Environmental Conditions - JUMO 709061/8-01-032 Operating Manual

Tya 201 single-phase thyristor power controller
Table of Contents

Advertisement

2 Mounting
Check
Load connec-
tion
Phasing
Control inputs

2.1.1 Environmental conditions

Incorrect use
Mounting site
Climatic
conditions
Avoid additional
sources of heat
Power loss
16
h That the data on the nameplate (rated load voltage, load current) corre-
sponds to the data for the plant.
h That the rotary electrical field has clockwise phasing if the economy circuit
configuration is used.
h That the configuration of the analog inputs, for example, corresponds to the
wiring.
h The analog input for the default setpoint specification in "Master-slave op-
eration" only needs to be connected to the master. The slave receives its in-
formation via the 1:1 patch cable.
However, the slave power controller can be disconnected separately by
means of its own inhibit input.
h The electronic switch (2 anti-parallel thyristors) is located between the U1
and U2 terminals.
h Where possible, load cables and cables for control inputs should be routed
so that they are isolated.
h Connect the mains voltage - thyristor power controller - load in accordance
with the connection diagram and check.
The voltage supply of the control electronics and the load voltage
must have the same phase.
The terminal strips for control connections (inputs and outputs) have been laid
out for safe isolation from the mains voltage (SELV). To prevent the safe isola-
tion from being impaired, ensure that all connected current circuits are also
safely isolated. The required auxiliary supplies must be SELV voltages.
The device is not suitable for installation in potentially explosive areas.
The power controller must be installed in a fire-proof control cabinet.
The cabinet should be vibration-free, free from aggressive media, and free
from dust to prevent the ventilation slots from becoming blocked.
- Relative humidity: 5 to 85 %, no condensation (3K3 according to EN 60721)
- Ambient temperature range: 0 to 45 °C (3K3 according to EN 60721-3-3)
- Storage temperature range: -30 to +70 °C class 1K5
- Ensure that the ambient temperature at the installation site is not increased
by other sources of heat or heat accumulation.
- Do not mount the power controller too close to the heating process (fur-
nace)
- Avoid direct sunlight.
Occurs as waste heat on the power controller's heat sink and must be dissi-
pated at the mounting site (e.g. in the control cabinet) in accordance with the
climatic conditions.
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]