Device overview
8.4 Air-cooled Active Line Modules for the grid infeed, chassis format
8.4.3.6

X42 terminal strip

Table 8- 5
Terminal strip X42 voltage supply for Control Unit, Sensor Module and Terminal Module
Terminal
1
2
3
4
Max. connectable cross-section 2.5 mm
Note
Connection options for terminal strip X42
The terminal strip is not intended to freely provide a 24 V DC supply (for example for
supplying additional components on the plant or system side), as the voltage supply of the
Control Interface Module could also be overloaded and the correct functioning could thus be
compromised.
8.4.3.7

DRIVE-CLiQ interfaces X400, X401, X402

Table 8- 6
DRIVE-CLiQ interfaces X400, X401, X402
PIN
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
154
Function
P24L
M
2
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Technical data
Voltage supply for Control Unit, Sensor Module, and
Terminal Module (18 to 28.8 V)
Maximum load current: 3 A
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground