Cable Lugs And Plug-In Screw Terminals As Of 32 A - JUMO 709061/8-01-032 Operating Manual

Tya 201 single-phase thyristor power controller
Table of Contents

Advertisement

3 Electrical connection
Terminal
X2_1 and X2_2
X3
U2, N/L2, V, L1, U1
For applications according to UL, only 60 °C or 60 °C / 75 °C copper conductors may be used!
Ground terminal PE M4 setscrew with hexagon

3.2 Cable lugs and plug-in screw terminals as of 32 A

Tools
28
Version
Slotted screws, blade width 2 mm
Slotted screws, blade width 3 mm
Slotted screws, blade width 5 mm
nut
Width across flats 7 mm
- Flat-blade screwdriver, blade width 2, 3, and 5 mm
- Ring or open-end wrench, width across flats 7, 10, 13 mm
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Conductor
cross
section
2
0.2-1.5 mm
2
0.5-2.5 mm
2
0.5-6 mm
Cable lug with
hole: 4 mm
Maximum
tightening
torque
0.25 Nm
0.5 Nm
0.6 Nm
3 Nm

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents