Power Controller; Setpoint Value Configuration - JUMO 709061/8-01-032 Operating Manual

Tya 201 single-phase thyristor power controller
Table of Contents

Advertisement

4.2.2 Power controller

Current load current
Current resistance

4.2.3 Setpoint value configuration

Current load voltage
and current
Current load voltage
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Value range
0 to 75 to 90° el
10 % to max. load
current for the de-
vice type +10 %
0 to 999.99 Ω
k
/ bold = default setting
Value range
0 to 180 °el
0 to U
to 1.15 U
nom.
nom.
of the load voltage,
0 to P
to 1.15 P
nom.
nom.
of the power
0 to I
nom.
of the max. load current
0 to 100 %
of the output level
Description
75° el is set per default.
If "α start" is set to "No" in the configuration, this window is
not displayed and α start is set to 0° el.
Current limiting:
It is possible to modify the current limit value in phase-
angle operation mode during operation.
This window is not displayed if "Current limiting" is set to
"No" in the configuration.
Resistance limitation:
Indirect temperature limit for a heating element with a
positive temperature coefficient.
Description
In logic operation, the phase angle of each sine wave can
be varied.
This means that excessive electrical impact stresses on
the load can be prevented.
In the case of continuous thyristor control via the analog
input, the maximum actuating variable at the measuring
range end (e.g. 20 mA) can be varied during operation.
The displayed value depends on the "Subordinate control
loop" setting:
2
U
and U: display in V (example: 0 to 230 to 264.5 V)
P:
display in W (example: 0 to 4600 to 5290 W)
2
I
and I:
display in A (example: 0 to 20 A)
None:
display in % (example: 0 to 100 %)
4 Operation
51