5 Configuration
5.1.3

Analog inputs

Current measuring
range
Current measuring
range, start
Current measuring
range, end
Voltage measuring
range
Voltage measuring
range, start
Voltage measuring
range, end
62
The power controller has a voltage input and a current input.
These inputs (setpoint specification) specify the output to be provided by the
power controller at the load output.
In most cases, this signal is sent as a standard signal from an electronic con-
troller or PLC and is adjusted with these settings.
Value / settings
0 to 20 mA
4 to 20 mA
1
Customer-specific
0 to 20 mA
0 to 20 mA
0 to 10 V
2 to 10 V
0 to 5 V
1 to 5 V
1
Customer-specific
0 to 10 V
0 to 10 V
k
/ bold = default setting
1.
Inverting analog inputs:
If, for example, the current measuring range start is set to 20 mA and the current measuring range end
is set to 0 mA, the power controller is switched off at 20 mA and switched on at 0 mA.
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Description
This setting specifies which current standard signal is con-
nected.
v Chapter 3.3 "Connection diagram"
Note: This parameter only appears if "Customer specific" is
set for the current measuring range (see above)!
Note: This parameter only appears if "Customer specific" is
set for the current measuring range (see above)!
This setting specifies which voltage standard signal is con-
nected.
v Chapter 3.3 "Connection diagram"
Note: This parameter only appears if "Customer specific" is
set for the voltage measuring range (see above)!
Note: This parameter only appears if "Customer specific" is
set for the voltage measuring range (see above)!