Chapter 3
Programming and Parameters
A466 [PID 1 Preload]
A478 [PID 2 Preload]
Sets the value used to preload the integral component on start or enable.
Values
Default:
Min/Max:
Display:
A467 [PID 1 Invert Err]
A479 [PID 2 Invert Err]
Changes the sign of the PID error.
Options
0 "Normal" (Default)
1 "Inverted"
A481 [Process Disp Lo]
Sets the value displayed in
b010
[Process Display] when the drive is running at
Values
Default:
Min/Max:
Display:
A482 [Process Disp Hi]
Sets the value displayed in
b010
[Process Display] when the drive is running at
Values
Default:
Min/Max:
Display:
A483 [Testpoint Sel]
Used by Rockwell Automation field service personnel.
Values
Default:
Min/Max:
Display:
A484 [Current Limit 1]
Maximum output current allowed before current limiting occurs.
Values
Default:
Min/Max:
Display:
A485 [Current Limit 2]
Maximum output current allowed before current limiting occurs.
Values
Default:
Min/Max:
Display:
106
Advanced Program Group (continued)
0.0 Hz
0.0/500.0 Hz
0.1 Hz
P043
[Minimum Freq].
0.00
0.00/99.99
0.01
P044
[Maximum Freq].
0.00
0.00/99.99
0.01
400
0/FFFF
1
Drive Rated Amps x 1.5
0.0/(Drive Rated Amps x 1.8)
0.1 A
Drive Rated Amps x 1.1
0.0/(Drive Rated Amps x 1.8)
0.1 A
Rockwell Automation Publication 520-UM001A-EN-E - February 2013
Related Parameter(s): b010,
P043
Related Parameter(s): b010,
P044
Related Parameter(s):
P033
Related Parameter(s):
P033