Chapter 3
Programming and Parameters
C144 [EN Idle Flt Actn]
Sets the action that the EtherNet/IP interface and drive takes if the EtherNet/IP interface detects that the scanner is idle because the controller was switched to program mode.
ATTENTION: Risk of injury or equipment damage exists. Parameter C144 [EN Idle Flt Actn] lets you determine the action of the EtherNet/IP interface and
connected drive if the scanner is idle. By default, this parameter faults the drive. you can set this parameter so that the drive continues to run. Precautions
should be taken to ensure that the setting of this parameter does not create a risk of injury or equipment damage. When commissioning the drive, verify that
your system responds correctly to various situations (for example, a disconnected drive).
Options
0 "Fault" (Default)
1 "Stop"
2 "Zero Data"
3 "Hold Last"
4 "Send Flt Cfg"
C145 [EN Flt Cfg Logic]
32
32 bit parameter.
Sets the Logic Command data that is sent to the drive if any of the following is true:
C143
[EN Comm Flt Actn] is set to 4 "Send Flt Cfg" and communications are disrupted.
C144
[EN Idle Flt Actn] is set to 4 "Send Flt Cfg" and the scanner is put into Program or Test mode.
See
Writing (06) Logic Command Data on page 175
Values
Default:
Min/Max:
Display:
C146 [EN Flt Cfg Ref]
32
32 bit parameter.
Sets the Reference data that is sent to the drive if any of the following is true:
C143
[EN Comm Flt Actn] is set to 4 "Send Flt Cfg" and communications are disrupted.
C144
[EN Idle Flt Actn] is set to 4 "Send Flt Cfg" and the scanner is put into Program or Test mode.
Values
Default:
Min/Max:
Display:
C147 [EN Flt Cfg DL 1]
C148 [EN Flt Cfg DL 2]
C149 [EN Flt Cfg DL 3]
C150 [EN Flt Cfg DL 4]
Sets the Ethernet Datalink Input data that is sent to the drive if any of the following is true:
C143
[EN Comm Flt Actn] is set to 4 "Send Flt Cfg" and communications are disrupted.
C144
[EN Idle Flt Actn] is set to 4 "Send Flt Cfg" and the scanner is put into Program or Test mode.
Values
Default:
Min/Max:
Display:
C153 [EN Data In 1]
C154 [EN Data In 2]
C155 [EN Data In 3]
C156 [EN Data In 4]
Datalink parameter number whose value is written from the embedded EtherNet/IP data table.
Values
Default:
Min/Max:
Display:
88
Communications Group (continued)
Drive stops per P045 [Stop Mode] setting.
Note: The Reference and Datalink values transmitted to the drive will be set to "0".
Note: The Reference and Datalink values transmitted to the drive will be held at their last value.
Note: The Logic, Reference, and Datalink values will be transmitted to the drive as configured in C145, C146, and C147...C150.
for more information.
0000 0000 0000 0000
0000 0000 0000 0000/1111 1111 1111 1111
0000 0000 0000 0000
0
0/50000
1
0
0/65535
1
0
0/800
1
Rockwell Automation Publication 520-UM001A-EN-E - February 2013
Related Parameter(s): P045, C145, C146,
Related Parameter(s): C143,
Related Parameter(s): C143,
C147-C150
C144