Voltage
High
TABLE 61
Low Voltage 1 Phase PDUs for Oracle Exadata Storage Expansion Rack
High Voltage
kVA Size
Marketing part number
Manufacturing part number
Phase
Voltage
Amps per PDU
Outlets
Number of inputs
Input current
Data center receptacle
Outlet groups per PDU
Usable PDU power cord length
Low Voltage 3 Phase PDUs for Oracle Exadata Storage Expansion Rack
TABLE 62
High Voltage
kVA Size
Marketing part number
Manufacturing part number
Phase
Voltage
Amps per PDU
Outlets
Number of inputs
Input current
Data center receptacle
Outlet groups per PDU
Phases
Reference
3
Table 64, "High Voltage 3 Phase PDUs for Oracle Exadata Storage Expansion Rack," on
page 292
One Phase
15 kVA
N/A
N/A
1 ph
200 to 240 VAC
72 A (3 inputs x 24 A)
42 C13
6 C19
3 inputs
24 A max. per input
NEMA 30A/250 VAC 2-pole/3-wire L6-30P
6
2 m (6.6 feet)
Three Phase
14.4 kVA
N/A
N/A
3 ph
190 to 220 VAC
69 A (3 inputs x 23 A)
42 C13
6 C19
2 inputs x 60 A, 3 ph
40 A max. per phase
IEC 60309 60A 4-pin 250 VAC 3 ph IP 67
6
Preparing for Installation
Comments
PDU power cords are 4 m long (13 feet), but
sections are used for internal routing in the
rack.
Comments
Connecting Expansion Racks
291