Logic Group

L180 [Stp Logic 0]
L181 [Stp Logic 1]
L182 [Stp Logic 2]
L183 [Stp Logic 3]
L184 [Stp Logic 4]
L185 [Stp Logic 5]
L186 [Stp Logic 6]
L187 [Stp Logic 7]
Stop drive before changing this parameter.
Values
Default:
Min/Max:
Display
See
Appendix D
and
Appendix E
for more information on applying Step Logic and Position StepLogic.
Parameters L180...L187 are only active if P047, P049, or
frequency commands. Each "step" can be based on time, status of a Logic input or a combination of time and the status of a Logic input.
Digits 1...4 for each [Stp Logic x] parameter must be programmed according to the desired profile. A Logic input is established by setting a digital input, parameters t062, t063,
t065...t068
[DigIn TermBlk xx] to 24 "Logic In 1" and/or 25 "Logic In 2" or by using Bits 6 and 7 of
A time interval between steps can be programmed using parameters
The speed for any step is programmed using parameters
Step StepLogic Parameter Related Preset Frequency Parameter
(Can be activated independent of StepLogic Parameters)
0
L180 [Stp Logic 0]
A410 [Preset Freq 0]
1
L181 [Stp Logic 1]
A411 [Preset Freq 1]
2
L182 [Stp Logic 2]
A412 [Preset Freq 2]
3
L183 [Stp Logic 3]
A413 [Preset Freq 3]
4
L184 [Stp Logic 4]
A414 [Preset Freq 4]
5
L185 [Stp Logic 5]
A415 [Preset Freq 5]
6
L186 [Stp Logic 6]
A416 [Preset Freq 6]
7
L187 [Stp Logic 7]
A417 [Preset Freq 7]
The position for any step is programmed using parameters
Step StepLogic Position Parameter
0
L200 [Step Units 0] & L201 [Step Units F 0]
1
L202 [Step Units 1] & L203 [Step Units F 1]
2
L204 [Step Units 2] & L205 [Step Units F 2]
3
L206 [Step Units 3] & L207 [Step Units F 3]
4
L208 [Step Units 4] & L209 [Step Units F 4]
5
L210 [Step Units 5] & L211 [Step Units F 5]
6
L212 [Step Units 6] & L213 [Step Units F 6]
7
L214 [Step Units 7] & L215 [Step Units F 7]
How StepLogic Works
The StepLogic sequence begins with a valid start command. A normal sequence always begins with L180 [Stp Logic 0].
Digit 1: Logic for next step
This digit defines the logic for the next step. When the condition is met the program advances to the next step. Step 0 follows Step 7. Example: Digit 1 is set to 3. When "Logic In 2"
becomes active, the program advances to the next step.
Digit 2: Logic to jump to a different step
For all settings other than F, when the condition is met, the program overrides Digit 0 and jumps to the step defined by Digit 3.
Digit 3: Different step to jump
When the condition for Digit 2 is met, this digit setting determines the next step or to end the program.
Digit 4: Step settings
This digit defines additional characteristics of each step.
Any StepLogic parameter can be programmed to control a relay or opto output, but you can not control different outputs based on the condition of different StepLogic commands.
00F1
0000/FAFF
0001
P051
[Speed Referencex] is set to 13 "Step Logic" or 16 "Positioning". These parameters can be used to create a custom profile of
L190...L197
[Stp Logic Time x]. See the table below for related parameters.
A410...A417
[Preset Freq x].
Related StepLogic Time Parameter
(Active when L180...L187 Digit 1 or 2 are set to 1, b, C, d or E)
L190 [Stp Logic Time 0]
L191 [Stp Logic Time 1]
L192 [Stp Logic Time 2]
L193 [Stp Logic Time 3]
L194 [Stp Logic Time 4]
L195 [Stp Logic Time 5]
L196 [Stp Logic Time 6]
L197 [Stp Logic Time 7]
L200...L214
[Step Units x].
Rockwell Automation Publication 520-UM001A-EN-E - February 2013
A560
[Enh Control Word].
Programming and Parameters
Chapter 3
Related Parameter(s):
91