ bold = default setting
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Description
"Yes" means that a soft start with phase-angle control or
burst-firing is performed after power ON.
This parameter only appears if soft start is set to "Yes".
Soft start type "With phase-angle control" is available in
phase-angle operation and in burst-firing operation.
Phase-angle operation:
Starting from 180 °, the phase control angle α is steadily re-
duced until the correct phase angle for the default setpoint
value is reached.
Burst-firing operation:
Starting from 180°, the phase control angle α is steadily re-
duced until a full wave has passed through.
This ends the soft start and the device switches to burst-firing
operation.
u
Softstartzeit
Note: If the output level is reduced to 0 % for longer than 8
seconds, a soft start is initiated again as soon as the output
level is increased once more.
If current limiting is activated during the soft start phase, the
duration of the soft start is extended because the phase con-
trol angle cannot be reduced further during current limiting.
This setting is available in burst-firing operation mode with a
fixed cycle time and with the fastest possible cycle time.
During the soft start time, the ON/OFF ratio is
increased from 0 to a maximum of 100 %.
u
Specifies the duration of the soft start.
Note:
Due to the system, the soft start duration is at least 4 s when
current limiting is switched on, even if a shorter time is config-
ured as the soft start duration.
Cycle time
t
t