Tya 201 single-phase thyristor power controller
Table of Contents

Advertisement

8 Error messages and alarms
Error message
Limiting active
high temperature
Mains voltage is
too low
Mains voltage is
too high
Temporary
drop in mains volt-
age
Master-slave
rotary field error
Master-slave
wiring is wrong.
Rotary field detec-
tion failed
Wire break
Current input
Wire break
Voltage input
Malfunction
Bus error
Master-slave
Error in comm.
Data cable
faulty
Synchronization
failed
102
Cause
Device temperature is higher than 105 °C.
Device is too hot, output level is reduced!
(Limited power due to excess temperature)
Mains voltage is not within specified toler-
ance range
v Chapter 10.1 "Voltage supply, load
current"
Mains voltage is not within specified toler-
ance range
Chapter 10.1 "Voltage supply, load cur-
rent"
Dangerous temporary equal proportion for
transformer loads has been detected.
v Chapter 5.1.5 "Monitoring"
Counterclockwise rotary field has been de-
tected
Wiring fault has been detected
Rotary field detection not possible
Input current too small for the selected
measuring range.
Input voltage too small for the selected
measuring range.
No connection to the Profibus master
Error in the data transfer between master
and slave
Communication between master and slave
interrupted.
Slave device switched off or communica-
tion between master and slave interrupted
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Remedy
- Ensure adequate ventilation or
provide for additional cooling
- Reduce load current
- Use power controller with high-
er maximum load current
Check nominal voltage of the device
type
v Chapter 1.3 "Order details"
Check nominal voltage of the device
type
Chapter 1.3 "Order details"
Ensure stable mains supply.
v Chapter 3.4.6 "Master-slave 3-
phase current economy circuit
for resistive loads in star/delta
connections,
or
loads (resistive-inductive)"
- Check connection
v Chapter 3.3 "Connection dia-
gram"
- Eliminate mains disturbances
- Check wiring for wire breaks and
reverse polarity.
- Check upstream devices (con-
trollers)
- Check wiring for wire breaks and
reverse polarity.
- Check upstream devices (con-
trollers)
Check wiring and master device (PLC).
Is the 1:1 patch cable plug connected
correctly?
Check the 1:1 patch cable and replace,
if necessary
Check plug connection of 1:1 patch
cable or voltage supply
transformer