9 What to do, if ...
What is happening?
Power controller is not
producing full power
even though the setpoint
value is set to 100 %
112
Cause / remedy
- Current limiting active
h Check settings
- Half-wave control set
(half power)
h Change to burst-firing operation mode or
phase-angle control
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Info
v See "Current limit-
ing" on page 61.
v See
"Operating
mode"
on
page 57.