Environmental Requirements; Heat Dissipation And Airflow Requirements - Oracle SuperCluster T5-8 Owner's Manual

Table of Contents

Advertisement

"Perforated Floor Tiles" on page 110

Environmental Requirements

Condition
Temperature
Relative humidity
Altitude
Except in China where regulations may limit installations to a maximum altitude of 2000 m (6560 ft.).
Related Information
"Heat Dissipation and Airflow Requirements" on page 107
"Perforated Floor Tiles" on page 110

Heat Dissipation and Airflow Requirements

The following table lists the maximum rate of heat released from a system. In order to cool the
system properly, ensure that adequate airflow travels through the system.
TABLE 17
Comments
Maximum
Typical
TABLE 18
Configuration
EF Quarter rack
Operating Requirement
5 to 32°C (41 to 89.6°F)
10 to 90% relative humidity,
noncondensing
3048 m (10000 ft.) maximum
SuperCluster T5-8 Specifications
Full Rack
54,405 BTU/hour
57.4 kJ/hour
45,422 BTU/hour
47.8 kJ/hour
Exadata X5-2 Expansion Rack Specifications
Non-operating Requirement
-40 to 70°C (-40 to 158°F).
Up to 93% relative humidity.
12000 m (40000 ft.).
BTU/Hour
Maximum
12,362
Preparing for Cooling
Comments
For optimal rack cooling, data
center temperatures from 21 to
23°C (70 to 47°F)
For optimal data center
rack cooling, 45 to 50%,
noncondensing
Ambient temperature is de-rated
by 1 degree Celsius per 300 m
above 900 m altitude above sea
level
Half Rack
31,013 BTU/hour
32.69 kJ/hour
25,591 BTU/hour
26.97 kJ/hour
kj/Hour
13,042
Preparing the Site
107