Allen-Bradley PowerFlex 525 User Manual page 64

Adjustable frequency ac drive
Hide thumbs Also See for PowerFlex 525:
Table of Contents

Advertisement

Chapter 3
Programming and Parameters
b007 [Fault 1 Code]
b008 [Fault 2 Code]
b009 [Fault 3 Code]
A code that represents a drive fault. Codes appear in these parameters in the order they occur
See
Fault and Diagnostic Group
for more information.
Values
Default:
Min/Max:
Display:
b010 [Process Display]
32
32 bit parameter.
Output frequency scaled by [Process Disp Hi] and [Process Disp Lo].
Values
Default:
Min/Max:
Display:
b012 [Control Source]
Active source of the Start Command and Frequency Command. Normally defined by the settings of P046, P048,
See
Start and Speed Reference Control on page 39
Start Command Source
1 = Keypad
2 = DigIn TrmBlk (Parameters t062,t063,t065-t068)
3 = Serial/DSI
4 = Network Opt
5 = EtherNet/IP
Frequency Command Source
00 = Other
01 = Drive Pot
02 = Keypad
03 = Serial/DSI
04 = Network Opt
05 = 0-10V Input
06 = 4-20mA Input
07 = Preset Freq (Parameters A410-A425)
08 = Anlg In Mult
09 = MOP
10 = Pulse Input
11 = PID1 Output
12 = PID2 Output
13 = Step Logic (Parameters L180-L187)
14 = Encoder
15 = EtherNet/IP
16 = Positioning
Frequency Command Source
0 = Other (Digit 2 & 3 are used. Digit 4 is not shown.)
1 = Jog
2 = Purge
Not Used
Values
Default:
Min/Max:
Display:
64
Basic Display Group (continued)
Read Only
F0/F127
F0
Read Only
0/9999
1
for more information.
Example
Digit 1
Display reads... Description
2004
113
155
Digit 2 & 3
052
011
Digit 4
Read Only
0000/2165
0000
Rockwell Automation Publication 520-UM001A-EN-E - February 2013
(b007
[Fault 1 Code] = the most recent fault). Repetitive faults are only recorded once.
Related Parameter(s): P046, P047, P048, P049, P050, P051,
P050
[Start Source x] and P047, P049,
Start source comes from Network Opt and Frequency source is Purge.
Start source comes from Serial/DSI and Frequency source comes from PID1 Output.
Start source and Frequency source comes from EtherNet/IP.
Start source comes from DigIn TrmBlk and Frequency source from 0-10V Input.
Start source comes from Keypad and Frequency source comes from Drive Pot.
Related Parameter(s):
F604-F610
Related Parameter(s): b001, A481,
t062, t063, t065-t068, L180-L187,
A410-A425
P051
[Speed Referencex].
A482

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents